ADEMCO 4208U
FEATURES
The ADEMCO 4208U is a V-Plex
with ADEMCO controls that support V-Plex (polling loop)
devices. Characteristics of this device include:
Can be optionally powered from the control panel aux.
power supply to reduce the amount of current draw from
the polling loop. NOTE: The 4208U cannot be used with an
external power supply for commercial fire applications.
Uniquely identifies 8 EOLR supervised zones (all zones use
10k resistors, supplied).
DIP Switches can be used to set zone numbers or serial
numbers.
When used in the serial number mode, each serial number
in the selected group can be assigned to any zone number.
Loops A & B can be programmed for fast (10msec)
response.
Tamper protected.
1. For all fire (NFPA) and UL Commercial Burglary
installations, the 4208U must be tamper protected or
mounted in a tamper-protected cabinet.
2. Refer to the control panel installation instructions for
specific programming/installation requirements.
U L
3. All circuits are supervised and power-limited.
4. Use only 14-22 AWG wire.
5. Close contact type initiating devices.
6. All zones are Class B, Style B.
7. Voltage rating all zones: 11VDC max., 1.5mA max.
MOUNTING
1. Power should be disconnected before proceeding.

2.
Be sure to mount the 4208U before making any wiring
connections.
When mounted remotely, tamper protection is required. Holes
on the back of the module's housing permit it to be mounted
horizontally or vertically. Wires can exit from the side or the
breakout on the back of the housing.
protection, set DIP Switch 8 to OFF and attach the tamper
magnet (provided) (Figure 1) to the module inside cover. Be
sure to enable the expansion zone tamper option at the control
(program field 724 = 0). If the module's cover is removed, the
magnet attached to the cover (positioned near the reed switch)
will cause a tamper signal to be sent to the control for every
active zone on the 4208U module. When the installation is
complete, install the cover and affix the Serial Number and
Zone Assignment Tables to the inside cover of the control.
When mounted inside the cabinet with the control, the 4208U
should be mounted horizontally and does not need tamper
protection, provided the cabinet is supervised.
screws into the raised metal tabs leaving the heads app. 1/8"
exposed, and then hang the 4208U using the two slots on the
back.
WIRING
For CE installations ADEMCO N6361 EMI suppression
C E
bead is required.
Instructions for wire routing instructions.
Polling loop and protection loop wires can be brought in either
through the back or front of the unit by removing the
knockouts.
INSTALLATION AND SETUP GUIDE
®
eight-zone expander for use
To enable tamper
Insert two
Refer to the N6361 Installation
Universal V-Plex
Use 22 gauge twisted pair wire for polling loop connections. All
protection loops use 10k EOL resistors (included). A maximum
resistance of 300 ohms is allowed on protection loops (excluding
EOLR). See Figure 2 for all connections.
Keep in mind that connections to the polling loop are always
required, while power supply connections are optional.
Figure 1. Tamper Magnet Installation
DIP SWITCH SETTINGS
Serial Number Mode:
In the serial number mode, the DIP Switches on the 4208U are
used to assign the unit to a group of 8 serial numbers. You can
assign any serial number to any zone number (except hardwire
zone numbers of the control) and you do not lose zone numbers if
you don't use all eight loops on the 4208U. Follow steps below
using Table 2 for DIP Switch settings.
Zone Assignment Mode:
In the zone assignment mode, the DIP Switches on the 4208U are
used to assign the unit to a group of 8 consecutive zones. These
zone numbers, once designated for the 4208U, cannot be used for
anything else, even if you don't use all 8. Follow the steps below
using Table 1 for DIP Switch settings.
Note: Zone Assignment Mode should only be used on panels that
DO NOT support Serial Mode.
®
Eight Zone Expander
1. INSERT BOTTOM TABS FIRST.
2. ENGAGE TOP WITH CLIP.

Advertisement

loading

Summary of Contents for Honeywell ADEMCO 4208U

  • Page 1 FEATURES ® Use 22 gauge twisted pair wire for polling loop connections. All The ADEMCO 4208U is a V-Plex eight-zone expander for use protection loops use 10k EOL resistors (included). A maximum with ADEMCO controls that support V-Plex (polling loop) resistance of 300 ohms is allowed on protection loops (excluding devices.
  • Page 2 POSITION 1: SELECT RESPONSE TIME 4208U FOR LOOPS A and B (SHOWN ON = SLOW). DIP Switches ( ) GND OPTIONAL AUX. POSITIONS 2-5: SELECT THE 8 SENSOR POWER INPUT. DEVICE GROUP ADDRESS SEE NOTE 1. (+) 12V (SHOWN ON, ON, ON, OFF = 2nd GROUP SELECTION).
  • Page 3 When prompted to learn the serial number for a particular Set the DIP switches on the 4208U as instructed below (see zone, you may either enter it manually through the keypad, Figure 3): through COMPASS Downloader, or “learn” it by momentarily Select fast/slow response for loops A and B using DIP faulting (shorting) the terminals of that zone as required by the Switch 1: Fast = OFF (10msec) Slow = ON (400msec).
  • Page 4 For the latest warranty information, please go to: www.honeywell.com/security/hsc/resources/wa. Patents Warranty MyWebTech For patent information, see www.honeywell.com/patents 2 Corporate Center Drive, Suite 100 P.O. Box 9040, Melville, NY 11747 © Copyright 2009 Honeywell International Inc. www.security.honeywell.com ÊN8215V8}Š N8215V8 2/11 Rev. B...