hit counter script

ABB RELION 670 Series Technical Manual page 133

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 502 066-UUS B
The unrestrained (that is, non-stabilized, "instantaneous") part of the differential protection is
used for very high differential currents, where it should be beyond any doubt, that the fault is
internal. This settable limit is constant and not proportional to the bias current. Neither harmonic,
nor any other restrain is applied to this limit, which is therefore allowed to trip the power
transformer instantaneously.
The restrained (stabilized) part of the differential protection compares the calculated
fundamental differential (operating) currents and the bias (restrain) current, by applying them to
the operate - restrain characteristic. Practically, the magnitudes of the individual fundamental
frequency differential currents are compared with an adaptive limit. This limit is adaptive because
it is dependent on the bias (that is, restrain) current magnitude. This limit is called the operate -
restrain characteristic. It is represented by a double-slope, double-breakpoint characteristic, as
shown in figure 36. The restrained characteristic is determined by the following 5 settings:
IdMin (Sensitivity in section 1, multiple of trans. HV side rated current set under the parameter
1.
RatedCurrentW1 )
EndSection1 (End of section 1, as multiple of transformer HV side rated current set under the
2.
parameter
EndSection2 (End of section 2, as multiple of transformer HV side rated current set under the
3.
parameter
SlopeSection2 (Slope in section 2, as multiple of transformer HV side rated current set under
4.
the parameter
SlopeSection3 (Slope in section 2, as multiple of transformer HV side rated current set under
5.
the parameter
The restrained characteristic in figure
IdMin
1.
EndSection1
2.
EndSection2
3.
4.
SlopeSection2
SlopeSection3
5.
Technical manual
RatedCurrentW1 )
RatedCurrentW1 )
RatedCurrentW1 )
RatedCurrentW1 )
36
is defined by the settings:
Section 6
Differential protection
127

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reg670

Table of Contents