hit counter script

ABB RELION 670 Series Technical Manual page 254

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 7
Impedance protection
BG sector
200°
ANSI06000384 V1 EN-US
Figure 115: Condition 1: Definition of faulty phase sector as angle between V
The angle is calculated in a directional function block and gives the angle in radians as input to the
V
and I
2
0
done by the directional element. The fault is classified as forward direction if the angle between V
and I
lies between 20 to 200 degrees, see figure 116.
0
200°
IEC06000385 V1 EN-US
Figure 116: Directional element used to release the measured angle between V
The input radians are summarized with an offset angle and the result evaluated. If the angle is
within the boundaries for a specific sector, the phase indication for that sector will be active see
figure 115. Only one sector signal is allowed to be activated at the same time.
The sector function for condition 1 has an internal release signal which is active if the main
sequence function has classified the angle between V
must be fulfilled for activating the release signals:
V2MinOp
|V
|>
2
|3I
|> 0.05 ·
0
|3I
|>maxIph ·
0
248
80°
CG sector
AG sector
function block. The input angle is released only if the fault is in forward direction. This is
Forward
Reverse
en06000385.vsd
IBase
INRelPG
V2A
(Ref)
320°
en06000384_ansi.vsd
20°
and I
0
1MRK 502 066-UUS B
and I
2
o
as valid. The following conditions
0
0
0
and I
0
Technical manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reg670

Table of Contents