Page 1
___________________ SCALANCE X005 / X005TS Introduction ___________________ Network topologies ___________________ Description of the device SIMATIC NET ___________________ Mounting Industrial Ethernet switches ___________________ SCALANCE X005 / X005TS Connecting up Maintenance and ___________________ troubleshooting Operating Instructions ___________________ Technical specifications ___________________ Approvals ___________________...
Page 2
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Notes on the e1/E1 approval of the SCALANCE X005TS ............32 Noise test of the SCALANCE X005TS ..................33 Overvoltage test of the SCALANCE X005TS ................33 Mechanical stability (in operation)....................33 Dimension drawings ..........................35 Index..............................37 SCALANCE X005 / X005TS Operating Instructions, 07/2014, C79000-G8976-C344-01...
The "SIMATIC NET Industrial Ethernet Twisted Pair and Fiber Optic Networks" manual contains additional information on other SIMATIC NET products that you can operate along with the SCALANCE X005 and SCALANCE X005TS IE switches in an Industrial Ethernet network. You can order the manual "SIMATIC NET Industrial Twisted Pair and Fiber Optic Networks",...
Page 6
Siemens recommends strongly that you regularly check for product updates. For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action (e.g. cell protection concept) and integrate each component into a holistic, state-of-the-art industrial security concept.
Industrial Ethernet linear bus or star structures with switching functionality. The devices are designed for installation in a cabinet. Note It is not possible to use a SCALANCE X005 or SCALANCE X005TS in a redundant ring because they do not support redundancy. Note If devices are supplied over long 24 V power supply lines or networks, measures are necessary to prevent interference by strong electromagnetic pulses on the supply lines.
Switching technology allows extensive networks to be set up with numerous nodes and simplifies network expansion. Which topologies can be implemented? Using the SCALANCE X005 and SCALANCE X005TS IE switches, you can implement star topologies. Note Keep to the maximum permitted cable lengths of the devices you are using. You will find the permitted cable lengths in the section "Technical specifications (Page 29)".
Description of the device 3.2 Product characteristics Product characteristics Possible attachments The SCALANCE X005 and SCALANCE X005TS have five RJ-45 jacks for connection of end devices or other network segments. Figure 3-1 SCALANCE X005 Note The SCALANCE X005 shown above has the same construction as the SCALANCE X005TS.
3.3 TP ports (twisted pair) TP ports (twisted pair) RJ-45 connector pinout With SCALANCE X005 and SCALANCE X005TS, the twisted-pair ports are designed as RJ- 45 jacks with MDI-X pin assignment (Medium Dependent Interface Autocrossover) of a network component. Pin number...
Page 14
If the pair of receiving cables is connected incorrectly (RD+ and RD- interchanged), the polarity is adapted automatically. Note The SCALANCE X005 and SCALANCE X005TS IE switches are plug-and-play devices that require no settings during commissioning. MDI / MDI-X autocrossover function With the MPI/MDI-X autocrossover function, the send and receive contacts of an Ethernet port are assigned automatically.
The port LEDs indicate the status of the ports. LED color LED status Meaning Green TP link exists, no data reception at port Yellow TP link exists, data reception at port Yellow Flashing Test phase during power on SCALANCE X005 / X005TS Operating Instructions, 07/2014, C79000-G8976-C344-01...
Page 16
Description of the device 3.4 LEDs SCALANCE X005 / X005TS Operating Instructions, 07/2014, C79000-G8976-C344-01...
Twisted Pair and Fiber Optic Networks". Note Provide suitable shade to protect the device against direct sunlight. This avoids unwanted warming of the device and prevents premature aging of the device and cabling. SCALANCE X005 / X005TS Operating Instructions, 07/2014, C79000-G8976-C344-01...
3. Fit the connectors for the power supply. See also section "Power supply (Page 23)". 4. Insert the terminal block into the sockets on the device. Figure 4-1 Installation on a 35 mm DIN rail SCALANCE X005 / X005TS Operating Instructions, 07/2014, C79000-G8976-C344-01...
Page 19
3. Release the DIN rail catch on the bottom of the device using a screwdriver. 4. Pull the lower part of the device away from the DIN rail. Figure 4-2 Removal from a 35 mm DIN rail SCALANCE X005 / X005TS Operating Instructions, 07/2014, C79000-G8976-C344-01...
To remove the device from the S7-300 standard rail, follow the steps below: 1. Disconnect all connected cables. 2. Release the screw on the bottom of the standard rail. 3. Remove the device from the standard rail. SCALANCE X005 / X005TS Operating Instructions, 07/2014, C79000-G8976-C344-01...
3. Insert the terminal block into the sockets on the device. 4. Screw the device to the wall. Note The wall mounting must be capable of supporting at least four times the weight of the device. SCALANCE X005 / X005TS Operating Instructions, 07/2014, C79000-G8976-C344-01...
The power supply is non-floating. The following figure shows the position of the power supply of the SCALANCE X005 or SCALANCE X005TS and the assignment of the terminal block.
Fitting the IE FC RJ45 Plug 180 to the IE FC Standard Cable You will find the notes on installation in the instructions that ship with the IE FC RJ45 Plug 180. Figure 5-1 IE FC 45 Plug 180 SCALANCE X005 / X005TS Operating Instructions, 07/2014, C79000-G8976-C344-01...
Page 25
If there is not enough space to release the lock with your hand, you can also use a 2.5 mm screwdriver. You can then remove the IE FC RJ45 Plug 180 from the RJ-45 jack. SCALANCE X005 / X005TS Operating Instructions, 07/2014, C79000-G8976-C344-01...
Page 26
Connecting up 5.3 IE FC RJ-45 Plug 180 SCALANCE X005 / X005TS Operating Instructions, 07/2014, C79000-G8976-C344-01...
Maintenance and troubleshooting Fuses The SCALANCE X005 and SCALANCE X005TS IE switches have a resettable fuse / PTC. If the fuse triggers (all LEDs are off despite correctly applied power supply), the device should be disconnected from the power supply for approximately 30 minutes before turning it on again.
Technical specifications Note Unless mentioned otherwise, the technical specifications in the following table relate to the SCALANCE X005 and SCALANCE X005TS. Table 7- 1 Technical specifications of the SCALANCE X005 and SCALANCE X005TS Technical specifications Order number SCALANCE X005 6GK5005-0BA00-1AA3...
Page 30
The number of connected SCALANCE X Industrial Ethernet Switches influences the frame propagation time. When a frame passes through the SCALANCE X005 or SCALANCE X005TS, it is delayed by the store and forward function of the switch: • with a 64 byte frame length by approx. 10 µs (at 100 Mbps) •...
You can check which of the following approvals have been granted for your product by the markings on the type plate. Approvals_intro_X-000 The following approvals apply to the SCALANCE X005 and SCALANCE X005TS. EMC directive The devices meet the requirements of the EC Directive 2004/108/EC "Electromagnetic Compatibility".
Underwriters Laboratories Inc. complying with ● UL 60950-1 (Information Technology Equipment) ● CSA C22.2 No. 60950-1-03 Report no. E115352 Notes on the e1/E1 approval of the SCALANCE X005TS Product name Product Order number SCALANCE X005TS 6GK5005-0BA00-1CA3 SCALANCE X005 / X005TS Operating Instructions, 07/2014, C79000-G8976-C344-01...