Function block "Enduser space heat-
ing"
This function block contains settings that the enduser himself can make.
5.1
Operating lines
Line
Function, parameter
1
Setpoint of NORMAL heating
2
Setpoint of REDUCED heating
3
Setpoint of holiday mode / frost protection
4
Weekday for the heating program
5
1. Third heating period, start of NORMAL heating
6
1. Third heating period, start of REDUCED heating
7
2. Third heating period, start of NORMAL heating
8
2. Third heating period, start of REDUCED heating
9
3. Third heating period, start of NORMAL heating
10
3. Third heating period, start of REDUCED heating
11
Holiday period
12
Date of first day of holiday
13
Date of last day of holiday
14
Heating curve, flow temperature setpoint TV1 at
an outside temperature of 15 °C
15
Heating curve, flow temperature setpoint TV2 at
an outside temperature of –5 °C
5.2
Setpoints
5.2.1
General
The setpoints of the NORMAL and the REDUCED room temperature and of frost pro-
tection for the plant / holiday mode are entered directly in °C room temperature. They
are independent of whether or not the control uses a room temperature sensor.
5.2.2
Frost protection for the building
The lowest valid room temperature setpoint always corresponds to at least the setpoint
of holiday mode / frost protection (setting on operating line 3), even if lower values have
been entered as the setpoints of the NORMAL and the REDUCED room temperature
(settings on operating lines 1 and 2).
If a room sensor is used and the room temperature falls below the holiday / frost pro-
tection setpoint, ECO – if available – will stop OFF until the room temperature has risen
1 °C above the holiday / frost protection setpoint.
5.3
Heating program
The heating program of the RVL471 provides a maximum of 3 heating periods per day;
also, every weekday may have different heating periods.
The entries to be made are not the switching times, but the periods of time during which
the NORMAL room temperature shall apply. Usually, these periods of time are identical
to the building's occupancy times. The actual switching times for the change from the
REDUCED to the NORMAL room temperature, and vice versa, are calculated by the
optimization function. (Precondition: Optimization is activated).
Basic Documentation RVL471
5 Function block "Enduser space heating"
Unit
Factory
Range
setting
°C
20.0
0...35
°C
14.0
0...35
°C
10.0
0...35
1-7
1...7, 1-7
hh:mm
06:00
--:-- / 00:00...24:00
hh:mm
22:00
--:-- / 00:00...24:00
hh:mm
--:--
--:-- / 00:00...24:00
hh:mm
--:--
--:-- / 00:00...24:00
hh:mm
--:--
--:-- / 00:00...24:00
hh:mm
--:--
--:-- / 00:00...24:00
dd:MM
--:--
--:-- / 01.01. ... 31.12.
dd:MM
--:--
--:-- / 01.01. ... 31.12.
°C
30
20...70
°C
60
20...120
1...8