Page 1
Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide First Published: 2023-08-18 Americas Headquarters Cisco Systems, Inc. 170 West Tasman Drive San Jose, CA 95134-1706 http://www.cisco.com Tel: 408 526-4000 800 553-NETS (6387) Fax: 408 527-0883...
Page 2
Any products and features described herein as in development or available at a future date remain in varying stages of development and will be offered on a when-and if-available basis. Any such product or feature roadmaps are subject to change at the sole discretion of Cisco and Cisco will have no liability for delay in the delivery or failure to deliver any products or feature roadmap items that may be set forth in this document.
Installing the Switch Using the NXK-ACC-KIT-1RU Rack-Mount Kit Grounding the Chassis Starting the Switch C H A P T E R 4 Connecting the Switch to the Network Overview of Network Connections Connecting a Console to the Switch Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
Page 4
Switch and Module Weights and Quantities Transceiver and Cable Specifications Switch Power Input Requirements Power Specifications 350-W AC Power Supply Specifications 350-W PHV Power Supply Specifications 440-W DC Power Supply Specifications Power Cable Specifications Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
Page 5
A P P E N D I X C LEDs Switch Chassis LEDs Fan Module LEDs Power Supply LEDs A P P E N D I X D Additional Kits Rack Mount Kit NXK-ACC-KIT-1RU Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
Overview, on page 1 Overview The Cisco Nexus 9348GC-FX3 switch (N9K-C9348GC-FX3) is a 1-RU fixed-port, L2/L3 switch, designed for deployment in data centers. This switch has 48 10/100/1000M copper RJ45 downlink ports, 4 10-/25G SFP28 uplink ports, and 2 40-/100G QSFP28 uplink ports.
Page 8
Grounding pad Power supply modules (1 or 2) (AC Fan modules (3) with slots numbered from 1 (left) to 3 (right) power supplies shown) with slots numbered 1 (left) and 2 (right) Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
Page 9
If the switch has port-side exhaust airflow (blue coloring for fan modules), you must locate the ports in the hot aisle. If you locate the air intake in a hot aisle, the switch can overheat and shut down. Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
Altitude Requirements Altitude rating is 10,000 ft (3048 m). For China, it is 6,562 ft (2000 m). Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
The wiring is unlikely to emit radio interference if you use a twisted-pair cable with a good distribution of grounding conductors. If you exceed the recommended distances, use a high-quality twisted-pair cable with one ground conductor for each data signal when applicable. Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
Rack and Cabinet Requirements You can install the following types of racks or cabinets for your switch: • Standard perforated cabinets • Solid-walled cabinets with a roof fan tray (bottom-to-top cooling) Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
Page 14
Statement 1048 Rack Stabilization The rack stabilizing mechanism must be in place, or the rack must be bolted to the floor before installation or servicing. Failure to stabilize the rack can cause bodily injury. Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
Starting the Switch, on page 19 Safety Before you install, operate, or service the switch, see the Regulatory, Compliance, and Safety Information for the Cisco Nexus 3000 and 9000 Series for important Safety Information. Warning Statement 1071 Warning Definition IMPORTANT SAFETY INSTRUCTIONS Before you work on any equipment, be aware of the hazards involved with electrical circuitry and be familiar with standard practices for preventing accidents.
Page 16
Only an instructed person or skilled person should be allowed to install, replace, or service this equipment. See statement 1089 for the definition of an instructed or skilled person. There are no serviceable parts inside. To avoid risk of electric shock, do not open. Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
Page 17
This equipment must be grounded. To reduce the risk of electric shock, never defeat the ground conductor or operate the equipment in the absence of a suitably installed ground conductor. Contact the appropriate electrical inspection authority or an electrician if you are uncertain that suitable grounding is available. Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
You can install the switch using the following rack-mount options: • Rack-mount kit (NXK-ACC-KIT-1RU) which you can order from Cisco. This option offers you easy installation, greater stability, increased weight capacity, added accessibility, and improved removability with front and rear removal.
50 to 60 Hz. Caution To prevent loss of input power, ensure the total maximum loads on the circuits supplying power to the switch are within the current ratings for the wiring and breakers. Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
You must supply the eight 10-32 or 12-24 screws required to mount the slider rails and switch to the rack. Before you begin • You have inspected the switch shipment to ensure that you have everything ordered. Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
Page 21
The holes that you use depend on the requirements of your rack and the amount of clearance required for interface cables (3 inches [7.6 mm] minimum) and module handles (1 inch [2.5 mm] minimum). Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
Page 22
Holding the switch with both hands, position the two rear rack-mount brackets on the switch between the rack or cabinet posts that do not have slider rails attached to them (see the following figure). Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
Page 23
Tighten the 10-32 screws to 20 in-lb (2.26 N·m) or tighten the 12-24 screws to 30 in-lb (3.39 N·m). Step 5 If you attached a grounding wire to the chassis grounding pad, connect the other end of the wire to the facility ground. Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
Verify that the ground wire is securely attached to the grounding lug by attempting to pull the wire out of the crimped lug. Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
• You have the designated power cables for the power supplies that you are connecting to the dedicated power sources. Note Depending on the outlet receptacle on your AC power distribution unit, you might need an optional jumper power cord to connect the switch to your outlet receptacle. Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
Page 26
After the switch boots, verify that the following LEDs are lit: • On the fan modules, the Status (STA or STS) LED is green. If a fan module Status LED is not green, try reinstalling the fan module. Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
Page 27
A setup utility automatically launches the first time that you access the switch and guides you through the basic configuration. For instructions on how to configure the switch and check module connectivity, see the appropriate Cisco Nexus 9000 Series configuration guide.
Page 28
Installing the Chassis Starting the Switch Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
When running cables in overhead or subfloor cable trays, we strongly recommend that you locate power cables and other potential noise sources as far away as practical from network cabling that terminates on Cisco equipment. In situations where long parallel cable runs cannot be separated by at least 3.3 feet (1 meter), we recommend that you shield any potential noise sources by housing them in a grounded metallic conduit.
You can find this cable in the accessory kit. Step 3 Route the RJ-45 rollover cable to the console or modem. Step 4 Connect the other end of the RJ-45 rollover cable to the console or to a modem. Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
To connect the switch to the network, you can use the default choices for each configuration except the IP address, which you must provide. You can perform the other configurations later as described in the Cisco Nexus 9000 Series NX-OS Fundamentals Configuration Guide.
RJ-45 connectors. For longer connections, you can use an optical cable with SFP transceivers (LH or SX type). Note Use only one of these management ports—the switch does not support the use of both management ports. Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
When removing transceivers from the switch, it is best to remove the optical cable first and then remove the transceiver. To determine which transceivers, adapters, and cables are supported by this switch, see the Cisco Transceiver Modules Compatibility Information document. Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
Page 34
Connecting the Switch to the Network Connecting Interface Ports to Other Devices Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
On the fan module that you are removing, press the two sides of the fan module handle together, and pull on the handles enough to unseat it from its connectors. Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
Pull the power cord out from the power receptacle on the power supply to be removed and verify that the LED turns off. The LED might be on and amber colored to indicate that the input power has been disconnected. Note Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
Step 2 Remove the power cable from the power supply by doing the following: Step 3 Grasp the power supply handle while pressing the release latch towards the power supply handle. Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
Make sure that the other end of the power cable is attached to the appropriate power source for the power supply. Note Depending on the outlet receptacle on your power distribution unit, you might need the optional jumper cable to connect the switch to your outlet receptacle. Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
Verify that the power supply is operational by making sure that the power supply LED is green. Installing a DC Power Supply You can replace one power supply while the other one provides power to the switch. Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
Page 40
Turn on the circuit breaker for the DC power source connected to the power supply. Step 4 Verify that the power supply is operational by making sure that the power supply LED is green. Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
• Standard 19-inch (48.3 cm) (two- or four-post EIA cabinet or rack, with mounting rails that conform to English universal hole spacing per section 1 of ANSI/EIA-310-D-1992). For more information, see Requirements Specific to Perforated Cabinets, on page Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
To help with cable management, you might want to allow additional space in the rack above and below the chassis to make it easier to route all of the fiber optic or copper cables through the rack. Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
Maximum inrush current 33 A (sub-cycle duration) Maximum hold-up time 12 ms at 350 W Power supply output voltage -54 VDC Efficiency rating Climate Savers Platinum Efficiency (80Plus Platinum certified) Form factor RSP1 Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
20 A The total input and total output BTU ratings refer to input power to the power supply and output power to the switch. The BTU ratings are based on -36 VDC. Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
250 V, 10 A, 8.2 feet (2.5 m) South Africa CAB-250V-10A-ID 250 V, 10 A, 8.2 feet (2.5 m) Switzerland CAB-9K10A-SW 250 VAC, 10 A, MP232 plug, 8.2 feet (2.5 m) Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
6.6-foot (2.0 m) cable with Saf-D-Grid and three terminal connectors 300V AC / 400V DC (+200/-200 V DC) NO-POWER-CORD All except Argentina, Not applicable Brazil, and Japan No power cord included with switch Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
• CAN/CSA-C22.2 No. 60950-1 Second Edition • CAN/CSA-C22.2 No. 62368-1-19 Third Edition • NRTL 60950-1 Second Edition • IEC 62368-1 • EN 62368-1 • AS/NZS 62368-1 • GB4943 • UL 62368-1 Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
Page 50
• CNS13438 Class A EMC: Immunity • EN55024 • CISPR24 • EN300386 • KN 61000-4 series RoHS The product is RoH-6 compliant with exceptions for leaded-ball grid-array (BGA) balls and lead press-fit connectors. Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
Amber Port admin state is 'Disabled, or the SFP is absent, or both. Port admin state is 'Enabled' and SFP is present, but interface is not connected. Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
Okay (PS_OK) and Okay (AC_OK) LEDs indicate the status for the module as shown in the following table. PS_OK LED AC_OK LED Status Green Green Power supply is on and outputting power to the switch. No power is present. Amber Output has failed. Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...
Hazardous substances list for customers in China The following table lists and illustrates the console cable (CAB-CONSOLE-RJ45) that can be ordered. Illustration Description Quantity Console cable with DB-9F and RJ-45F connectors Cisco Nexus 9348GC-FX3 NX-OS Mode Switch Hardware Installation Guide...