SCALANCE X-

SIMATIC NET
Industrial Ethernet Switches
SCALANCE X-300
Operating Instructions
10/2010
A5E01113043-10
300

___________________
Preface
___________________
Safety instructions
___________________
Introduction
___________________
Network topologies
___________________
Description of the device
___________________
Installation
___________________
Connecting
___________________
Configuration, displays and
display elements
___________________
Technical specifications
Approvals, certificates,
___________________
standards
___________________
Accessories
___________________
Graphics
___________________
Appendix
1
2
3
4
5
6
7
8
9
10
11
A

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SCALANCE X-300

  • Page 1 ___________________ SCALANCE X- Preface ___________________ Safety instructions ___________________ Introduction SIMATIC NET ___________________ Network topologies Industrial Ethernet Switches ___________________ SCALANCE X-300 Description of the device ___________________ Installation Operating Instructions ___________________ Connecting ___________________ Configuration, displays and display elements ___________________ Technical specifications Approvals, certificates,...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Preface

    Classification Description Product line (X-300) For all devices and variants of all product groups within the SCALANCE X-300 product line, the term "IE Switch X-300" is used. Product group For all devices and variants of a product group, only the product group is used.
  • Page 4 BAK X-300 EEC A5E02661176A XR-300M EEC BAK XR-300M EEC A5E02630809A X-300M PoE BAK X-300M PoE A5E02630810A XR-300M PoE BAK XR-300M PoE A5E02661178A MM900 (media modules) BAK MM900 A5E02630805A SFP (transceivers) BAK SFP A5E02630804A Notices leaflet A5E02648904A SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 5 If you have questions on the use of SIMATIC NET products, please contact your Siemens sales partner. Standards and approvals The devices of the SCALANCE X-300 product line meet the requirements for the CE mark. For more detailed information, refer to section Approvals, certificates, standards (Page 201). Integration in STEP 7 projects The current GSDML file must be used for integration in STEP 7 V5.4 SP5 projects.
  • Page 6 Preface SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 7: Table Of Contents

    Media redundancy in ring topologies ...................35 3.4.2 MRP .............................36 3.4.3 HSR..............................39 Redundant coupling of network segments...................40 Description of the device ......................... 43 Compatibility of SCALANCE X-300 .....................43 Product groups..........................45 4.2.1 X-300 product group ........................45 4.2.1.1 SCALANCE X304-2FE product characteristics ................45 4.2.1.2 SCALANCE X306-1LD FE product characteristics..............46...
  • Page 8 19" rack mounting - XR-300M EEC product group ..............108 Inserting media modules and SFP transceivers ............... 112 5.3.1 Installation and removal of media modules................112 5.3.2 SFP installation in SFP media module..................117 Connecting ............................121 Connecting the switch ....................... 121 SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 9 Further properties of XR-300M ....................166 Technical specifications for X-300EEC..................167 8.4.1 X-300EEC construction, installation and environment ..............167 8.4.2 Connectors and electrical data X-300EEC ................169 8.4.3 X-300EEC cable lengths......................171 8.4.4 Further properties of the X-300EEC ..................171 SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 10 X-300EEC approvals and certificates ..................219 9.4.2 X-300EEC declaration of conformity..................223 9.4.3 Overview of the approvals for the X-300EEC ................223 9.4.4 X-300EEC mechanical stability (in operation)................224 XR-300M EEC product group ....................224 SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 11 SFP dimension drawings ......................270 11.8 X-300M PoE dimension drawings....................271 11.9 XR-300M PoE dimension drawings ...................273 Appendix..............................275 TP port ............................275 Fitting the IE FC RJ-45 Plug ......................276 Electrical tests (EEC devices)....................278 Glossary ..............................281 Index..............................289 SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 12: Scalance X

    Table of contents SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 13: Safety Instructions

    National Electrical Code (r) (ANSI / NFPA 70). There is an additional requirement if devices are operated with a redundant power supply: If the equipment is connected to a redundant power supply (two separate power supplies), both must meet these requirements. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 14 Provisions shall be made to prevent the rated voltage from being exceeded by transient voltage surges of more than 40%. This criterion is fulfilled, if supplies are derived from SELV (Safety Extra-Low Voltage) only. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 15 ● Installation in a suitable cabinet. ● Installation in a suitable enclosure. ● Installation in a suitably equipped, enclosed control room. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 16 Safety instructions SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 17: Introduction

    300 ms. Support of IT standards such as VLAN, RSTP, IGMP, and GARP makes seamless integration of automation networks in existing office networks possible. The IE Switches X-300 are designed for use in switching cubicles and cabinets. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 18 As a result, a functional, end-to-end structure is restored. For information on this topic, refer to the Configuration Manual "SIMATIC NET - Industrial Ethernet Switches SCALANCE X-300 SCALANCE X-400." SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 19: Product Overview

    SC port 1000 Mbps single mode FO cable (up to max. 10 km). SC port 1000 Mbps single mode FO cable (up to max. 40 km). SC port 1000 Mbps single mode FO cable (up to max. 70 km). SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 20: Designs Of The Ie Switch X-300 Devices

    2.2.2 Designs of the IE Switch X-300 devices Designs and variants of the IE Switch X-300 The IE switches of the SCALANCE X-300 product line can have the following designs and variants: Designs of the IE Switch X300 Compact devices: IE switches X-300 (3 sizes: 60, 120, 180) Rack devices (R): 19"...
  • Page 21: X-300 Product Group

    X-300 product group Type Order number X304-2FE 6GK5 304-2BD00-2AA3 X306-1LD FE 6GK5 306-1BF00-2AA3 X307-3 6GK5 307-3BL00-2AA3 X307-3LD 6GK5 307-3BM00-2AA3 X308-2 6GK5 308-2FL00-2AA3 X308-2LD 6GK5 308-2FM00-2AA3 X308-2LH 6GK5 308-2FN00-2AA3 X308-2LH+ 6GK5 308-2FP00-2AA3 X310 6GK5 310-0FA00-2AA3 SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 22 Product family Product line Number of Hyphen Number of LD = Long Blank = FE = Fast electrical optical Distance separator for Ethernet X = SCALANCE X 3 = 300 ports (20) ports (3) extension SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 23: Product Group X-300M

    (1 x 100 to 240 V AC, cable [6GK5 324-0GG00-3AR2] outlet front) XR324-12M (2 x 24 V DC, cable outlet rear) [6GK5 324-0GG00-1HR2] XR324-12M (1 x 100 to 240 V AC, cable [6GK5 324-0GG00-3HR2] outlet rear) SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 24: X-300Eec Product Group

    2 x power supply unit 100 to 240 VAC / 60 to 250 VDC 6GK5307-2FD00-4EA3 2 x power supply unit 100 to 240 VAC / 60 to 250 VDC 6GK5307-2FD00-4GA3 Printed board varnished * See naming key below SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 25: Xr-300M Eec Product Group

    (2 x 24 V DC, cable outlet rear) [6GK5 324-4GG00-2JR2] XR324-4M EEC (1 x 100 to 240 V AC, cable [6GK5 324-4GG00-3JR2] outlet rear) XR324-4M EEC (2 x 100 to 240 V AC, cable [6GK5 324-4GG00-4JR2] outlet rear) SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 26: Product Group X-300M Poe

    ● 4-pin terminal block for the power supply ● 2-pin terminal block for the signaling contact ● Operating Instructions (compact) ● Product CD with documentation and software Order numbers Type Order number X308-2M PoE 6GK5 308-2QG00-2AA2 SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 27: Product Group Xr-300M Poe

    1 x 100 V to 240 V AC, 6GK5 324-4QG00-3HR2 cable outlet front 1 x 24 V DC, PoE 6GK5 324-4QG00-1AR2 cable outlet rear 1 x 100 V to 240 V AC, 6GK5 324-4QG00-3AR2 cable outlet rear SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 28: Mm900 Media Modules

    (2 x 1000 Mbps, SC ports optical, single mode FO [6GK5 992-2AP00-8AA0] cable, up to max. 70km) 9922AP MM992-2ELH (2 x 1000 Mbps, SC ports optical, single mode FO [6GK5 992-2AQ00-8AA0] cable, up to max. 120km) 9922AQ SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 29: Sfp Transceiver

    SC port 1000 Mbps single mode FO cable (up to max. 120 km) SFP media module 2.2.11 SFP transceiver NOTICE Only the media module MM992-2SFP may be fitted with approved SFP transceivers. The SFP media module can be fitted with up to two SFPs. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 30 * form factor product ports pluggable name) SFP991-1LH+ 1 = 100 Mbps SFP992-1ELH 2 = 1000 Mbps LD (Long Distance ), LH (Long Haul), LH+ (Long Haul +), ELH (Extreme Long Haul) SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 31: Network Topologies

    Star/tree structure Functional description Star/tree structures can be created with the IE Switches X-300. The cascading depth and total span of a network are limited only by the signal propagation times of the communication connections. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 32: Ring With Redundancy Manager

    ● Optical: SCALANCE X-400, SCALANCE X-300, SCALANCE X-200 ● Electrical: SCALANCE X-400, SCALANCE X-300, SCALANCE X-200 or ESM Functional description The two ends of the bus are closed to form a ring by a IE Switch X-300 operating as a redundancy manager.
  • Page 33 The redundancy manager function is enabled by the SELECT/SET button or by a setting in the software. For more detailed information, refer to the configuration manual "SCALANCE X-300 and SCALANCE X-400 Industrial Ethernet Switches". In contrast to the ring ports of the redundancy clients, the ring ports of the redundancy manager are disconnected when the network is operating problem-free.
  • Page 34 Sample configurations with IE Switch X-300, SIMATIC S7-200/300/400, operator control and monitoring system, H system, and PC as end devices. Figure 3-3 Gigabit ring with redundancy manager (RM) Figure 3-4 Ring with FO cable and redundancy manager SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 35: Options Of Media Redundancy

    On the S7 Ethernet CP modules, the ring ports are indicated by an "R" after the port number. Note Create the configuration of the devices to be connected to form a ring before you close the ring. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 36: Mrp

    The "MRP" method conforms to the Media Redundancy Protocol (MRP) specified in the standard IEC 61158 Type 10 "PROFINET". The reconfiguration time after an interruption of the ring is a maximum of 0.2 seconds. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 37 CP 1604 (6GK1 160-4AA00) as of firmware version V2.2 – Non-Siemens devices that support this functionality. Further Siemens devices are planned that will support MRP. ● All devices must be interconnected via their ring ports. ● If you configure in STEP 7, MRP must be enabled on all devices in the ring (see "MRP configuration in PROFINET IO").
  • Page 38 Non MRP-compliant devices can be connected to the ring via a SCALANCE X switch or via a PC with a CP 1616. Note SCALANCE X-300 - modular devices (M) Remember that in the modular switches the ring ports are located on MM900 media modules.
  • Page 39: Hsr

    ● On all other devices in the ring, either the "HSR Client" or "Automatic Redundancy Detection" mode must be activated. You can do this with Web Based Management, CLI or SNMP. ● In the basic status, the "HSR Client" or "Automatic Redundancy Detection" mode is set as default. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 40: Redundant Coupling Of Network Segments

    Redundant coupling of two subnets in mixed operation with SCALANCE X310 and SCALANCE X308-2 In this case, network segments are rings with a redundancy manager (RM). The rings can also be interrupted at one point (linear topology). SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 41 This configuration is set in Web Based Management, Command Line Interface or using SNMP access. For more detailed information, refer to the "Configuration Manual SCALANCE X-300 and SCALANCE X-400 Industrial Ethernet Switches". The two IE Switches X-300 connected in the configuration exchange data frames with each other to synchronize their operating statuses (one device is master and the other slave).
  • Page 42 Network topologies 3.5 Redundant coupling of network segments SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 43: Description Of The Device

    Description of the device Compatibility of SCALANCE X-300 Compatibility list Note Modular devices (M) The MM900 media modules and the SFP transceivers are used only in modular devices (M). The following products and devices are compatible with IE Switches X-300: ●...
  • Page 44 ESM/OSM SCALANCE X-200 SCALANCE X-200IRT SCALANCE XF200 SCALANCE XF204IRT SCALANCE X-300 (it may be necessary to configure other ring ports) SCALANCE X-400 – Optical ring structure: SCALANCE X-400 SCALANCE X-300 (exceptions SCALANCE X310 and SCALANCE X310FE) ● Redundant coupling of networks –...
  • Page 45: Product Groups

    Figure 4-1 X304-2FE Column Port number Connection type No marking → Fast Ethernet port electrical ) marking → gigabit Ethernet port Connection type ) marking → Fast Ethernet port optical ) marking → gigabit port SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 46: Scalance X306-1Ld Fe Product Characteristics

    Column Port number P1 * Connection type No marking → Fast Ethernet port electrical ) marking → gigabit Ethernet port Connection type ) marking → Fast Ethernet port optical ) marking → gigabit port SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 47: Scalance X307-3 Product Characteristics

    P8 * P9 * P10 * Connection type No marking → Fast Ethernet port electrical ) marking → gigabit Ethernet port Connection type ) marking → Fast Ethernet port optical ) marking → gigabit port SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 48: Scalance X307-3Ld Product Characteristics

    P8 * P9 * P10 * Connection type No marking → Fast Ethernet port electrical ) marking → gigabit Ethernet port Connection type ) marking → Fast Ethernet port optical ) marking → gigabit port SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 49: Scalance X308-2Lh Product Characteristics

    P8 * P9 * P10 * Connection type No marking → Fast Ethernet port electrical ) marking → gigabit Ethernet port Connection type ) marking → Fast Ethernet port optical ) marking → gigabit port SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 50: Scalance X308-2Lh+ Product Characteristics

    P8 * P9 * P10 * Connection type No marking → Fast Ethernet port electrical ) marking → gigabit Ethernet port Connection type ) marking → Fast Ethernet port optical ) marking → gigabit port SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 51: Scalance X310Fe Product Characteristics

    SCALANCE X310FE Column Port number Connection type No marking → Fast Ethernet port electrical ) marking → gigabit Ethernet port Connection type ) marking → Fast Ethernet port optical ) marking → gigabit port SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 52: Scalance X308-2 Product Characteristics

    P8 * P9 * P10 * Connection type No marking → Fast Ethernet port electrical ) marking → gigabit Ethernet port Connection type ) marking → Fast Ethernet port optical ) marking → gigabit port SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 53: Scalance X308-2Ld Product Characteristics

    P8 * P9 * P10 * Connection type No marking → Fast Ethernet port electrical ) marking → gigabit Ethernet port Connection type ) marking → Fast Ethernet port optical ) marking → gigabit port SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 54: Scalance X310 Product Characteristics

    P8 * P9 * P10 * Connection type No marking → Fast Ethernet port electrical ) marking → gigabit Ethernet port Connection type ) marking → Fast Ethernet port optical ) marking → gigabit port SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 55: Scalance X320-1Fe Product Characteristics

    Column Port number P21 * Connection type No marking → Fast Ethernet port electrical ) marking → gigabit Ethernet port Connection type ) marking → Fast Ethernet port optical ) marking → gigabit port SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 56: Scalance X320-3Ld Fe Product Characteristics

    P21 * P22 * P23 * Connection type No marking → Fast Ethernet port electrical ) marking → gigabit Ethernet port Connection type ) marking → Fast Ethernet port optical ) marking → gigabit port SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 57: Product Group X-300M

    S2) depending on the application. End devices and other network segments are connected according to the media modules being used. Note When shipped, the slots for the media modules have a dummy cover fitted. Figure 4-13 SCALANCE X308-2M with dummy covers SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 58 Figure 4-14 SCALANCE X308-2M with MM992-2 and MM991-2 Column Slot number Media MM992-2 MM991-2 modules used Port number P1 * P5 *) P7 *) P2 * P3 * P6 *) P8 *) P4 * SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 59: Product Group Xr-300M

    S12) depending on the application. End devices and other network segments are connected according to the modules being used. Note When shipped, the slots for the media modules have a dummy cover fitted. Figure 4-15 SCALANCE XR324-12M with blind covers SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 60 Figure 4-16 SCALANCE XR324-12M with MM900 Slot number Media MM992-2CUC MM992-2CUC MM992-2CUC MM991-2 (SC) MM991-2 (SC) MM991-2 (SC) modules used Port number Slot number Media MM992-2CUC MM992-2CUC MM992-2CUC MM991-2 MM991-2 MM991-2 modules used Port number SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 61: X-300Eec Product Group

    ● Power supply unit – Single – Redundant ● Printed board – Varnished (suitable for aggressive environments) – Unvarnished This combination of versions results in the product variants listed in section X-300EEC product group (Page 24). SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 62 In a device with a varnished printed circuit board, you may only use a C-PLUG with a varnished board. To remove the C-PLUG, open the slider and close it again after inserting the C-PLUG. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 63 To increase mechanical stability, secure the IE FC RJ-45 PLUGs to this securing bracket with a cable binder. LEDs of the X-300EEC You will find the meaning of the individual LEDs in section “LED display”. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 64 The SCALANCE X302-7EEC has the following ports: ● 2 electrical gigabit ports (P8 to P9) ● 7 optical Fast Ethernet ports (P1 to P7) Figure 4-19 SCALANCE X302-7EEC Port number Connection type Optical Electrical Fast Ethernet Gigabit Ethernet SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 65 – 5 Fast Ethernet ports (P3 to P7) – 2 gigabit ports (P8, P9) ● 2 optical Fast Ethernet ports (P1, P2) Figure 4-20 SCALANCE X307-2EEC Port number Connection type Optical Electrical Electrical Fast Ethernet Fast Ethernet Gigabit SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 66: Xr-300M Eec Product Group

    IE Switch Order number SCALANCE XR324-4M EEC (1 x 24 V … 48 V, cable outlet front) 6GK5 324-4GG00-1ER2 SCALANCE XR324-4M EEC (2 x 24 V … 48 V, cable outlet front) 6GK5 324-4GG00-2ER2 SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 67 Gigabit Ethernet port → marking * Connection type Fast Ethernet port → marking * optical Gigabit port → marking * Connection type Type of attachment depending on module used → marking*) Module slot SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 68: Product Group X-300M Poe

    S2) depending on the application. End devices and other network segments are connected according to the media modules being used. Note When shipped, the slots for the media modules have a dummy cover fitted. Figure 4-22 SCALANCE X308-2M PoE with dummy covers SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 69 P1 (gigabit Ethernet) P5 (gigabit multimode fiber-optic cable, SC ports) (interface depends on SFP used) P2 (gigabit Ethernet) P3 (gigabit Ethernet) P6 (gigabit multimode P8(interface depends on SFP fiber-optic cable, SC ports) used) P4 (gigabit Ethernet) SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 70: Product Group Xr-300M Poe

     2 x FX1000  or 2 x SFP slots With FX, single mode fibers or multimode fibers are possible. Connecting end devices or other network segments does not depend on the module slots. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 71: Mm900 Media Modules

    Figure 4-26 MM992-2CU [9922SA] [Device labeling in square brackets] Note Only the media module MM992-2SFP may be fitted with approved SFP transceivers. The SFP media module can be fitted with up to two SFPs. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 72 Possible attachments The MM991-2LD media module has the following: ● 2 x 100 Mbps, BFOC port optical, (single mode glass), up to max. 26 km Figure 4-29 MM991-2LD [9912AC] [Device labeling in square brackets] SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 73 The MM991-2LH+ (SC) media module has the following: ● 2 x 100 Mbps, SC port optical, (single mode glass), up to max. 70 km Figure 4-32 MM991-2LH+ (SC) [9912AE] [Device labeling in square brackets] SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 74 Possible attachments The MM992-2LH media module has the following: ● 2 x 1000 Mbps, SC port optical, (single mode glass), up to max. 40 km Figure 4-35 MM992-2LH [9922AN] [Device labeling in square brackets] SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 75: General Notes On Mm900

    4.2.8.1 General notes on MM900 Note Use media modules only in an approved modular device ("M") Use an MM900 media module only in a device equipped with suitable slots for such modules. Example: X308-2M. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 76 Electrical RJ-45 ports without securing collar BFOC ports optical Optical SC ports SFP transceivers Only the SFP media module MM992-2SFP may be fitted with approved SFP transceivers. The SFP media module can be fitted with up to two SFPs. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 77: Sfp Transceiver

    ● 1 x 100 Mbps, LC port optical (single mode, glass) up to max. 26 km Figure 4-39 SFP991-1LD Possible attachments The SFP991-1LH+ transceiver has the following: ● 1 x 100 Mbps, LC port optical (single mode, glass) up to max. 70 km Figure 4-40 SFP991-1LH+ SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 78 ● 1 x 1000 Mbps, LC port optical (single mode, glass) up to max. 10 km Figure 4-42 SFP992-1LD Possible attachments The SFP992-1LH transceiver has the following: ● 1 x 1000 Mbps, LC port optical (single mode, glass) up to max. 40 km Figure 4-43 SFP992-1LH SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 79: General Notes On Sfp

    [6GK5 992-2AS00-8AA0] media module) 9922AS Note An SFP with multimode has a black clip and an SFP with single mode has a blue clip. To protect the pins, these are fitted with a dummy plug. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 80: Interfaces And Signaling Contact Of The Switches

    For 10 Mbps, at least a category 3 (Cat 3) and for 100 Mbps, at least a four-wire (2 x 2) category 5 (Cat 5) cable is necessary. Transmission range The maximum transmission range (segment length) is 100 m. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 81: 1000Base-T

    Two-way alternate transmission mode - it is only possible to either send or receive over the interfaces at any one time. ● Full duplex mode Two-way simultaneous - both communication partners can send and receive at the same time. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 82: Power Over Ethernet (Poe)

    As a PSE, the X308-2M PoE supplies PoE-compliant devices with power over Ethernet. The 48 V power required to supply the powered devices is generated internally on the switch, no extra power supply unit is necessary. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 83: Ports Of The Xr-300M Poe

    (type 1) for environment A , in other words power supply over Ethernet within a power supply system. For details of configuring and enabling PoE for individual ports, refer to the configuration manual SCALANCE X-300 / X-400 on the accompanying CD. Possible attachments The X308-2M PoE is a partially modular device and has 4 fixed ports and 2 slots for media modules.
  • Page 84: Isolation Between The Tp Ports

    (type 1) for environment A , in other words power supply over Ethernet within a power supply system. For details of configuring and enabling PoE for individual ports, refer to the configuration manual SCALANCE X-300 / X-400 on the accompanying CD. Possible attachments The XR324-4M PoE is a partially modular device and has 16 fixed ports and 4 slots for media modules.
  • Page 85: Ethernet Interfaces - Optical Ports

    Transmission with 1000Base-LX is defined in the IEEE 802.3z standard and is specified as 1000 Mbps transmission rate and full duplex. Transmission medium Data is transmitted over single mode FOC. The wavelength is 1310 nm or 1550 nm. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 86: Signaling Contact

    ● The connection or disconnection of a communication node on an unmonitored port does not lead to an error message. ● The signaling contact remains activated until the error/fault is eliminated or until the current status is entered in the fault mask as the new desired status. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 87: C-Plug (Configuration Plug)

    Inserting a C-PLUG that does not contain the configuration of a compatible device type, accidentally removing the C-PLUG or general malfunctions of the C-PLUG are signaled by the diagnostics mechanisms of the IE Switch (LEDs, WEB-based management, SNMP, CLI and PROFINET diagnostics). SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 88 1. Remove the cover. - right 2. Insert the C-PLUG in the intended slot. 3. Close the cover again correctly. X-300EEC Top of the housing 1. Open the slider. 2. Insert the C-PLUG. 3. Close the slider. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 89: Components Of The Product

    3. Close the slider. Components of the product Unpacking, checking 1. Make sure that the package is complete. 2. Check all the parts for transport damage. WARNING Do not use any parts that show evidence of damage! SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 90: Components Of The Product

    4.5 Components of the product 4.5.1 Components of the product The following components are supplied with a SCALANCE X-300: ● Device with C-PLUG exchangeable medium. ● A four-pin terminal block for the 24 VDC power supply. ● A two-pin terminal block for the signaling contact.
  • Page 91: X-300Eec Product Components

    2 x power supply unit 24 V DC,  ● 2 x 2-pin 2 x 4-pin ● ● printed board unvarnished [6GK5302-7GD00-2EA3] 2 x power supply unit 24 V DC,  printed board varnished [6GK5302-7GD00-2GA3] SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 92 ● V AC / 60...250 V DC Printed board unvarnished [6GK5307-2FD00-4EA3] 2 x power supply unit 100...240  V AC / 60...250 V DC Printed board varnished [6GK5307-2FD00-4GA3] BAK: Operating Instructions (compact) on paper SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 93: Components Of The Xr-300M Eec Product

    RJ-45 port electrical Module slots 10/100/1000 Mbps X308-2M PoE Components of the product The following parts ship with a SCALANCE X-300M PoE: ● Device with C-PLUG exchangeable medium ● 4-pin terminal block for the power supply SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 94: Components Of The Xr-324-4M Poe Product

    – A 2-pin terminal block for the signaling contact ● With devices with 24 V DC power supply: – 4-pin terminal block for the power supply – 2-pin terminal block for the signaling contact – 4 adhesive feet for desktop mounting SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 95: Components Shipped With The Mm900 Product

    Plug-in terminal block Device Product CD Transceiver (signaling (24V) contact) 4-pin 2-pin SFP991-1 ● ● SFP991-1LD ● ● SFP991-1LH+ ● ● SFP992-1 ● ● SFP992-1LD ● ● SFP992-1LH ● ● SFP992-LH+ ● ● SFP992-1ELH ● ● SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 96 Description of the device 4.5 Components of the product SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 97: Installation

    Unless stated otherwise, the mounting options listed below apply to all IE Switch X-300. Mounting position of the IE Switch X-300EEC CAUTION Only the normal mounting position with the cable outlets downwards is permitted. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 98: Overview Of The Methods Of Installation

    Media modules and SFP transceivers Media modules and SFP transceivers are used in modular devices. ● Media modules are used in the appropriate slots of the switch. ● SFP transceivers are used only in SFP media modules. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 99: Installing A Switch

    4. Fit the connectors for the signaling contact. 5. Insert the terminal blocks into the sockets on the IE Switch X-300. Figure 5-1 Mounting an IE Switch X-300 on a DIN rail (35 mm) SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 100: Installation On A Standard Rail

    2. Screw the IE Switch X-300 to the underside of the standard rail. 3. Connect the grounding of the switch according to the description in the section Connecting the grounding (Page 122). 4. Connect the power supply to the appropriate terminal block. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 101 To remove an IE Switch X-300 from the SIMATIC S7-300 standard rail, follow these steps: 1. Disconnect all connected cables. 2. Loosen the screws on the underside of the standard rail and lift the IE Switch X-300 away from the rail. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 102: Wall Mounting

    Wall mounting of the IE Switch X-300EEC To mount the IE Switch X-300EEC on a wall, you require an additional securing bracket. You will find the dimensions for a suitable securing bracket in section Graphics (Page 251). SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 103: 19" Rack Mounting

    CAUTION Four-point mounting If mechanical load is high, the device should be secured at four points. You will find more detailed information in the section "Mechanical stability in operation". SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 104 On the back of the housing, you will find the diagnostics port  of the device. (For more details, refer to Diagnostics port XR-300.) On the SCALANCE X-300M EEC, you will also find the connectors for the signaling contacts and power supply here. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 105 Fit the connectors for the power supply. Note that the SCALANCE X-300 is available for different power supplies (100 to 240 V AC and 24 V DC variants). Fit the remaining connectors, for example the signaling contact.
  • Page 106 See also installation of modular devices: - Installing media modules in a slot - Installing an SFP in an SFP media module. Turn the rack device (R) over and fit the four adhesive feet on the base. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 107: 19" Rack Mounting - X-300Eec Product Group

    Here, two X-300EEC devices are fastened together with plates before installation in the rack: – 1 plate as middle section (6 screws) – 2 plates on the outside (3 screws each) You will find dimension drawings of the plates in section X-300EEC dimension drawings (Page 260). SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 108: 19" Rack Mounting - Xr-300M Eec Product Group

    19" rack mounting - XR-300M EEC product group WARNING Use of approved components  Use only approved 19" cabinets.  Use only supplied mounting brackets. There are several ways of fixing the mounting brackets depending on the mounting position required. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 109 CAUTION Four-point mounting If mechanical load is high, the device should be secured at four points. You will find more detailed information in the section "Mechanical stability in operation". SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 110 On the back of the housing, you will find the diagnostics port  of the device. (For more details, refer to Diagnostics port XR-300.) On the SCALANCE X-300M EEC, you will also find the connectors for the signaling contacts and power supply here. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 111 Fit the connectors for the power supply. Note that the SCALANCE X-300 is available for different power supplies (100 to 240 V AC and 24 V DC variants). Fit the remaining connectors, for example the signaling contact.
  • Page 112: Inserting Media Modules And Sfp Transceivers

    Connecting media modules and SFP transceivers CAUTION Use only approved SFPs If you use components not approved by Siemens AG, in particular SFPs, Siemens cannot accept any responsibility for the correct functioning of the "Ethernet switch system" according to the specification.
  • Page 113 The following aspects can restrict the maximum permitted operating temperature:  The orientation of the carrier device.  The use of SFP transceivers.  The use of transceivers of the types LH, LH+ or ELH. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 114 – SFP991-1LD – SFP992-1 – SFP992-1LD NOTICE Slot number With modular devices (M), the MM900 media modules must be given a slot number. The slot number labels are supplied with the modular devices (M). SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 115 Pull out the handle on the selected media module. Place the media module in the guide rails of the device slot. The media module is correctly installed when it clips easily into the device. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 116 Before removing an MM900 media module, turn the switch off and allow the device to cool down first. 1. Remove all connectors from the media module. 2. Pull out the handle of the media module and remove the media module from the device slot. 3. Secure the dummy cover. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 117: Sfp Installation In Sfp Media Module

    SFP installation in SFP media module WARNING Use only approved SFPs If you use components not approved by Siemens AG, in particular SFPs, Siemens cannot accept any responsibility for the correct functioning of the Ethernet switch system according to the specification.
  • Page 118 Open the clip on the selected SFP and remove the blind plug. Close the clip again. Insert the SFP with the clip closed in the SFP media module. Notice: Closing the clip after insertion does not lock the device in the rack. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 119 2. Open the clip on the SFP and remove the SFP from the SFP media module. Notice: It must be possible to remove the SFP easy without using force. 3. Fit a blind plug to the SFP. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 120 Installation 5.3 Inserting media modules and SFP transceivers SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 121: Connecting

    The ring ports of the device being inserted in the ring were configured as ring ports. The required redundancy mode must also be enabled (see "Configuration Manual SCALANCE X-300 / X-400", section "X-300 Ring Configuration"). If the device is intended to operate as the redundancy manager, "Redundancy manager enabled" must also be set.
  • Page 122: Connecting Media Modules/Sfps

    ● 24 V DC variant: Grounding is via the mounting bracket on the device. ● 100 to 240 V AC variant: The device must be grounded using the grounding bolts on the rear of the device. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 123: Grounding Of The X-300Eec

    It is essential that you connect the main protective conductor for the X-300EEC with multirange power supply unit 100...240 V AC / 60...250 V DC via the housing bolts on the bottom of the device. Figure 6-1 Grounding bolts on the bottom of the X-300EEC housing SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 124: Power Supply

    Cable outlet front or rear There are devices with single (1 x 24 V) or redundant power supply (2 x 24 V). The cable outlet can be to the front or rear on the device. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 125: Safety Extra Low Voltage

    L1+ 24 V DC Pin 2 Pin 3 Pin 4 L2+ 24 V DC 6.4.1.2 Safety extra low voltage Table 6- 2 Power supply for a SCALANCE X-300 Type 24 V safety extra-low voltage (SELV), redundant X304-2FE ● X306-1LD FE ● X307-3 ●...
  • Page 126: X-300M Product Group

    Device variants with 1 or 2 power supply units There are device variants with one power supply unit and with two power supply units. Connect the power supply as described below to achieve a correlation between the pin assignment and LED display. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 127 ● If the power supply fails at pins L1/M1 of terminal block "X1", this is indicated by LED L1. ● If the power supply fails at pins L1/M1 of terminal block "X2", this is indicated by LED L2. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 128: 24 V Product Group Xr300M Poe

    IE Switch X-300 alone. ● The power supply is connected over a high resistance with the enclosure to allow an ungrounded set up. The two power inputs are non-floating. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 129: Ac Power Supply

    Devices with a 100 to 240 V AC power supply do not have an ATEX approval. Devices with a 100 to 240 V AC power supply are not approved for use in hazardous areas according to EC-RL-94/9 (ATEX). SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 130: Fitting The Connector For 100 To 240 V Ac

    The connector can only fitted correctly to two-wire cables. If used with cables with more than two cores, correct functioning of the connector casing cannot be guaranteed. In this case, human life may be endangered by the line voltage because the two halves of the casing can separate! SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 131 Cut off the excess cable tie. 4. Fit the upper part of the housing. The housing is correctly mounted when the two catches audibly click into place and are flush with the surface of the housing. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 132: Connecting The Power Supply 100

    ● The two power inputs are always non-floating. Terminal block assignment (2-pin) Table 6- 5 Pin assignment of the power supply 100 ...240 V AC Pin number Assignment Labeling Pin 1 L1 (100...240 V) Pin 2 SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 133: Connecting The Power Supply 100

    DC voltage is connected at the following terminals: ● Plus to "L" ● M to "N" Secure the firm seat of connectors and the terminal block by tightening the screws (does not apply to X-300EEC). SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 134: Connecting The 100 To 240 V Ac Power Supply With The Xr-300M Poe

    IE Switch X-300 alone. ● The two power inputs are always non-floating. Terminal block assignment (2-pin) Table 6- 7 Pin assignment of the power supply 100 ...240 V AC Assignment Labeling SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 135: Signaling Contact

    CAUTION Laying the connecting cables of the signaling contact with the X-300EEC To improve the EMC properties (surge protection), the two connecting cables of the signaling contact should be laid together. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 136: Ac / 60

    Securing cables with dangerous voltage Make sure that the connector cannot be released accidentally by pulling on the connecting cable. Lay the cables in cable ducts or cable channels and secure the cables, where necessary, with cable ties. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 137: Configuration, Displays And Display Elements

    2. Place the tongue in the opening on the module. 3. Press the slot number into the recess on the front of the housing with your finger. The slot number breaks out of the wheel. Figure 7-1 Slot number plate SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 138: Show Location

    The diagnostics port of a SCALANCE XR-300M is located on the rear of the device and is an RJ-11 jack. Connect this port to the serial interface (RS-232) of a PC. A connecting cable with suitable connectors ships with the XR-300M. Figure 7-2 Diagnostics port SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 139 D-sub (9-pin, female) Pin number Assignment Pin number Assignment n.c. n.c. n.c. RD (Receive Data) TD (Transmit Data) TD (Transmit Data) SG (Signal Ground) n.c. RD (Receive Data) SG (Signal Ground) n.c. n.c. n.c. n.c. n.c. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 140: The Set / Select Button

    3. The result of the action depends on the initial situation: – If the redundancy manager and media redundancy were disabled, media redundancy is also enabled after enabling the redundancy manager. – If you disable the redundancy manager, media redundancy remains enabled. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 141: Led Display

    Bad firmware image. During normal operation, the "F" LED provides the following information: LED color LED status Meaning during operation No operating problems The device has detected an error. The signaling contact opens. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 142 For devices with power supply unit 24 to 48 V DC: Limit 17 V For devices with a multiple range power supply unit 100 to 240 V AC / 60 to 250 V DC: Limit voltage = 46.5 V DC or 80 V AC SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 143 / lit Receiving data at port. With SCALANCE X-300 devices, both the receipt and the sending of data is indicated for the optical gigabit ports. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 144 The port is monitored, in other words, if no connection was established at the port (for example no cable inserted), this triggers the signaling contact and an error state results. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 145: Technical Specifications

    ● ● X308-2LH ● *) ● ● X308-2LH+ ● *) ● ● X310 ● *) ● ● X310FE ● *) ● ● X320-1 FE ● *) ● ● X320-3LD FE ● *) ● ● SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 146: Scalance X

    X320-3LD FE -40 °C to +60 °C -40 °C to +70 °C ‹ 95 % 2000 m at max. 56 °C as of hardware product version 01 (no condensation) 3000 m at max. 50 °C SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 147: X-300 Connectors And Electrical Data

    / full duplex) 3 x RJ-45 jacks with MDI-X assignment 10/100/1000 Mbps (half / full duplex) X310FE 10 x RJ-45 jacks with MDI-X 1 x 4-pin 1 x 2-pin assignment 10/100 Mbps (half / full duplex) SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 148 X308-2 ● 9.6 W X308-2LD ● 9.6 W X308-2LH ● 9.6 W X308-2LH+ ● 9.6 W X310 ● 9.6 W X310FE ● 9.6 W X320-1 FE ● 9.6 W X320-3LD FE ● 12 W SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 149 Electrical data: Transmitter output optical and receiver input Type Transmitter output optical Receiver input min. max. Sensitivity min. [dBm] max. input power [dBm] [dBm] [dBm] X304-2FE X306-1LD FE X307-3 -9.5 X307-3LD -9.5 X308-2 -9.5 X308-2LD -9.5 X308-2LH SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 150 The device is also equipped with 2 optical interface transceivers. (Fast Ethernet, long distance interface)  (Fast Ethernet, multimode interface)  For this reason, the electrical data in the technical specifications is divided into two parts: Transmitter output optical and receiver input. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 151: Cable Lengths X-300

    9 dB max. permitted FO cable attenuation at 3 dB link power margin) 9/125 µm single mode 0 -26 km fiber (0.5 dB/km at 1300 nm; maximum insertion loss 0.5 dB; 14 dB max. permitted FO cable attenuation at 2 dB link power margin) SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 152 *) – 70 km fiber (0.28 dB/km at 1550 nm; maximum insertion loss 0.5 dB, 21 dB max. permitted FO cable attenuation at 2 dB link power margin, *) minimum cable attenuation 8 dB) X310 SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 153: Further Properties Of X-300

    20 years X308-2 25 years X308-2LD 25 years X308-2LH 25 years X308-2LH+ 25 years X310 40 years X310FE 40 years X320-1 FE 25 years X320-3LD FE 15 years *) These values apply at 40 °C. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 154: X-300M Technical Specifications

    This means that the more IE Switch X-300 devices the frame passes through, the longer the frame delay. X-300M technical specifications 8.2.1 X-300M construction, installation and environment Note With modular devices (M), take the values of media modules and transceivers into account SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 155 Vertical mounting position/installation of the X308-2M reduces the maximum permitted ambient temperature If the device is installed in the vertical position, the maximum permitted ambient temperature is reduced to +50 °C. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 156: X-300M Connectors And Electrical Data

    Table 8- 21 Connector for power supply and signaling contact Device: (Variant) Plug-in terminal block for connecting: SCALANCE Power supply Power supply Signaling contact single redundant X308-2M 1 x 4 pin 1 x 2 pin SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 157 (Variant) Transmitter output optical Receiver input SCALANCE min. max. Sensitivity min. max. input power [dBm] [dBm] [dBm] [dBm] X308-2M Note: The values correspond to those of the permitted MM900 media modules and SFP transceivers. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 158: X-300M Cable Lengths

    SFP transceivers. 8.2.4 Further properties of X-300M Table 8- 30 Switching properties Device: (Variant) Max. number Aging time Switching Latency SCALANCE of learnable technique addresses X308-2M 8000 30 s Store and 5 μs forward SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 159  with a 64 byte frame length by approx. 10 microseconds (at 100 Mbps)  with a 1500 byte frame length by approx. 130 microseconds (at 100 Mbps) This means that the more IE Switch X-300 devices the frame passes through, the longer the frame delay. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 160: Xr-300M Technical Specifications

    Desktop operation is permitted only for the 24 V DC variants of the rack devices (R). The adhesive feet ship with the 24 V DC variants. In this case, the permitted ambient temperature is -40 °C to +50 °C. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 161  If you use more than two of these modules in other module slots, the maximum permitted ambient temperature of the SCALANCE is reduced to +50 °C. MM992-2SFP with SFP992-1 or SFP992-1LD  The maximum permitted ambient temperature of the SCALANCE when using these modules is +60 °C. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 162: Xr-300M Connectors And Electrical Data

    XR324-12M 2 x 24 V DC, cable outlet rear - 1 x 4-pin 1 x 2-pin XR324-12M 1 x 100 to 240 V AC, cable 1 x 2 pin 1 x 2-pin outlet rear SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 163 100 mA XR324-12M 2 x 24 V DC, cable outlet rear 24 V DC max. 100 mA XR324-12M 1 x 100 to 240 V AC, cable outlet rear 24 V DC max. 100 mA SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 164: Xr-300M Cable Lengths

    XR324-12M 1 x 100 to 240 V AC, cable outlet front and SFP transceivers. XR324-12M 2 x 24 V DC, cable outlet rear XR324-12M 1 x 100 to 240 V AC, cable outlet rear SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 165: Block Architecture Of The Xr-300

    When operating solely with Fast Ethernet (100 Mbps), the XR devices support full wire speed via all blocks. 1 Gbit/s 1 Gbit/s Figure 8-1 Block architecture of the XR324-12M 1 Gbit/s 1 Gbit/s Figure 8-2 Block architecture of the XR324-4M SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 166: Further Properties Of Xr-300M

    The number of packets depends on the packet length according to the IEEE802.3 standard: Table 8- 49 Full wire speed switching Number of frames At a frame length of (in bytes): at 100 Mbps at 1000 Mbps 148810 1488095 84459 844595 SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 167: Technical Specifications For X-300Eec

    (all variants) 216 x 203 x 99 (with   1 850 (1 power supply unit 100...240V AC / DC 60...250 bracket) 2 120 (2 power supply units 100...240V AC / DC 60...250  SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 168  (all variants) (IEEE1613 Class V.S.2) Frequency: 1...150 Hz   Acceleration: 15 g X-300EEC Shock (all variants) (IEC 60068-2-27) Duration of the pulse: 11 ms  Number of shocks per direction: 3  SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 169: Connectors And Electrical Data X-300Eec

    (46.25 to 300 V) (80 to 276 V ** 250 VDC With a redundant power supply unit 24 VDC, "L1" of both power supply units must be connected. 50/60 Hz AC ± 5 % SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 170 Values for glass fiber: 62.5 to 125 μm multimode Table 8- 61 Overvoltage category Device: General In the application range of EN 60255-27 SCALANCE X302-7EEC / X307-2EEC Overvoltage category II Overvoltage category III SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 171: X-300Eec Cable Lengths

    Further properties of the X-300EEC Table 8- 65 Switching properties of the SCALANCE X-300EEC (all variants) Max. number of learnable Aging time Switching technique Latency addresses 8000 30 s Store and forward 5 μs SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 172 2 x power supply unit 100...240 V AC / 60...250 V 6GK5307-2FD00-4GA3 16.1 Printed board varnished The IE Switches X-300 support "full wire speed switching" complying with IEEE 802.3 on all ports. The number of packets therefore depends on the packet length. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 173: Xr-300M Eec Technical Specifications

    1 x 100 to 240 V AC 483 x 44 x 305 IP20 1 height unit (1HU) 2 x 100 to 240 V AC 483 x 44 x 305 IP20 1 height unit (1HU) SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 174: Xr-300M Eec Connectors And Electrical Data

    1 x 24 V DC, cable outlet front ● 1 x 2-pin 2 x 24 V DC, cable outlet front ● 2 x 2-pin 1 x 100 to 240 V AC, cable outlet front ● 1 x 2-pin SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 175 Overcurrent protection at input Non-replaceable fuse (F) 24 V to 48 V DC T2H / 250 V 100 V to 240 V AC T2H / 250 V 60 V to 250 V DC T2H / 300 V SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 176 The MTBF value of the power supply unit is > 20 years. Table 8- 79 Overvoltage category Device General In the application range of EN 60255-27 X324-4M EEC Overvoltage category II Overvoltage category III SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 177: Xr-300M Eec Cable Lengths

    Device: (Variant) Fiber FO cable length SCALANCE XR324-4M EEC Note: The values correspond to those of the permitted MM900 media modules and SFP transceivers. Note Maximum insertion loss of 0.5 dB per SC connector. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 178: Further Properties Of Xr-300M Eec

    The number of packets depends on the packet length according to the IEEE802.3 standard: Table 8- 85 Full wire speed switching Number of frames at a frame length of (in bytes): at 100 Mbps at 1000 Mbps 148810 1488095 84459 844595 45290 452899 23496 234962 SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 179: Mm900 Technical Specifications

    2 x 1000 Mbps, SC ports optical, single mode FO cable, up to max. 70km MM992-2ELH 2 x 1000 Mbps, SC ports optical, single mode FO cable, up to max. 120km MM992-2SFP 2 x 100/1000 Mbps, SFP media module SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 180: Electrical Data

    Note Fusing and signal contacts with media modules The MM900 media modules do not have their own fuses and have no signaling contacts. The fuses and the signaling contacts exist in the SCALANCE device. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 181 2000 m at max. 56 °C temperature 3000 m at max. 50 °C [*] The hardware product version is shown on the device. You can also read out this information from the device with the WBM or the CLI. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 182 0.28 dB/km at 1550 nm, maximum insertion loss 0.5 dB, 26 dB max. permitted FO cable attenuation at 2 dB link power margin, minimum cable attenuation 3 dB Maximum lengths of FO cables for Gigabit Ethernet SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 183 Maximum length MM992-2SFP Depending on the SFP transceiver used. Mean time between failure (MTBF) Media module MTBF MM992-2CUC > 250 years MM992-2CU > 250 years MM992-2SFP Without components > 250 years MM991-2 > 55 years SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 184: Sfp Technical Specifications

    SFP installation in SFP media module SFP991-1 (1 x 100 Mbps, LC port optical, ● multimode glass, up to max. 3 km) SFP991-1LD (1 x 100 Mbps, LC port optical, single ● mode glass, up to max. 26 km) SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 185 (1 x 1000 Mbps, LC port optical, single -40 °C through -40 °C to ‹ 95 % 2000 m at max. 56 °C mode glass, up to max. 120km) +85 °C +85 °C (no condensation) 3000 m at max. 50 °C SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 186: Sfp Connectors And Electrical Data

    (1 x 1000 Mbps, LC port optical, single mode glass, up to max. 120km) 0.63 W *) Note: SFP values in 25 °C environment. Note Fusing of transceivers The SFP transceivers do not have fuses. The fuse is in the modular device (M). SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 187 40km) SFP992-LH+ (1 x 1000 Mbps, LC port optical, single mode glass, up to max. 70km) SFP992-1ELH (1 x 1000 Mbps, LC port optical, single mode glass, up to max. 120km) SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 188: Cable Lengths For Sfp

    (0.4 dB/km at 1550 nm; up to max. 40km) maximum insertion loss 0.5 dB, 18 dB max. permitted FO cable attenuation at 2 dB link power margin, *) minimum cable attenuation 3 dB) SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 189: Other Properties Of Sfp

    The number of packets depends on the packet length according to the IEEE802.3 standard: Table 8- 95 Full wire speed switching Number of frames At a frame length of (in bytes): at 100 Mbps at 1000 Mbps 148810 1488095 84459 844595 45290 452899 23496 234962 SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 190: X-300M Poe Technical Specifications

    All values apply to the switch without media modules inserted. When used in shipbuilding, installation on a 35 mm DIN rail is not permitted. In ships, the 35 mm DIN rail does not provide adequate support. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 191 The hardware product version is shown on the product. You can also read out this information from the device with the WBM or the CLI. For information on mechanical stability, refer to section “X-300M PoE mechanical stability in operation”. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 192: Connectors And Electrical Data

    Redundant power supply units Connector 1 x 4-pin plug-in terminal block 24 V DC signaling contact Power 24 V DC Connector for signaling contact 1 x 2-pin plug-in terminal block Switching capacity (resistive load) max. 100 mA SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 193: Cable Lengths

    ● Permitted cable lengths (fiber-optic) Fast Ethernet: Depending on the approved MM900 media modules and SFP transceivers used ● Permitted cable lengths (fiber-optic) gigabit: Depending on the approved MM900 media modules and SFP transceivers used SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 194: Switching And Other Properties

    Table 8- 101 Example of the frame delays caused by latency at 100 Mbps Frame length Delay resulting from latency 64 bytes by approximately 10 microseconds 1 500 bytes by approximately 130 microseconds SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 195: Xr-300M Poe Technical Specifications

    MM992-2SFP and the following SFP transceivers * , ** SFP991-1 SFP991-1LD SFP992-1 SFP992-1LD Operating temperature with media module -40 °C to +50 °C MM992-2SFP and the following SFP transceivers * , ** SFP991-1LH+ SFP992-1LH SFP992-1LH+ SFP992-1ELH SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 196: Connectors And Electrical Data

    46 W Overcurrent protection of the power Non-replaceable fuse supply 24 V DC device variant: T 5 A / 250 V  230 V AC device variant: T 2 A / 500 V  SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 197 1 x 2-pin plug-in terminal block 24 V DC signaling contact Power 24 V DC Connector for signaling contact 1 x 2-pin plug-in terminal block Switching capacity (resistive load) max. 100 mA Diagnostics port Diagnostics port RJ-11 jack SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 198: Cable Lengths

    ● Permitted cable lengths (fiber-optic) Fast Ethernet: Depending on the approved MM900 media modules and SFP transceivers used ● Permitted cable lengths (fiber-optic) gigabit: Depending on the approved MM900 media modules and SFP transceivers used SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 199: Switching And Other Properties

    Table 8- 107 Example of the frame delays caused by latency at 100 Mbps Frame length Delay resulting from latency 64 bytes by approximately 10 microseconds 1 500 bytes by approximately 130 microseconds SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 200: Block Architecture Of The Xr-300M Poe

    When operating solely with Fast Ethernet (100 Mbps), the XR devices support full wire speed via all blocks. 1 Gbit/s 1 Gbit/s Figure 8-3 Block architecture of the XR324-4M PoE SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 201: Approvals, Certificates, Standards

    The installation of expansions that are not approved for SIMATIC NET products or their target systems may violate the requirements and regulations for safety and electromagnetic compatibility. Only use expansions that are approved for the system. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 202 Note for the manufacturers of machines This product is not a machine in the sense of the EC Machinery Directive. There is therefore no declaration of conformity relating to the EC Machinery Directive 89/392/EEC for this product. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 203  "Approval of SIMATIC/ SIMATIC NET Products for Direct Installation in Ex-Zone 2" You will find this on the Internet on the pages of Siemens Industry Automation Customer Support under the following entry ID: 33118441 (http://support.automation.siemens.com/WW/view/en/33118441)
  • Page 204 ● UL 60950-1 (Information Technology Equipment) ● CSA C22.2 No. 60950-1-03 ● UL 1604 and 2279-15 (Hazardous Location) Approved for use in Cl. 1, Div. 2, GP. A, B, C, D, T4 Cl. 1, Zone 2, GP. IIC T4 SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 205: X-300 Type Plate

    Example English: "Declaration of Conformity SCALANCE X310". 9.1.4 X-300 FDA and IEC approvals The following devices meet the FDA and IEC requirements listed below: Type Fulfills FDA and IEC requirements X304-2FE ● X306-1LD FE ● X307-3 X307-3LD ● X308-2 SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 206: Overview Of The X-300 Approvals

    ● ● ● ● ● X310 ● ● ● ● ● ● X310FE ● ● ● ● ● ● X320-1FE ● ● ● ● ● ● X320-3LD FE ● ● ● ● ● ● SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 207: Mechanical Stability (In Operation)

    The specified approvals apply only when the corresponding mark is printed on the product. You can check which of the following approvals have been granted for your product by the markings on the type plate. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 208 The product was tested with a device that also complies with the standards listed above. If the product is operated with a device that does not meet these standards, there is no guarantee that the corresponding values will be adhered to. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 209  "Approval of SIMATIC/ SIMATIC NET Products for Direct Installation in Ex-Zone 2" You will find this on the Internet on the pages of Siemens Industry Automation Customer Support under the following entry ID: 33118441 (http://support.automation.siemens.com/WW/view/en/33118441)
  • Page 210 Underwriters Laboratories Inc. complying with ● UL 60950-1 (Information Technology Equipment) ● CSA C22.2 No. 60950-1-03 cULus Approval for Industrial Control Equipment cULus Listed 69B1 Underwriters Laboratories Inc. complying with ● UL 508 ● CSA C22.2 No. 142-M1987 SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 211: X-300M Type Plate

    You will find the EC Declaration of Conformity for these products on the Internet at the following address: http://support.automation.siemens.com/WW/view/en/10805868 --> Entry list --> Entry type "Certificates" --> Certificate type "Declaration of Conformity" Example German: "EG-Konformitätserklärung SCALANCE X310", Example English: "Declaration of Conformity SCALANCE X310". SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 212: X-300M Fda And Iec Approvals

    ● ● ● ● For temperature information "T.." or the maximum ambient temperature "Ta:..", refer to the type plate. Note Shipbuilding approval No applications for shipbuilding approvals will be made for the SCALANCE xxx. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 213: X-300M Mechanical Stability (In Operation)

    The SIMATIC NET product meets the requirements of the EC Directive: 2004/108/EEC "Electromagnetic Compatibility" The product is designed for use in the following areas: Area of application Requirements Emission Immunity Industrial area EN 61000-6-4: 2007 EN 61000-6-2: 2005 SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 214 Note for the manufacturers of machines This product is not a machine in the sense of the EC Machinery Directive. There is therefore no declaration of conformity relating to the EC Machinery Directive 89/392/EEC for this product. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 215  "Approval of SIMATIC/ SIMATIC NET Products for Direct Installation in Ex-Zone 2" You will find this on the Internet on the pages of Siemens Industry Automation Customer Support under the following entry ID: "Entry list"...
  • Page 216: Xr-300M Type Plate

    ● UL 1604 and 2279-15 (Hazardous Location) Approved for use in Cl. 1, Div. 2, GP. A, B, C, D, T4 Cl. 1, Zone 2, GP. IIC T4 See also ID = 28518276 (http://support.automation.siemens.com/WW/view/en/28518276) ID = 8763736 (http://support.automation.siemens.com/WW/view/en/8763736) 33118441 (http://support.automation.siemens.com/WW/view/en/33118441) 9.3.2 XR-300M type plate...
  • Page 217: Xr-300M Conformity Certificate

    The 24 V DC variants do not have an E1 approval. The 100 to 240 V AC variants have C-Tick and CE approvals but are only UL508 listed. They do not have UL hazloc, FM or ATEX approvals. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 218: Xr-300M Mechanical Stability (In Operation)

    ● XR324-12M (2 x 24 V DC, cable outlet rear) ● ● ● XR324-12M (1 x 100...240 V AC, cable outlet rear) ● ● ● *) Note: When rack mounted with 4 securing points SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 219: X-300Eec Product Group

    The installation of expansions that are not approved for SIMATIC NET products or their target systems may violate the requirements and regulations for safety and electromagnetic compatibility. Only use expansions that are approved for the system. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 220 The very latest documentation is available on the Internet! You will find the installation instructions documentation on the Internet on the pages of Siemens Industry Automation Customer Support under the following entry ID: – SIMATIC NET Industrial Twisted Pair and Fiber Optic Networks Manual 8763736 (http://support.automation.siemens.com/WW/view/en/8763736)
  • Page 221  "Approval of SIMATIC/ SIMATIC NET Products for Direct Installation in Ex-Zone 2" You will find this on the Internet on the pages of Siemens Industry Automation Customer Support under the following entry ID: 33118441 (http://support.automation.siemens.com/WW/view/en/33118441)
  • Page 222 ● ANSI / ISA 12.12.01 ● CSA C22.2 No. 213-M1987 ● UL 1604 and 2279-15 Approved for use in Cl. 1, Div. 2, GP. A, B, C, D, T4 Cl. 1, Zone 2, GP. IIC T4 SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 223: X-300Eec Declaration Of Conformity

    II 3 G Ex nA II T4 KEMA nn ATEX nnnnX Power supply 24 to 48 V DC ● ● ● ● Power supply 100 to 240 V AC ● ● ● / 60 to 250 V DC SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 224: X-300Eec Mechanical Stability (In Operation)

    The SIMATIC NET product meets the requirements of the EC Directive: 2004/108/EEC "Electromagnetic Compatibility" The product is designed for use in the following areas: Area of application Requirements Emission Immunity Industrial area EN 61000-6-4: 2007 EN 61000-6-2: 2005 SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 225: Scalance X

    Note for the manufacturers of machines This product is not a machine in the sense of the EC Machinery Directive. There is therefore no declaration of conformity relating to the EC Machinery Directive 89/392/EEC for this product. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 226  "Approval of SIMATIC/ SIMATIC NET Products for Direct Installation in Ex-Zone 2" You will find this on the Internet on the pages of Siemens Industry Automation Customer Support under the following entry ID: "Entry list"...
  • Page 227 ● UL 60950-1 (Information Technology Equipment) ● CSA C22.2 No. 60950-1-03 ● UL 1604 and 2279-15 (Hazardous Location) Approved for use in Cl. 1, Div. 2, GP. A, B, C, D, T4 Cl. 1, Zone 2, GP. IIC T4 SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 228: Xr-300M Eec Declaration Of Conformity

    ● cable outlet front) XR324-4MEEC (1 x 24 V DC, ● ● ● ● ● ● cable outlet rear) XR324-4MEEC (2 x 24 V DC, ● ● ● ● ● ● cable outlet rear) SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 229: Xr-300M Eec Mechanical Stability (In Operation)

    15 g , 11 ms duration 6 shocks per axis ● IEC 60068-2-6 (vibrations during transportation) Test parameters: 10 – 58 Hz: 0.075 mm 85 – 150 Hz: 1 g 1 octave/min, 20 sweeps SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 230: Product Group X-300M Poe

    The installation of expansions that are not approved for SIMATIC NET products or their target systems may violate the requirements and regulations for safety and electromagnetic compatibility. Only use expansions that are approved for the system. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 231 The very latest documentation is available on the Internet! You will find the installation instructions documentation on the Internet on the pages of Siemens Industry Automation Customer Support under the following entry ID: – SIMATIC NET Industrial Twisted Pair and Fiber Optic Networks Manual 8763736 –...
  • Page 232  "Approval of SIMATIC/ SIMATIC NET Products for Direct Installation in Ex-Zone 2" You will find this on the Internet on the pages of Siemens Industry Automation Customer Support under the following entry ID: "Entry list"...
  • Page 233: X-300M Poe Declaration Of Conformity

    CSA C22.2 No. 60950-1-03 CSA C22.2 No. 213-M1987 UL 1604 and 2279-15 CL.1, Div.2 Gp.A.B.C.D T4 CL.1, Zone 2, Gp.IIC, T4 ● ● ● For temperature information "T.." or the maximum ambient temperature "Ta:..", 60° C applies. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 234: X-300M Poe Mechanical Stability In Operation

    For temperature information "T.." or the maximum ambient temperature "Ta:..", 60° C applies. Note Shipbuilding approval You will find shipbuilding approvals on the Internet on the pages of Siemens Industry Automation Customer Support under the following entry ID: "Entry list" tab > entry type "Certificates"...
  • Page 235: Product Group Xr-300M Poe

    The installation of expansions that are not approved for SIMATIC NET products or their target systems may violate the requirements and regulations for safety and electromagnetic compatibility. Only use expansions that are approved for the system. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 236 The very latest documentation is available on the Internet! You will find the installation instructions documentation on the Internet on the pages of Siemens Industry Automation Customer Support under the following entry ID: – SIMATIC NET Industrial Twisted Pair and Fiber Optic Networks Manual 8763736 –...
  • Page 237: X-300M Poe Declaration Of Conformity

    5 to 8.51 Hz: 3.5 mm 8.51 – 500 Hz: 1 g 1 octave/min, 20 sweeps IEC 60068-2-27 (shock) ● Mounting in the rack (2-point mounting): 15 g, 11 ms duration, 6 shocks per axis SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 238: Mm900 Product Group

    The installation of components, accessories and expansions that are not approved for SIMATIC NET products or their target systems may violate the requirements and regulations for safety and electromagnetic compatibility. Only use components that are approved for the system. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 239 The very latest documentation is available on the Internet! You will find the installation instructions documentation on the Internet on the pages of Siemens Industry Automation Customer Support under the following entry ID: – SIMATIC NET Industrial Twisted Pair and Fiber Optic Networks Manual 8763736 (http://support.automation.siemens.com/WW/view/en/8763736)
  • Page 240  "Approval of SIMATIC/ SIMATIC NET Products for Direct Installation in Ex-Zone 2" You will find this on the Internet on the pages of Siemens Industry Automation Customer Support under the following entry ID: 33118441 (http://support.automation.siemens.com/WW/view/en/33118441)
  • Page 241: Mm900 Declaration Of Conformity

    Fulfills FDA and IEC requirements MM992-2CUC MM992-2CU MM992-2SFP MM991-2 MM991-2LD ● MM991-2 (SC) MM991-2LD (SC) ● MM991-2LH+ (SC) ● MM992-2 ● MM992-2LD ● MM992-2LH ● MM992-2LH+ ● MM992-2ELH ● Figure 9-7 FDA and IEC approvals SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 242: Product Group Sfp

    The installation of expansions that are not approved for SIMATIC NET products or their target systems may violate the requirements and regulations for safety and electromagnetic compatibility. Only use expansions that are approved for the system. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 243 Note for the manufacturers of machines This product is not a machine in the sense of the EC Machinery Directive. There is therefore no declaration of conformity relating to the EC Machinery Directive 89/392/EEC for this product. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 244  "Approval of SIMATIC/ SIMATIC NET Products for Direct Installation in Ex-Zone 2" You will find this on the Internet on the pages of Siemens Industry Automation Customer Support under the following entry ID: 33118441 (http://support.automation.siemens.com/WW/view/en/33118441)
  • Page 245: Sfp Type Plate

    You will find the EC Declaration of Conformity for these products on the Internet at the following address: http://support.automation.siemens.com/WW/view/en/10805868 --> Entry list --> Entry type "Certificates" --> Certificate type "Declaration of Conformity" Example German: "EG-Konformitätserklärung SCALANCE X310", Example English: "Declaration of Conformity SCALANCE X310". SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 246: Sfp Fda And Iec Approvals

    Overview of the SFP approvals Note The SFP transceivers only have UL60950, C-Tick, CE, FM and ATEX approvals. The other approvals are device approvals and are obtained for the device with the various components. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 247 120km) For temperature information "T.." or the maximum ambient temperature "Ta:..", refer to the table of environmental conditions. Note Shipbuilding approval The shipbuilding approval applies to all SFP transceivers. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 248: Sfp Mechanical Stability (In Operation)

    SFP992-LH+ (1 x 1000 Mbps, LC port ● ● optical, single mode glass, up to max. 70km) ● SFP992-1ELH (1 x 1000 Mbps, LC port ● optical, single mode glass, up to max. 120km) SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 249: Accessories

    20 = 10 duplex connectors FC BFOC coupler, 10 single couplings 6GK1900-1GP00-0AB0 FC SC coupler, 5 duplex couplings 6GK1900-1LP00-0AB0 C-PLUG SCALANCE X-200 / X-300 / X-400 / W-700 C-PLUG 6GK1900-0AB00 SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 250 Accessories 10.1 Accessories SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 251: Graphics

    Dimension drawing Note The IE Switches X-300 are available in small, medium and large variants. The dimension drawings are shown below. Small design Figure 11-1 Small design dimension drawing (example used here SCALANCE X306-1LD FE) SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 252 Graphics 11.1 Dimension drawing Figure 11-2 Small design dimension drawing (IE Switch X-306) Medium design Figure 11-3 Medium design dimension drawing (example used here SCALANCE X308-2) SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 253 Graphics 11.1 Dimension drawing Figure 11-4 Medium design dimension drawing (IE Switch X-300) SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 254 Graphics 11.1 Dimension drawing Large design Figure 11-5 Large design dimension drawing Part 1 (example used here SCALANCE X320-3LD FE) Figure 11-6 Large design dimension drawing Part 2 (example used here SCALANCE X320-3LD FE) SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 255 Graphics 11.1 Dimension drawing Figure 11-7 Large design dimension drawing (IE Switch X-320) SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 256: X-300M Dimension Drawings

    Graphics 11.2 X-300M dimension drawings 11.2 X-300M dimension drawings Note The following dimension drawings are available for the X-300M product group. Figure 11-8 X308-2M dimension drawing SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 257: Xr-300M Dimension Drawings

    Graphics 11.3 XR-300M dimension drawings Figure 11-9 X308-2M drilling template 11.3 XR-300M dimension drawings Note The following dimension drawings are available for the XR-300M product group. Figure 11-10 Front view of the XR324-12M SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 258 Graphics 11.3 XR-300M dimension drawings Figure 11-11 XR324-12M from above SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 259 Graphics 11.3 XR-300M dimension drawings Figure 11-12 XR324-12M from above SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 260: X-300Eec Dimension Drawings

    Graphics 11.4 X-300EEC dimension drawings 11.4 X-300EEC dimension drawings All dimensions in the drawings are in millimeters Figure 11-13 Dimension drawing IE Switch X302-7EEC - view SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 261 Graphics 11.4 X-300EEC dimension drawings Figure 11-14 Dimension drawing IE Switch X302-7EEC - side view Figure 11-15 Dimension drawing IE Switch X302-7EEC - from above SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 262: Xr-300M Eec Dimension Drawings

    Graphics 11.5 XR-300M EEC dimension drawings 11.5 XR-300M EEC dimension drawings Figure 11-16 Housing front and rear Figure 11-17 Top of the housing SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 263 You will find other accessories, such as screws in the tables. If you have questions, contact our Customer Support. You will also find dimension drawings on the Internet on the pages of Siemens Industry Automation Customer Support under the following entry ID: 33118441 (http://support.automation.siemens.com/WW/view/en/33118441)
  • Page 264 Figure 11-19 Rack mounting of two X-300EECs fastened together (view from below) Table 11- 1 Legend for rack mounting of two X-300EECs fastened together Number needed Name Plate for side Spring washer SN60727-4-NrSt Hexagonal nut ISO 4032-M4-8 Mid part of mounting support SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 265 Graphics 11.5 XR-300M EEC dimension drawings Figure 11-20 Side part of mounting support for X-300EEC (dimensions in mm) Material: Plate 2.0 DIN EN10152 DC01+ZE25/25 SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 266 11.5 XR-300M EEC dimension drawings Figure 11-21 Middle part of mounting support for X-300EEC (dimensions in mm) Material: Plate 2.0 DIN EN10152 DC01+ZE25/25 See also 19" rack mounting - X-300EEC product group (Page 107) SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 267: Mm900 Dimension Drawings

    The following dimension drawings are available for the MM900 product group. Figure 11-22 MM900 dimension drawing 1: Electrical RJ-45 ports with securing collar Figure 11-23 MM900 dimension drawing 2: Electrical RJ-45 ports without securing collar SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 268 Graphics 11.6 MM900 dimension drawings Figure 11-24 MM900 dimension drawing 3: BFOC ports Figure 11-25 MM900 dimension drawing 4: Optical SC ports SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 269 Graphics 11.6 MM900 dimension drawings Figure 11-26 MM900 dimension drawing 5: SFP media module SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 270: Sfp Dimension Drawings

    11.7 SFP dimension drawings 11.7 SFP dimension drawings Note The following dimension drawings are available for the SFP product group. Note All dimensions are ± 0.2 mm unless otherwise specified. Figure 11-27 SFP dimension drawing SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 271: X-300M Poe Dimension Drawings

    Graphics 11.8 X-300M PoE dimension drawings 11.8 X-300M PoE dimension drawings All dimensions in the drawings are in millimeters. Figure 11-28 X308-2M PoE: Front view SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 272 Graphics 11.8 X-300M PoE dimension drawings Figure 11-29 X308-2M PoE: Side view SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 273: Xr-300M Poe Dimension Drawings

    Graphics 11.9 XR-300M PoE dimension drawings Figure 11-30 X308-2M PoE: Drilling template 11.9 XR-300M PoE dimension drawings All dimensions in the drawings are in millimeters. Figure 11-31 XR324-4M PoE: Front view SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 274 Graphics 11.9 XR-300M PoE dimension drawings Figure 11-32 XR324-4M PoE: Side view Figure 11-33 XR324-4M PoE: Rear Figure 11-34 XR324-4M PoE: From above SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 275: Appendix

    TP cords or TP-XP cords with a maximum length of 10 m can be connected to the RJ-45 TP port. With the IE FC cables and IE FC RJ-45 plug, an overall cable length of up to 100 m is permitted between two devices depending on the cable type. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 276: Fitting The Ie Fc Rj-45 Plug

    Assembly of the IE FC RJ-45 Plug on an IE FC Standard Cable For information on assembling an IE FC RJ-45 Plug on a SIMATIC NET Industrial Ethernet FastConnect cable, please refer to the instructions supplied with the IE FC RJ-45 Plug. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 277 If there is not enough space to release the lock with your hand, you can also use a 2.5 mm screwdriver. You can then remove the IE FC RJ-45 Plug from the twisted pair socket. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 278: Electrical Tests (Eec Devices)

    Irradiation with RF field, single frequencies IEC 60255-22-3, IEC 61000-4-3, class III – amplitude modulated – pulse modulated 10 V/m 80/160/450/900 MHz; 80 % AM; 1 kHz Fast transients / burst IEC 60255-22-4 and IEC 61000-4-4 and IEEE C37.90.1 class IV 4 kV SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 279 A Radiated electric field strength IEC-CISPR 22, 30 MHz to 1000 MHz limit value class A Voltage fluctuations and flicker on the power supply cable at 230 VAC IEC 61000-3-3; limit values kept to. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 280 Appendix A.3 Electrical tests (EEC devices) SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 281: Glossary

    To ensure that the CSMA/CD protocol functions correctly, the propagation time of a data packet from one node to another is restricted. This propagation time results in a spatially limited span for the network depending on the data rate known as the collision domain. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 282 The display mode can be switched over using a button on the IE Switch X-300. Enhanced Environmental Conditions The device groups SCALANCE X-300EEC and XR-300M EEC are intended for use in environmental conditions with enhanced requirements. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 283 See also ►media redundancy. High Speed Redundancy → Latency Latency specifies the time taken by frames to pass through an IE Switch X-300. This does not include the time required for buffering frames. Lucent Connector SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 284 See also ►media redundancy. Management Information Base. The MIB is a formal description of network objects in the form of a tree structure that contains all the relevant information for network management in SNMP. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 285 125 µm and 50 or 62.5 µm core diameter. Due to the larger core diameter the pulse edges degrade more than in single mode transmission resulting in shorter transmission distances. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 286 (►redundancy clients) in the ring over a linear bus. Ring port Port of a device that establishes the connection to a neighboring device in a ring topology. A device has two ring ports. Redundancy manager → SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 287 Module slot → Small Form Factor Pluggable (SFP) An SFP is a pluggable, compact transceiver for network connections. With SCALANCE X, an SFP transceiver may be plugged only into the → SFP media module. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 288 Web Based Management. With WBM, configuration and diagnostics are handled with an Internet browser. Entries made by the user are sent to the IE Switch X-300 using the HTTP protocol and the IE Switch X-300 transfers its replies by HTTP to the user. SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 289: Index

    HSR, 39 Transceiver, 122 Low voltage equipment directive, 219 Redundancy Power supply, 126, 133 Redundancy manager, 32, 36 MDI /MDIX autocrossover function, 276 Media redundancy, 36, 38 Media redundancy methods, 36, 39 SFP, 21 SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...
  • Page 290 Index Signaling contact redundant, 63 Transmission mode, 80 Full duplex, 80 Half duplex, 80 Transmission rate, 80 X-300EEC power supply Redundancy, 126 SCALANCE X-300 Operating Instructions, 10/2010, A5E01113043-10...