CP 343-
1


SIMATIC NET
S7-300 - Industrial Ethernet /
PROFINET
CP 343-1
Manual
Manual Part B
10/2012
C79000−G8976−C201-07
___________________
Preface
___________________
Properties / services
___________________
Performance data
___________________
Requirements for use
___________________
LEDs
Installation, connecting up
___________________
and commissioning
Notes on configuration and
___________________
operation
___________________
Service and maintenance
___________________
Technical specifications
___________________
Approvals
___________________
References
1
2
3
4
5
6
7
8
A
B

Advertisement

Table of Contents
loading

Summary of Contents for Siemens PROFINET CP 343-1

  • Page 1 ___________________ CP 343- Preface ___________________ Properties / services ___________________ Performance data SIMATIC NET ___________________ Requirements for use S7-300 - Industrial Ethernet / ___________________ PROFINET LEDs CP 343-1 Installation, connecting up ___________________ and commissioning Manual Notes on configuration and ___________________ operation ___________________ Service and maintenance ___________________...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Preface

    Preface Legend: ① LEDs ② Under the front panel: PROFINET interface, 2 x 8-pin RJ-45 jack ③ Under the front cover: - Socket for 24 VDC power supply - Slider for setting the ground connector ④ Order number ⑤ Under the front panel: printed text with MAC addresses and firmware version ⑥...
  • Page 4 Preface Note Names  In this document, the term "CP" is used instead of the full product name.  The name STEP 7 is used for the configuration tool instead of the names STEP 7 V5.5 and STEP 7 Professional. Innovations and compatibility with the predecessor product Note You will find the new functions of the module in the section Enhanced functions (Page 9).
  • Page 5 – Programmed connections and IP configuration – PROFINET IO Current manual release on the Internet You will also find the current version of this manual on the Internet pages of Siemens Automation Customer Support under the following entry ID: 24485272 (http://support.automation.siemens.com/WW/view/en/24485272) CP documentation in the Manual Collection (order no.
  • Page 6 Security messages Note For its automation and drives product portfolio, Siemens provides IT security mechanisms to support secure operation of the plant/machine. Our products are continuously being further developed also taking into account the aspect of IT security. We therefore recommend that you regularly check for updates of our products and that you only use the latest versions.
  • Page 7: Table Of Contents

    Table of contents Preface ..............................3 Properties / services ..........................9 Application............................9 Enhanced functions ........................9 Communication services......................10 Other services ..........................12 The CP as Web server.........................13 Performance data ............................ 15 Transmission and reaction times ....................15 Number of possible Ethernet/PROFINET connections..............15 Characteristics of S7 communication ..................16 Characteristic data of the SEND/RECEIVE Interface ..............17 PROFINET IO characteristic data....................18 Characteristic data of the integrated switch.................21...
  • Page 8 Table of contents IP configuration ........................... 46 6.6.1 Detection of double IP addressing in the network ..............46 6.6.2 Obtain IP address vie DHCP: CP STOP on expiry of the lease ..........46 6.6.3 Configured S7 connections cannot be operated if the IP address is assigned over DHCP ..47 6.6.4 IP access protection using the IP access control list with a PROFINET IO device ....
  • Page 9: Properties / Services

    Properties / services Application The CP 343-1 communications processor is intended for operation in a SIMATIC S7-300, SIMATIC C7-300 automation system or SINUMERIK 840D power line. It allows the connection of the S7-300 to Industrial Ethernet and supports PROFINET IO. To integrate the CP in a linear bus or a ring, to connect a further Ethernet device or to use PROFINET media redundancy, a 2-port ERTEC real-time switch with autocrossing, autonegotiation and autosensing was integrated.
  • Page 10: Communication Services

    Enhanced functions of earlier firmware versions and predecessor modules You will find an overview of the earlier firmware versions and predecessor modules in the version history of the Industrial Ethernet CPs on the Internet pages of Siemens Automation Customer Support under the following entry ID: 56699406 (http://support.automation.siemens.com/WW/view/en/56699406)
  • Page 11 Properties / services 1.3 Communication services – Shared device Individual submodules of the CP as IO device can be assigned up to two PROFINET IO controllers in STEP 7 V5.5. Note the information on configuring PROFINET IO systems with shared IO devices in the "PROFINET System Description", see references, /13/ (Page 71).
  • Page 12: Other Services

    Properties / services 1.4 Other services Other services ● Media redundancy (MRP) Within an Ethernet network with a ring topology, the CP supports the media redundancy protocol MRP. You can assign the role of MRP client to the CP. ● Time-of-day synchronization over Industrial Ethernet Time-of-day synchronization can be configured in the following modes: –...
  • Page 13: The Cp As Web Server

    Properties / services 1.5 The CP as Web server ● Web diagnostics With the aid of Web diagnostics, you can read out the diagnostics data from a station connected via the CP to a PG/PC with a Web browser. This makes it possible to read the diagnostics buffers of the intelligent modules in the rack.
  • Page 14 Properties / services 1.5 The CP as Web server Diagnostics buffer entries When supplied, diagnostics buffer entries shown on diagnostics pages are always in English. This is the case whichever language you have selected to display the Web pages. How to download other language files to the CP and further information about Web diagnostics can be found in the general Part A of this manual.
  • Page 15: Performance Data

    Measured values of transmission and reaction times over Ethernet, PROFIBUS and PROFINET networks for a series of configurations can be found on the Internet at the following address: http://www.siemens.com/automation/pd (http://www.siemens.com/automation/pd) Number of possible Ethernet/PROFINET connections Maximum number of parallel connections...
  • Page 16: Characteristics Of S7 Communication

    Performance data 2.3 Characteristics of S7 communication ● Further TCP connections for Web diagnostics ● PROFINET IO – As PROFINET IO device: 1 PROFINET connection to a PROFINET IO controller – As shared device: 2 PROFINET connections to 2 PROFINET IO controllers –...
  • Page 17: Characteristic Data Of The Send/Receive Interface

    Measurements of transmission and reaction times in Ethernet, PROFIBUS and PROFINET networks for a series of configurations can be found on the Internet at the following address: 25209605 (http://support.automation.siemens.com/WW/view/en/25209605) Characteristic data of the SEND/RECEIVE Interface The SEND/RECEIVE interface provides access to communication over TCP, ISOonTCP, ISO transport and UDP connections.
  • Page 18: Profinet Io Characteristic Data

    Note Measurements of transmission and reaction times in Ethernet, PROFIBUS and PROFINET networks for a series of configurations can be found on the Internet at the following address: 25209605 (http://support.automation.siemens.com/WW/view/en/25209605) PROFINET IO characteristic data Possible modes with PROFINET IO In PROFINET IO, the CP can operate as a PROFINET IO device or as a PROFINET IO controller.
  • Page 19 Performance data 2.5 PROFINET IO characteristic data Characteristic Explanation / values 240 bytes Inputs  240 bytes Outputs  Size of the consistency area for a submodule 240 bytes Permitted number of CP 343-1 modules that can be used as PROFINET IO controllers within an S7-300 station Note: Regardless of the CP type (EX30, GX30, GX31 ...), only 1 CP may be a PROFINET IO controller.
  • Page 20 S7-300 CPU is decisive for the calculation of the reaction times in PROFINET IO. Note Measurements of transmission and reaction times in Ethernet, PROFIBUS and PROFINET networks for a series of configurations can be found on the Internet at the following address: 25209605 (http://support.automation.siemens.com/WW/view/en/25209605) CP 343-1 Manual, 10/2012, C79000−G8976−C201-07...
  • Page 21: Characteristic Data Of The Integrated Switch

    Performance data 2.6 Characteristic data of the integrated switch Characteristic data of the integrated switch Learning addresses / deleting addresses (aging time) The switch integrated in the CP (PROFINET interface) reads the source addresses included in the data packets. The switch therefore learns the addresses of the end devices connected via a port.
  • Page 22 Performance data 2.6 Characteristic data of the integrated switch CP 343-1 Manual, 10/2012, C79000−G8976−C201-07...
  • Page 23: Requirements For Use

    Requirements for use Operation in control device families The CP can be operated in the following device families: ● S7-300 stations with the following CPU types: – Standard – Compact – Modular ● C7 compact units in C7 packaging system ●...
  • Page 24 Requirements for use 3.1 Operation in control device families Order number CPU 314 6ES7 314-1AE00-0AB0 6ES7 314-1AE04-0AB0 6ES7 314-1AE84-0AB0 6ES7 314-1AF10-0AB0 6ES7 314-1AF11-0AB0 6ES7 314-1AG13-0AB0 CPU 314 IFM 6ES7 314-5AE03-0AB0 6ES7 314-5AE10-0AB0 6ES7 314-5AE82-0AB0 6ES7 314-5AE83-0AB0 CPU 314C-2 DP 6ES7 314-6CF00-0AB0 6ES7 314-6CF01-0AB0 6ES7 314-6CF02-0AB0 6ES7 314-6CG03-0AB0...
  • Page 25 Requirements for use 3.1 Operation in control device families Order number CPU 319-3 PN/DP 6ES7 318-3EL00-0AB0 6ES7 318-3EL01-0AB0 CPU 319-3F PN/DP 6ES7 318-3FL00-0AB0 6ES7 318-3FL01-0AB0 Table 3- 2 Use of the CP with C7 control systems Order number C7-613 6ES7 613-1CA01-0AE03 6ES7 613-1CA02-0AE3 CPU 614 6ES7 614-1AH03-0AB3...
  • Page 26: Project Engineering

    Locating the support package You can install the support package from your local file system if it is already stored there or from the Internet pages of Siemens Automation Customer Support. ● STEP 7 V5.5 You will find the support package (HSP) on the Internet at the following address: 23183356 (http://support.automation.siemens.com/WW/view/en/23183356)
  • Page 27: Programming

    GSDML file for configuration in third-party systems You will find the GSDML file for the CP described here on the Internet under the following entry ID (entry type "Download"): 19698639 (http://support.automation.siemens.com/WW/view/en/19698639) Programming Program blocks For some communications services, there are preprogrammed program blocks (FCs / FBs) available as the interface in your STEP 7 user program.
  • Page 28 Requirements for use 3.3 Programming CP 343-1 Manual, 10/2012, C79000−G8976−C201-07...
  • Page 29: Leds

    LEDs LEDs The display on the front panel consists of the following LEDs that indicate the operating mode and communications status. Figure 4-1 LEDs of the CP 343-1 The LEDs have the following meaning: ● SF: Group error ● BF: Bus fault on Ethernet interface ●...
  • Page 30 LEDs LEDs for displaying the operating mode The different combinations of the LEDs on the front panel indicate the status: Table 4- 1 LEDs: SF, BF, RUN, STOP SF(red) BF (red) RUN (green) STOP (yellow) CP operating mode Starting up after power "ON" ...
  • Page 31 LEDs The "MAINT" LED Note When the "MAINT" LED lights up, important error messages and/or diagnostics interrupts have occurred. The CP continues in RUN mode. Check the entries in the diagnostics buffer of the device. LEDs for displaying the CP communications status In addition to the LEDs that signal the CP state, the following LEDs provide information about the status of the CP interface to Industrial Ethernet.
  • Page 32 LEDs CP 343-1 Manual, 10/2012, C79000−G8976−C201-07...
  • Page 33: Installation, Connecting Up And Commissioning

    Installation, connecting up and commissioning Important notes on using the device Safety notices on the use of the device The following safety notices must be adhered to when setting up and operating the device and during all associated work such as installation, connecting up, replacing devices or opening the device.
  • Page 34 Installation, connecting up and commissioning 5.1 Important notes on using the device WARNING Replacing components EXPLOSION HAZARD SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2 OR ZONE 2. WARNING Requirements for the cabinet/enclosure When used in hazardous environments corresponding to Class I, Division 2 or Class I, Zone 2, the device must be installed in a cabinet or a suitable enclosure.
  • Page 35: Installing The Cp, Connecting Power And Ground

    Installation, connecting up and commissioning 5.2 Installing the CP, connecting power and ground WARNING Suitable cables for temperatures in excess of 70 °C If the cable or conduit entry point exceeds 70°C or the branching point of conductors exceeds 80°C, special precautions must be taken. If the device is operated at ambient temperatures above 50°C, the permitted temperature range of the selected cable must be suitable for the temperatures actually measured.
  • Page 36 Installation, connecting up and commissioning 5.2 Installing the CP, connecting power and ground Legend: Attachment to Industrial Ethernet (PROFINET interface): 2 x 8pin RJ45 jack Connecting the power supply Slider for setting the chassis ground connection Figure 5-1 Connectors of the CP Ground/chassis ground concept Note Note the instructions regarding the grounding and chassis ground concept in the...
  • Page 37 Installation, connecting up and commissioning 5.2 Installing the CP, connecting power and ground Installing and connecting up NOTICE Ensuring ventilation During installation, make sure that the upper and lower ventilation slits of the module are not obstructed and good ventilation is possible. 1.
  • Page 38: Connecting The Cp To Ethernet

    Installation, connecting up and commissioning 5.3 Connecting the CP to Ethernet The PG / PC requires a LAN attachment, for example via a CP 1613 or CP 1411 and must have the necessary software (for example the S71613 package or SOFTNET IE). The TCP/IP protocol must be installed.
  • Page 39 Installation, connecting up and commissioning 5.3 Connecting the CP to Ethernet Figure 5-2 Connecting switches Note MRP configuration With an MRP configuration, keep to the setup guidelines for MRP. You will find examples of network attachments in the general Part A of this manual, see /1/ (Page 68).
  • Page 40 Installation, connecting up and commissioning 5.3 Connecting the CP to Ethernet CP 343-1 Manual, 10/2012, C79000−G8976−C201-07...
  • Page 41: Notes On Configuration And Operation

    Notes on configuration and operation NOTICE The front panel must be kept closed during operation. Project engineering Project engineering To set up the CP for communication services, read the information on configuring in the sections Project engineering (Page 26) and Replacing a module without a programming device (Page 59).
  • Page 42: Network Settings

    Notes on configuration and operation 6.3 Network settings ● The following functions remain enabled: – Downloading the configuration data and diagnostics of the CP System connections for configuration, diagnostics and PG channel routing still exist. – Web diagnostics (HTTP access) –...
  • Page 43 Notes on configuration and operation 6.3 Network settings STEP 7 special diagnostics and Web diagnostics display the network setting Diagnostics of the port settings for the CP described here is possible using the entries in the diagnostics buffer using Web diagnostics, SNMP, STEP 7 diagnostics, and the LED displays.
  • Page 44: Influence Of Mpi On Connections Via Industrial Ethernet

    Notes on configuration and operation 6.4 Influence of MPI on connections via Industrial Ethernet ● Recommendation: Change "individual network settings" only over MPI If you modify the LAN settings in the properties dialog of the CP in the “Port Parameters" tab, these changes will be adopted by the CP and activated when the configuration data is downloaded to the CP.
  • Page 45: Profinet Io

    ("switch depth"), the update time and the MC/BC frame lengths. You will find further information about the influencing factors as well as possible solutions in: 29104898 (http://support.automation.siemens.com/WW/view/en/29104898) CP 343-1 Manual, 10/2012, C79000−G8976−C201-07...
  • Page 46: Ip Configuration

    Notes on configuration and operation 6.6 IP configuration IP configuration 6.6.1 Detection of double IP addressing in the network To save you timeconsuming troubleshooting in the network, the CP detects double addressing in the network. The reaction of the CP when double addressing is detected varies as follows: ●...
  • Page 47: Configured S7 Connections Cannot Be Operated If The Ip Address Is Assigned Over Dhcp

    Notes on configuration and operation 6.7 Media redundancy 6.6.3 Configured S7 connections cannot be operated if the IP address is assigned over DHCP Note If you obtain the IP address using DHCP, any S7 connections you may have configured will not work.
  • Page 48: Snmp Agent

    SNMP client you are using (example of an SNMP client: SNMP OPC server from SIMATIC NET). You will find more information on MIBs on the following SIMATIC NET Internet page: 15177711 (http://support.automation.siemens.com/WW/news/en/8797900) Supported MIBs The CP supports the following groups of MIB objects of the standard MIB II according to RFC1213: ●...
  • Page 49 If you use an SNMP tool, you will find the MIB files relevant to the CP in the STEP 7 installation in the following folder: <Drive>\<Installation folder>\Siemens\Step7\S7DATA\snmp\mib For the Automation System MIB, for example, these are the following files: CP 343-1...
  • Page 50: Possible Security Gaps On Standard It Interfaces: Preventing Unauthorized Access

    If you have questions on the use of firewall systems and IT security, please contact your local Siemens office or representative. You will find the address in the SIMATIC catalog IK PI or on the Internet at the following address: (http://www.automation.siemens.com/partner/guisearch.asp)
  • Page 51: Programmed Communication Connections

    Notes on configuration and operation 6.11 Programmed communication connections 6.11 Programmed communication connections 6.11.1 Programmed communication connections with FB55 IP_CONFIG Downloading the configuration using FB55 IP_CONFIG IP_CONFIG allows programcontrolled transfer of the configuration data. Note If the CP is in PG STOP mode and the configuration is downloaded using IP_CONFIG, the CP then changes automatically to RUN.
  • Page 52: Permitted Length Of Icmp Packets

    Notes on configuration and operation 6.12 Permitted length of ICMP packets How to configure IP access protection is described in the general part of this manual /1/ (Page 68). 6.12 Permitted length of ICMP packets Permitted length of ICMP packets Pings with a packet size of more than 1000 bytes are evaluated as an attack and filtered by the CP.
  • Page 53: Service And Maintenance

    Service and maintenance Memory reset / reset to factory defaults If the CP was configured with the "Status-dependent" protection level, the following two functions are available only when the CPU is in STOP mode. You will find a setting in the properties dialog of STEP 7 >...
  • Page 54: Memory Reset - Acl

    Service and maintenance 7.2 Memory reset - ACL ● Reset to factory settings – In STEP 7 V5.5 with the menu command "PLC" > "Edit Ethernet Node..." > Select CP > "OK" > "Reset to Factory Defaults" – In STEP 7 special diagnostics with the "Operating Mode" > "Reset to Factory Settings" menu command –...
  • Page 55: Replacing A Module

    Service and maintenance 7.4 Replacing a module ● Via the update center in the Web diagnostics of the CP With this method, the CP remains in RUN mode. You can reach the update center using Web diagnostics. Requirement: The option "Firmware download via Web" is selected in the configuration. Both options for loading the firmware are described in the manual Part A, see /1/ (Page 68).
  • Page 56: Module Replacement / Upgrading

    Service and maintenance 7.4 Replacing a module ● Upgrading (module replacement with compatible functions) Describes the situation when the module described here can be used instead of an older module as long as adaptations are made to the configuration. Here, the previously used CP needs to be replaced in the configuration by the new CP.
  • Page 57  AG_UNLOCK (as of V4.0) Note Always use the latest block versions for new user programs. You will find information on the current block versions and the current blocks for downloading on the Internet under: 8797900 (http://support.automation.siemens.com/WW/news/en/8797900) CP 343-1 Manual, 10/2012, C79000−G8976−C201-07...
  • Page 58 Service and maintenance 7.4 Replacing a module Module replacement Please follow the procedure below when replacing an older module with the module described here: Table 7- 1 Replacing an older module Originally configured module Configuration procedure 6GK7 343-1EX21-0XE0 Case a: Configuration unchanged / module replacement 6GK7 343-1EX20-0XE0 If you have no requirements beyond what you had with the previous CP (for example configuration limits), you do not...
  • Page 59: Replacing A Module Without A Programming Device

    Service and maintenance 7.4 Replacing a module 7.4.3 Replacing a module without a programming device General procedure The configuration data of the CP is stored optionally on the CPU or CP. Replacing the CP with a module of the same type (identical order number) without a PG is only possible if the data is stored on the CPU.
  • Page 60 Service and maintenance 7.4 Replacing a module CP 343-1 Manual, 10/2012, C79000−G8976−C201-07...
  • Page 61: Technical Specifications

    Technical specifications Table 8- 1 Technical specifications Technical specifications Attachment to Industrial Ethernet Number 1 x PROFINET interface with 2port switch Execution Connector 2 x RJ-45 jacks Transmission rate 10 / 100 Mbps When working with PROFINET IO and cyclic transfer, the transmission speed of 100 Mbps full duplex is mandatory.
  • Page 62 Technical specifications For further data, refer to section Performance data (Page 15) In addition to this, all the information in the "SIMATIC S7-300 Automation System Module Data" see /12/ (Page 70) in the section "General Technical Specifications" on the topics listed below applies to the CP: ●...
  • Page 63: Approvals

    SIMATIC NET products are regularly submitted to the relevant authorities and approval centers for approvals relating to specific markets and applications. You will also find the current approvals for the product on the Internet pages of Siemens Automation Customer Support under the following entry ID: (http://support.automation.siemens.com/WW/view/en/10806075)
  • Page 64 – EN 61131–2 / IEC 61131–2 (programmable logic controllers, part 2: equipment requirements and verifications) The EC Declaration of Conformity is available for the responsible authorities according to the above-mentioned EC Directive at the following address: Siemens Aktiengesellschaft Industry Automation Industrielle Kommunikation SIMATIC NET Postfach 4848 D-90327 Nürnberg...
  • Page 65 Approvals cULus HAZ.LOC. approval Underwriters Laboratories Inc. cULus Listed 7RA9 IND. CONT. EQ. FOR HAZ. LOC.: ● UL 508 (Industrial Control Equipment) ● UL 1604 (Hazardous Location) ● CSA C22.2 No. 142 (Pocess Control Equipment) ● CSA C22.2 No. 213 (Hazardous Location) APPROVED for Use in: ●...
  • Page 66 Approvals CP 343-1 Manual, 10/2012, C79000−G8976−C201-07...
  • Page 67: References

    References Finding the SIMATIC NET documentation ● Catalogs You will find the order numbers for the Siemens products of relevance here in the following catalogs: – SIMATIC NET Industrial Communication / Industrial Identification, catalog IK PI – SIMATIC Products for Totally Integrated Automation and Micro Automation, catalog...
  • Page 68 SIMATIC NET S7 CPs for Industrial Ethernet Configuring and Commissioning Manual Part - General Application Configuration Manual Siemens AG (SIMATIC NET Manual Collection) On the Internet under the following entry ID: 30374198 (http://support.automation.siemens.com/WW/view/en/30374198) SIMATIC NET Version history / current downloads for the SIMATIC NET S7 CPs...
  • Page 69 References B.3 On programming SIMATIC Configuring Hardware and Connections with STEP 7 Siemens AG Part of the documentation package "STEP 7 Basic Knowledge" (Part of the online documentation in STEP 7) On programming Version history of the SIMATIC NET function blocks and functions for SIMATIC S7...
  • Page 70 References B.4 On installing and commissioning the CP SIMATIC NET Industrial Communication with PG/PC Volume 1 - Basics System manual Siemens AG (SIMATIC NET Manual Collection) On the Internet under following entry ID: 42783968 (http://support.automation.siemens.com/WW/view/de/42783968) SIMATIC NET Industrial Communication with PG/PC Volume 2 - Interfaces...
  • Page 71 Siemens AG (SIMATIC NET Manual Collection) On IT security /15/ You will find further information on IT security and on data security in industrial communication on the following Internet pages of Siemens AG: (http://www.automation.siemens.com/mcms/industrial-communication/en/ie/industrial- ethernet-security) CP 343-1 Manual, 10/2012, C79000−G8976−C201-07...
  • Page 72 B.7 On setting up and operating an Industrial Ethernet network On setting up and operating an Industrial Ethernet network /16/ SIMATIC NET Industrial Ethernet - Network Manual system manual Siemens AG Entry ID: 27069465 (http://support.automation.siemens.com/WW/view/en/27069465) SIMATIC and STEP 7 basics /17/ SIMATIC...
  • Page 73 References B.9 Other topics /20/ RFC 1006 (ISO Transport Service on top of the TCP Version: 3) Request For Comment http://www.ietf.org (http://www.ietf.org) /21/ RFC 793 (TCP) http://www.ietf.org (http://www.ietf.org) /22/ RFC 791 (IP) http://www.ietf.org (http://www.ietf.org) CP 343-1 Manual, 10/2012, C79000−G8976−C201-07...
  • Page 74 References B.9 Other topics CP 343-1 Manual, 10/2012, C79000−G8976−C201-07...
  • Page 75: Index

    Index MAC address, 4, 55 Manual Collection, 5 Abbreviation "EX", Addressing, 37 ATEX, 34 Open communications services, 5 Cabinet, 34 Cables for temperatures in excess of 70 °C, 35 Connection and system diagnostics, 5 Ping, 52 PROFIenergy, 9 Programmed connections and IP configuration, 5 Protection against transient voltage surges, 35 Diagnostics, 38 Download, 37...
  • Page 76 Index CP 343-1 Manual, 10/2012, C79000−G8976−C201-07...