Page 2
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Overview of the technical documentation of the IE Switches X-300 A CD is supplied with the IE Switches X-300 on which you will find a detailed description of the products in PDF format in the relevant subfolder. SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
Page 6
Security messages Note Siemens offers IT security mechanisms for its automation and drive product portfolio in order to support the safe operation of the plant/machine. Our products are also continuously developed further with regard to IT security. We therefore recommend that you regularly check for updates of our products and that you only use the latest versions.
2 x power supply unit 100 to 240 VAC / 60 to 250 VDC 6GK5307-2FD00-4EA3 2 x power supply unit 100 to 240 VAC / 60 to 250 VDC 6GK5307-2FD00-4GA3 Printed board varnished * See naming key below SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
26 km in length. • Port 21: Multimode • Port 22: LD (long distance, single mode) • Port 23: LD (long distance, single mode) SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
There is an additional requirement if devices are operated with a redundant power supply: If the equipment is connected to a redundant power supply (two separate power supplies), both must meet these requirements. WARNING For use in an environment with pollution level 2 SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
Page 12
When used in hazardous environments corresponding to Class I, Division 2 or Class I, Zone 2, the device must be installed in a cabinet or a suitable enclosure. WARNING Opening the device DO NOT OPEN WHEN ENERGIZED. SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
DO NOT DISCONNECT WHILE CIRCUIT IS LIVE UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS. WARNING Restricted area of application This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or non- hazardous locations only. SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
Page 14
● Installation in a suitable cabinet. ● Installation in a suitable enclosure. ● Installation in a suitably equipped, enclosed control room. SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
• Injury to persons • Loss of the approvals • Violation of the EMC regulations Use only undamaged parts. 1. Make sure that the package is complete. 2. Check all the parts for transport damage. SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
● 1 x 3-pin 1 x 3-pin ● to 250 VDC 2 x power supply unit 100 to 240 VAC / 60 ● 2 x 3-pin 2 x 3-pin ● to 250 VDC SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
3.2 Characteristics of the X-300EEC product group Characteristics of the X-300EEC product group Variants The SCALANCE X-300EEC is a 19"/2 device with 9 ports for the connection of end devices or other network segments. There are 2 device types with the following ports: ● SCALANCE X302-7EEC –...
Page 18
In a device with a varnished printed circuit board, you may only use a C-PLUG with a varnished board. To remove the C-PLUG, open the slider and close it again after inserting the C-PLUG. SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
Page 19
To increase mechanical stability, secure the IE FC RJ-45 PLUGs to this securing bracket with a cable binder. LEDs of the X-300EEC You will find the meaning of the individual LEDs in the Operating Instructions (BA) of the IE Switch SCALANCE X-300. SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
The SCALANCE X302-7EEC has the following ports: ● 2 electrical gigabit ports (P8 to P9) ● 7 optical Fast Ethernet ports (P1 to P7) Figure 3-3 SCALANCE X302-7EEC Port number Connection type Optical: Fast Ethernet Electrical: Gigabit Ethernet SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
A. 2. Hold down the SELECT/SET button for 12 seconds. If you release the button before the 12 seconds have elapsed, the reset is canceled. SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
Page 23
3. The result of the action depends on the initial situation: – If the redundancy manager and media redundancy were disabled, media redundancy is also enabled after enabling the redundancy manager. – If you disable the redundancy manager, media redundancy remains enabled. SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
Bad firmware image. During normal operation, the "F" LED provides the following information: LED color LED status Meaning during operation No operating problems. The device has detected an error. The signaling contact opens. SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
Page 25
For devices with power supply unit 24 to 48 VDC: Limit voltage = 17 VDC • For devices with a multiple range power supply unit 100 to 240 VAC / 60 to 250 VDC: • Limit voltage = 46.5 VDC or 80 VAC SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
Page 26
4 times per sec- Port exists and is in the "monitor port" status. In this sta- tus, the data traffic of another port is mirrored to this port. SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
Page 27
The port is monitored, in other words, if no connection was established at the port (for example no cable insert- ed), this triggers the signaling contact and an error state results. SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
Inserting a C-PLUG that does not contain the configuration of a compatible device type, accidentally removing the C-PLUG or general malfunctions of the C-PLUG are signaled by the diagnostics mechanisms of the device (LEDs, Web-based management, SNMP, CLI and PROFINET diagnostics). SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
3. The housing of the C-PLUG has a protruding ridge on the long side (position B). The slot has a groove at this position. Insert the C-PLUG correctly oriented into the slot. 4. Close the housing again with the sealing screw. SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
When installing and operating the device, keep to the installation instructions and safety- related notices as described here and in the manual SIMATIC NET - Twisted Pair and Fiber Optic Networks. Unless stated otherwise, the installation options listed below apply to all device variants. SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
● Wall mounting ● 19" rack mounting Note Standard rail and wall mounting of the IE Switch X-300EEC With the X-300EEC, note the special features in the relevant subsection on standard rail or wall mounting. SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
On the X-300EEC with power supply 100 to 240 V AC, you must always connect protective ground via the bolts on the bottom of the device housing. See also Connecting the switch (Page 40) SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
To remove the switch from the SIMATIC S7-300 standard rail, follow these steps: 1. Disconnect all connected cables. 2. Loosen the screws on the underside of the standard rail and lift the switch away from the rail. SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
Note To mount the IE Switch X-300EEC on a wall, you require an additional securing bracket. You will find the dimensions for a suitable securing bracket in section Dimension drawings (Page 59). SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
Figure at top: Rear of the switches Figure at bottom: View from below Table 4- 2 Legend for rack mounting of two IE-Switches X-300EEC fastened together Name Plate for side Spring washer Hexagonal nut SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
Page 37
Assembling 4.6 19" rack mounting Name Side section (the side panel should be under slight tension) IE Switch X-300EEC SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
"Standby connection" must be "enabled" and the "Standby connection name" must match the name of the partner device. You will also need to configure the port with "Enable Standby Port Monitoring" (see "Configuration Manual SCALANCE X-300 / X-400", section "X-300/X-400 Standby Mask"). SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
With devices with a supply voltage of 100 to 240 VAC / 60 to 250 VDC, you should also connect the protective earth to the grounding bolt. On the SCALANCE X-300EEC, the grounding bolt is on the bottom of the device. On the SCALANCE XR-300M EEC, the grounding bolt is on the rear of the housing between the power connectors.
Page 41
To wire up the protective ground, use a copper cable of category 14-8 AWG or cable with a cross-section of 1.5 to 6 mm². Grounding bolts on the underside of the housing of the X-300EEC or on the rear of the XR- 300M-EEC SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
0.75 to 2.5 mm². NOTICE Laying the connecting cables of the signaling contact with the X-300EEC To improve the EMC properties (surge protection), the two connecting cables of the signaling contact should be laid together. SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
Make sure that the connector cannot be released accidentally by pulling on the connecting cable. Lay the cables in cable ducts or cable channels and secure the cables, where necessary, with cable ties. SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
• The signaling contact can be subjected to a maximum load of 100 mA (safety extra-low voltage (SELV) 24 V DC). • Never operate the device with AC voltage or DC voltage higher than 58 V DC. SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
If you connect an X-300EEC with redundant power supply units 24...48 V DC to two power supplies, you will need to connect the power supply to terminal "L1" on both power supply units. Only "L1" is monitored on each connector. SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
● If the power supply fails at pins L1/M1, this is indicated by LED L1. ● If the power supply fails at pins L2/M2, this is indicated by LED L2. SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
2 x 100 to 240 VAC / 60 to 250 VDC ● X307-2EEC 1 x 100 to 240 VAC / 60 to 250 VDC ● 2 x 100 to 240 VAC / 60 to 250 VDC ● SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
Make sure that the connector cannot be released accidentally by pulling on the connecting cable. Lay the cables in cable ducts or cable channels and secure the cables, where necessary, with cable ties. SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
With devices with a supply voltage of 100 to 240 VAC / 60 to 250 VDC, you should also connect the protective earth to the grounding bolt. On the SCALANCE X-300EEC, the grounding bolt is on the bottom of the device. On the SCALANCE XR-300M EEC, the grounding bolt is on the rear of the housing between the power connectors.
Page 50
DC voltage is connected at the following terminals: ● Plus to "L" ● M to "N" Secure the firm seat of connectors and the terminal block by tightening the screws (does not apply to X-300EEC). SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
2 x power supply units 2120 g IP30 Without clip: • 100 to 240 VAC / 60 to 250 60 × 125 × 123 mm With clip: • 216 × 203 × 99 mm SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
Page 52
-40 °C to +70 °C < 95 % (no conden- Max. 65 ℃ as of 2000 m sation) Max. 60 ℃ as of 3000 m The IE Switch was type tested for 16 h at +85 °C. SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
Page 53
Velocity: <10 mm/s • (IEEE1613 Class V.S.2) Frequency: 1 to 150 Hz • Shock Acceleration: 15 g • (IEC 60068-2-27) Duration of the pulse: 11 ms • Number of shocks per direction: 3 • SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
0.5 to 0.3 A 12 W 100 to 240 VAC / 60 to 250 0.3 to 0.2 A (AC) 12 to 13 W (AC) 0.3 to 0.1 A (DC) 12 to 13 W (DC) SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
Page 55
Electrical data: Transmitter output (optical) and receiver input Transmitter output (optical) Receiver input min. [dBm] max. [dBm] Sensitivity min. [dBm] Input power max. [dBm] Values for glass fiber: 62.5 to 125 μm multimode SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
62.5/125 μm 0 to 5 km ≤1 dB/km at 1310 nm; 1200 MHz×km; maximum insertion loss 50/125 μm, 0.5 dB; 9 dB max. permitted FO cable attenuation at 3 dB link power margin SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
These values apply at 40 °C. Note The IE Switches X-300 support "full wire speed switching" complying with IEEE 802.3 on all ports. The number of packets therefore depends on the packet length. SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
Page 58
• at 64 bytes frame length: Delay of approx. 10 microseconds (at 100 Mbps) • at 1500 bytes frame length: Delay of approx. 130 microseconds (at 100 Mbps) This means, the more IE Switches X-300 a frame runs through, the higher the frame delay. SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
Page 61
You will find other accessories, such as screws in the tables. If you have questions, contact our Customer Support. You will also find dimension drawings on the Internet on the pages of Siemens Industry Automation Customer Support under the following entry ID: 33118441 (http://support.automation.siemens.com/WW/view/en/33118441)
Page 62
Dimension drawings Mounting support for EEC wall mounting Figure 7-4 X-300EEC wall mounting (dimensions in mm) SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
Page 63
Rack mounting of two X-300EECs fastened together (view from below) Table 7- 1 Legend for rack mounting of two X-300EECs fastened together Number needed Name Plate for side Spring washer SN60727-4-NrSt Hexagonal nut ISO 4032-M4-8 Mid part of mounting support SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
Page 64
Dimension drawings Figure 7-6 Side part of mounting support for X-300EEC (dimensions in mm) Material: Plate 2.0 DIN EN10152 DC01+ZE25/25 SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
Page 65
Dimension drawings Figure 7-7 Middle part of mounting support for X-300EEC (dimensions in mm) Material: Plate 2.0 DIN EN10152 DC01+ZE25/25 See also 19" rack mounting (Page 36) SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
The term "the product" as used below includes all device variants of the SCALANCE X-300EEC unless specific variants are expressly named for an approval. EC directives SIMATIC NET products meet the requirements and aims of the following EC directives.
Page 68
(http://support.automation.siemens.com/WW/view/en/27069465)", in "Further documentation". – "EMC Installation Guidelines" configuration manual ID = 60612658 (http://support.automation.siemens.com/WW/view/en/60612658) ● Working on the device To protect the device from electrostatic discharge, personnel must first discharge any electrostatic charge from their body before touching the device.
Page 69
Area". You will find this document • on the data medium that ships with some devices. • on the Internet pages of Siemens Industry Online Support (http://support.automation.siemens.com/WW/view/en). Enter the document identification number C234 as the search term. SIMATIC NET products meet the requirements of the EC directive:94/9/EC "Equipment and Protective Devices for Use in Potentially Explosive Atmospheres".
Page 70
Non Incendive / Class I / Zone 2 / Group IIC / T4 Note Only variants with 24 VDC power supply meet the requirements of this approval. C-Tick The product meets the requirements of the AS/NZS 2064 standard (Class A). SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
Page 71
Cl. 1, Div. 2, GP A, B, C, D T4 Cl. 1, Zone 2, GP IIC T4 Report no. E240480 Note Only variants with 24 VDC power supply meet the requirements of this approval. SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...
24 to 48 ● ● ● ● ● ● 7EEC X302- 100...240 ● ● ● 2EEC VAC / 60...250 For temperature information "T.." or the maximum ambient temperature "Ta:..", refer to the type plate. SCALANCE X-300EEC Compact Operating Instructions, 11/2015, A5E02630809-09...