9.3 Controlling via the AOP30 operator panel
9.3.7.6

AOP setpoint

Settings: MENU – Commissioning / Service – AOP Settings – Control Settings
Save AOP setpoint (factory setting: No)
● Yes: In LOCAL mode, the last setpoint (once you have released the Increase or
Decrease key or confirmed a numeric entry) is saved.
The next time you switch the system ON in LOCAL mode, the saved value is selected.
This is also the case if you switched to REMOTE in the meantime or the power supply
was switched off.
When the system is switched from REMOTE to LOCAL mode while the drive is switched
on (motor is running), the actual value that was last present is set as the output value for
the motorized potentiometer setpoint and saved.
If the system is switched from REMOTE to LOCAL mode while the drive is switched off,
the motorized potentiometer setpoint that was last saved is used.
● No: On power-up in LOCAL mode, the speed is always set to the value entered under
"AOP starting setpoint". When the system is switched from REMOTE to LOCAL mode
while the drive is switched on (motor is running), the actual value that was last present is
set as the output value for the AOP setpoint.
AOP setpoint ramp-up time (factory setting: 20 s)
Defines the speed at which the setpoint specified by the AOP is increased when the "+" key
is pressed.
AOP setpoint ramp-down time (factory setting: 30 s)
Defines the speed at which the setpoint specified by the AOP is decreased when the "-" key
is pressed.
AOP starting setpoint (factory setting: 0.000 rpm)
The AOP starting setpoint is the speed setpoint which is active when the drive is switched on
(with the "ON" key on the AOP30); The "Save setpoint" system setting must be set to "No"
for this purpose (see also the description of the "Save AOP setpoint" system setting).
Note
The internal drive ramp-function generator is always active.
9.3.7.7

Inhibiting AOP LOCAL mode

Settings: MENU – Commissioning / Service – AOP Settings – Control Settings
Inhibit AOP local mode (factory setting: No)
● Yes: Deactivates the "Control via operator panel" function, thereby disabling the
LOCAL/REMOTE key.
● No: Activates the LOCAL/REMOTE key.
364
SINAMICS DCM Control Module
Operating Instructions, 12/2018, A5E34888669A