Simatic net
industrial ethernet switches (38 pages)
Summary of Contents for Siemens SIMATIC NET S7-300
Page 1
Introduction Network topologies Product properties SIMATIC NET Installation S7-300 Compact Switch Module CSM 377 Maintenance and troubleshooting Approvals and markings Operating Instructions References Graphics 06/2022 A2B00073499-02...
Page 2
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
You will find the SIMATIC NET glossary here: • SIMATIC NET Manual Collection or product DVD The DVD ships with certain SIMATIC NET products. • On the Internet under the following address: 50305045 (https://support.industry.siemens.com/cs/ww/en/view/50305045) Security information Compact Switch Module CSM 377 Operating Instructions, 06/2022, A2B00073499-02...
(https://www.siemens.com/cert). Device defective If a fault develops, send the device to your SIEMENS representative for repair. Repairs on-site are not possible. Recycling and disposal The products are low in pollutants, can be recycled and meet the requirements of the WEEE directive 2012/19/EU for the disposal of electrical and electronic equipment.
Introduction 1.3 Introduction Introduction What is possible? The CSM 377 device allows the cost-effective installation of Industrial Ethernet bus or star structures with switching functionality. Note It is not possible to use the CSM 377 switch in a redundant ring because it does not support redundancy.
Network topologies Network topologies Switching technology allows extensive networks to be set up with numerous nodes and simplifies network expansion. Which topologies can be implemented? Linear (bus) and star topologies can be implemented with the compact switch module CSM 377. Note Make sure that the maximum permitted cable lengths for the relevant devices are not exceeded.
Page 10
Network topologies 2.1 Network topologies Star topology Figure 2-2 Star topology. Example with the CSM 377 Compact Switch Module CSM 377 Operating Instructions, 06/2022, A2B00073499-02...
Product properties Components of the product The CSM 377 compact switch module always ships with the following: • 2-pin terminal block (power supply) • Operating Instructions (on the CD) • CD Compact Switch Module CSM 377 Operating Instructions, 06/2022, A2B00073499-02...
Product properties 3.2 Unpacking and checking Unpacking and checking Unpacking, checking 1. Make sure that the package is complete. 2. Check all the parts for transport damage. WARNING Do not use any parts that show evidence of damage! Compact Switch Module CSM 377 Operating Instructions, 06/2022, A2B00073499-02...
Product properties 3.3 CSM 377 product characteristics CSM 377 product characteristics Possible attachments The CSM 377 has four RJ-45 jacks for the connection of end devices or other network segments. Figure 3-1 Compact Switch Module CSM 377 Compact Switch Module CSM 377 Operating Instructions, 06/2022, A2B00073499-02...
Product properties 3.4 TP ports TP ports Connector pinout On the CSM 377, the TP ports are implemented as RJ-45 sockets with MDI-X assignment (Medium Dependent Interface–Autocrossover) of a network component. Figure 3-2 RJ-45 jack Table 3-1 Pin assignment of the RJ-45 jack Pin number Assignment Pin 8...
Page 15
Product properties 3.4 TP ports Autonegotiation Autonegotiation means the automatic detection of the functionality of the port at the opposite end. Using autonegotiation, network components or end devices can detect the functionality available at the port of a partner device allowing automatic configuration of different types of device.
Product properties 3.5 Displays Displays Power indicator (green LED) The status of the power supply is indicated by a green LED: Status Meaning LED lit green Power supply is connected LED not lit Power supply is not connected or <14 V Also see the <<Note>>...
Product properties 3.6 Technical specifications Technical specifications Technical specifications of the CSM 377 Connectors Attachment of end devices or network components 4 x RJ-45 sockets with MDI-X pinning 10/100 Mbps over twisted pair (half/ full duplex), floating Connector for power supply 2-terminal plug-in block Electrical data Power supply...
Page 18
Product properties 3.6 Technical specifications Permitted ambient conditions Weight in g Installation options S7-300 mounting rail Order numbers CSM 377 6GK7377-1AA00-0AA0 "Industrial Ethernet TP and Fiber Optic Networks" 6GK1970-1BA10-0AA0 manual TP Cord RJ45/RJ45 0.5 m 6XV1850-2GE50 IE FC Stripping Tool 6GK1901-1GA00 IE FC blade cassettes 6GK1901-1GB00...
Installation CAUTION To prevent injury and damage, read the manual before using the device. Compact Switch Module CSM 377 Operating Instructions, 06/2022, A2B00073499-02...
Installation 4.1 Important notes on using the device Important notes on using the device Read the safety notices Note the following safety notices. These relate to the entire working life of the device. WARNING If a device is operated in an ambient temperature of more than 55 °C, the temperature of the device enclosure may be higher than 70 °C.
Page 21
Installation 4.1 Important notes on using the device WARNING The device is intended for indoor use only. WARNING The device may only be operated in an environment of contamination class 1 or 2 (see EN/IEC 60664-1, GB/T 16935.1). WARNING When used in hazardous environments corresponding to Class I, Division 2 or Class I, Zone 2, the device must be installed in a cabinet or a suitable enclosure.
Page 22
Installation 4.1 Important notes on using the device WARNING Unprotected cable ends There is a risk of explosion due to unprotected cable ends in hazardous areas. • Protect unused cable ends according to IEC/EN 60079-14. WARNING Improper installation of shielded cables There is a risk of explosion due to equalizing currents between the hazardous area and the non- hazardous area.
Page 23
Installation 4.1 Important notes on using the device WARNING Transient overvoltages Take measures to prevent transient overvoltages of more than 40% of the rated voltage (or more than 119 V). This is the case if you only operate devices with SELV (safety extra-low voltage).
Installation 4.2 Installation Installation Type of mounting The Compact Switch Module CSM 377 is intended exclusively for mounting on a SIMATIC S7‑300 mounting rail. Note When installing and operating the device, keep to the installation instructions and safety-related notices as described here and in the manual SIMATIC NET Industrial Ethernet Twisted Pair and Fiber Optic Networks /1/.
Installation 4.3 Installation on a standard rail Installation on a standard rail Installation on a SIMATIC S7-300 standard rail Note The CSM 377 does not have a feedthrough for the backplane bus. It must therefore be mounted either at the start or end of the station! 1.
Installation 4.4 Power supply Power supply Power supply The power supply is connected using a 2-terminal plug-in block. The power supply is connected over a high resistance to the S7 mounting rail to allow an ungrounded set up. The power supply is non-floating.
Page 27
Installation 4.4 Power supply WARNING Power supply The device is designed for operation with a directly connectable safety extra low voltage (SELV) from a limited power source (LPS). The power supply therefore needs to meet at least one of the following conditions: •...
Installation 4.5 Grounding Grounding S7 standard rail The device is grounded over its rear panel and the neck of the screw. Compact Switch Module CSM 377 Operating Instructions, 06/2022, A2B00073499-02...
Installation 4.6 Fitting the IE FC RJ-45 Plug 180 Fitting the IE FC RJ-45 Plug 180 IE FC RJ45 Plug 180 The rugged node connectors are designed for industry with PROFINET-compliant connectors and provide additional strain and bending relief with a locking mechanism on the casing. Assembly of the IE FC RJ45 Plug 180 to the IE FC Standard Cable For information on assembling an IE FC RJ45 Plug 180 on a SIMATIC NET Industrial Ethernet FastConnect cable, please refer to the instructions supplied with the IE FC RJ45 Plug.
Page 30
Installation 4.6 Fitting the IE FC RJ-45 Plug 180 With its tight fit and locking mechanism with the PROFINET-compliant male connector IE FC RJ45 Plug 180, the securing collar on the TP port of the CSM 377 ensures a rugged node attachment that provides strain and bending relief for the twisted pair jack.
Installation 4.7 Disassembly Disassembly WARNING Improper disassembly Improper disassembly may result in a risk of explosion in hazardous areas. For proper disassembly, observe the following: • Before starting work, ensure that the electricity is switched off. • Secure remaining connections so that no damage can occur as a result of disassembly if the system is accidentally started up.
Maintenance and troubleshooting WARNING Unauthorized repair of devices in explosion-proof design Risk of explosion in hazardous areas • Repair work may only be performed by personnel authorized by Siemens. WARNING Impermissible accessories and spare parts Risk of explosion in hazardous areas •...
L-LED and all port LEDs go off. The functionality of the CSM 377 is no longer available. Device defective If a fault develops, please send the device to your SIEMENS service center for repair. Repairs on- site are not possible.
Current approvals on the Internet You will find the current approvals for the product on the Internet pages of Siemens Industry Online Support (https://support.industry.siemens.com/cs/ww/en/ps/15273/cert). Compact Switch Module CSM 377...
Approvals and markings 6.1 Notes on the CE Mark Notes on the CE Mark Product name Compact switch module SIMATIC NET CSM 377 6GK7377-1AA00-0AA0 Observe installation guidelines The product meets the requirements if you keep to the installation instructions and safety- related notices as described here and in the manual "SIMATIC NET Industrial Ethernet Twisted Pair and Fiber Optic Networks"...
Page 37
Germany Importer UK: Siemens plc, Manchester M20 2UR You can find the current UK Declaration of Conformity for these products on the Internet pages under Siemens Industry Online Support (https://support.industry.siemens.com/cs/ww/en/ps/ 15273/cert). Compact Switch Module CSM 377 Operating Instructions, 06/2022, A2B00073499-02...
Page 38
"SIMATIC NET Product Information Use of subassemblies/modules in a Zone 2 Hazardous Area". You will find this document • on the data medium that ships with some devices. • on the Internet pages under Siemens Industry Online Support (https:// support.industry.siemens.com/cs/ww/en/view/78381013).
Page 39
Approvals and markings 6.1 Notes on the CE Mark You will find the current versions of the standards in the currently valid certificates. EMC (electromagnetic compatibility) The SIMATIC NET products described in these operating instructions meet the electromagnetic compatibility requirements according to the EU Directive 2014/30/EU as well as the UK- Regulation SI 2016/1091 and their associated amendments.
Page 40
Approvals and markings 6.1 Notes on the CE Mark cULus for Hazardous Locations ANSI/ISA 12.12.01-2007, CSA C22.2 No. 213-M1987 CL. 1, Div. 2 GP. A.B.C.D T.. CL. 1, Zone 2, GP, IIC, T.. (T.. = For detailed information on the temperature class, refer to the type plate) Note for Australia - RCM The product meets the requirements of the RCM standard.
References References Sources of information and other documentation 1. SIMATIC NET Industrial Twisted Pair and Fiber-Optic Networks, Order numbers: 6GK1970-1BA10-0AA0 German 6GK1970-1BA10-0AA1 English 6GK1970-1BA10-0AA2 French 6GK1970-1BA10-0AA4 Italian 2. PROFINET Cabling and Interconnection Technology Guideline Can be ordered from the PROFIBUS User Organization (PNO) Compact Switch Module CSM 377 Operating Instructions, 06/2022, A2B00073499-02...
References 7.2 Internet Internet Further information on the Internet You will find additional information on SIMATIC NET products in the Internet at http:// www.automation.siemens.com/net/index_00.htm Compact Switch Module CSM 377 Operating Instructions, 06/2022, A2B00073499-02...