Application planning
3.2 Restrictions compared to the S7-1500 automation system
Software restrictions
Table 3- 4
Function
Instructions
Display: "Modules" menu command
Firmware update
Hardware detection in STEP 7 (read
out configuration)
HMI tags
I-device
IRT
Configured connections
Motion Control
MRPD
Multiuser Engineering
Online functions
OPC UA
PID controller
Protection functions
Secure OUC
PROFINET send clock
Shared Device
SIMATIC ProDiag
S7 routing
52
Software restrictions
Restriction
Not supported, restrictions for specific instructions: You can
find additional information in the section Restrictions
(Page 150).
Not supported
Firmware update via accessible devices is not supported.
Not supported
The direct entry of tags on the HMI device is only possible in
the RUN-Solo system state.
Cannot be used as I-device
Not supported
Connection type not support for communication connection.
Only programmed connections are supported.
Motion Control functions are not supported in the CPUs
Not supported
Not supported
Download not possible in the RUN-Redundant system
•
state
SIMATIC Automation Tool (SAT tool) not supported
•
OPC UA (server and client) not supported
Compact PID controllers not supported:
PID_Compact
•
PID_3Step
•
PID_Temp
•
Only the PID basic functions are supported. The PID basic
functions can only be commissioned online in the RUN-Solo
system state.
Not supported: Copy protection
Not supported as certificate management is not possible for
the R/H CPUs:
If you have enabled Secure OUC, you can compile and load
the user program but cannot add certificates to the R/H
CPUs.
1 ms only
Not supported
Not supported
No S7 routing between PROFINET interface X1 and
PROFINET interface X2 of the R/H CPUs
System Manual, 10/2018, A5E41814787-AA
1)
S7-1500R/H redundant system