Cabinet design
6.3 Electromagnetic compatibility
Drive systems of Category C2 may only be used in the first environment if they are installed
and commissioned by an expert and the limit values for harmonic currents are complied with.
Note
Disturbance of radio communication services due to radio-frequency interferences in
residential environments
In a residential environment, this product can cause radio-frequency interferences, which
may make interference suppression measures necessary.
• Have the installation and commissioning performed with appropriate radio interference
suppression measures by experts.
Category C3
Drive systems with a rated voltage < 1000 V that are solely intended for use in the second
environment.
Note
Disturbance of radio communication services due to radio-frequency interferences in
residential environments
In a residential environment, this product can cause radio-frequency interferences.
• Do not use this device in the first environment (residential area).
Category C4
Drive systems for IT line supplies for operation in complex systems in the second
environment. An EMC plan must be drawn up.
6.3.3

Drive system applications

SINAMICS S120 units are designed for use in the second environment. They are to be used
on a professional basis in trade, business and industry and are not sold to the general public.
In order to satisfy the EMC requirements, the drive system must be installed by appropriately
qualified personnel in compliance with EMC regulations and the installation notes provided in
the manual.
Note
Qualified personnel
An appropriately trained and qualified person has the necessary experience for installing
and/or commissioning drive systems (Power Drive Systems - PDS), including the associated
EMC aspects.
More detailed requirements regarding areas of application can be found in the SINAMICS
S120 Manual "Booksize Power Units".
100
Power Units in Booksize C/D-Type Format