DELTANET R7515A/B, RP7515A/B, R7516B MICROCEL
SLIT FLAT SIDE
OF ELECTRICAL
JACKET (SIDE WITH
PAPER MARKER)
CURVED
SIDE
Install four conductors in T-tap connector on AK3326
T-Tap Cable Assembly as follows:
a. Open cover and lay four conductors in slots in
color-coded base as shown in Figure 11.
NOTE: Do not strip insulation from four conductors.
T-tap connector displaces insulation to
make electrical connections.
b. Snap cover in place over conductors in base.
c. To complete individual electrical connections,
press down each of four connector buttons with
channel lock pliers.
d. Connector buttons should be flush with cover
when properly secured.
BUTTONS
(4)
Fig. 11. Installing Bus Conductors in T-Tap Connector.
95-6083
LEAVE OPEN SECTION
OF ELECTRICAL JACKET
TO ACT AS STRAIN RELIEF
PAPER
MARKER
T-TAP CONNECTOR
Fig. 10. Installing T-Tap Connections to AK3711 Cable Assembly.
RS-485
C-NAP 24V AC FROM
CLASS II POWER
SOURCE
COVER
BASE
TO
CONTROLLER
C3506-4
™
CONTROLLERS
8 IN. (200 MM)
RED
RED
YELLOW
YELLOW
BLACK
BLACK
BLUE
BLUE
AK3326 T-TAP
CABLE ASSEMBLY
6 FT (1.8M)
Connect plug on AK3326 T-Tap Cable Assembly into
Connector J9 on MicroCel base unit as shown in
Figure 12.
CAUTION
Maximum current rating for the T-Tap Cable Assembly
is 1.0A (MicroCel is nominally 250 mA). For loads
greater than 1.0A, hard-wire the system and dedicate
a transformer for each MicroCel.
FROM T7515
FROM AK3711
SPACE SENSOR
CABLE ASSEMBLY
SPACE
SENSOR
CABLE
ASSEMBLY
PLUG
Fig. 12. Installing T-Tap Cable to MicroCel Base Unit.
8
ELECTRICAL
JACKET
AK3711
CABLE
ASSEMBLY
PLUG
TO CONNECTOR J9
IN CONTROLLER
C3384-2
AK3326 T-TAP
CABLE ASSEMBLY
J9 24 VAC C-NAP
BUS CONNECTOR
PLUG
J11 ALTERNATE
24 VAC SCREW
TERMINALS
CONTROLLER
BASE INPUT
BOARD SIDE
J7 ALTERNATE CNAP
SCREW TERMINALS
J8 WALL MOD
CONNECTOR
C3385-2