hit counter script

Switch And Module Weights And Quantities; Transceiver And Cable Specifications; Switch Power Input Requirements; Power Specifications - Cisco Nexus 9348D-GX2A Hardware Installation Manual

Aci-mode switch
Table of Contents

Advertisement

Switch and Module Weights and Quantities

Switch and Module Weights and Quantities
Component
Cisco Nexus 9348D-GX2A Chassis
(N9K-C9348D-GX2A)
Fan Module
– Port-side intake (burgundy)
(NXA-FAN-160CFM-PI)
Power Supply module
– 3200-W AC/HVDC port-side
intake (burgundy)
(NXA-PAC-3200W-PI)

Transceiver and Cable Specifications

To determine which transceivers, adapters, and cables are supported by this switch, see
c/en/us/support/interfaces-modules/transceiver-modules/products-device-support-tables-list.html.
To see the transceiver specifications and installation information, see
interfaces-modules/transceiver-modules/products-device-support-tables-list.html.

Switch Power Input Requirements

The following table lists the typical amount of power that the switch consumes. It also lists the maximum
amount of power that you must provision for the switch and power supply for peak conditions.
Note
Switch
Cisco Nexus
9348D-GX2A

Power Specifications

Power specifications include the specifications for each type of power supply module.
Cisco Nexus 9348D-GX2A ACI-Mode Switch Hardware Installation Guide
46
Some power supplies have capabilities that are greater than the maximum power requirements for a
switch. To determine the power consumption characteristics for the switch, use the typical and maximum
requirements that are listed in the following table.
Typical Power
Consumption (AC or DC)
1380 W
Weight per Unit
51.2 lb (23.22 kg)
1.35 lb (0.61 kg)
3.6 lb (1.63 kg)
Maximum Power
Consumption (AC or DC)
3124 W
System Specifications
Quantity
1
4
2 (1 for operations and 1 for
redundancy)
https://www.cisco.com/
https://www.cisco.com/c/en/us/support/
Heat Dissipation
Requirement
10,659.531 BTUs per
hour

Advertisement