SiXCO
Carbon Monoxide (CO) Detector / Monoxyde de carbone (CO)
Quick Installation Guide
This device is intended for use with Honeywell controls that support SiX series devices
including the SiXCO. Check the control for compatibility with this device. This device
occupies one control panel zone.
See Honeywell Installation Guide (P/N 800-23974–
https://mywebtech.honeywell.com/) and the Limitations of
Carbon Monoxide Alarm Systems Insert (P/N 800-15144
12/15) and Limitation of Carbon Monoxide Detectors (P/N
K14670V1 4/08 Rev. A).
FEATURES
• 10-year life Carbon Monoxide (CO) sensor
• CO Detector End-of-Life reporting (detector needs replacing)
• CO Maintenance Reporting
• Low Battery Detection
• One Go / All Go: all CO detectors in the system programmed
as one-go-all-go will sound on alarm.
POWER UP
•
Remove battery pull tab. Be sure batteries are seated
properly to avoid a low battery condition after 15 seconds.
•
Upon power up, Green LED Blinks every 2 secs / Sounder is
Silent.
ENROLLMENT
IMPORTANT NOTES:
• The Carbon Monoxide (CO) has a
unique MAC ID number (serial
number) and is used for
enrollment.
• Once enrolled, the device cannot
be used with another system
until it is removed from the
current controller. See the 24-
hour Enrollment Deletion section
below or the controller's
instructions.
Enroll the Device Services (CO)
1. Remove the detector from the
base plate (tamper switch must
be faulted when enrolling).
2. Put the control panel in Zone
Programming mode.
For Lyric Controller: Security >
installer code > Program >
(scroll down) > SiX
Programming
3. Pull the battery tab to activate
enrollment process (be sure
batteries are seated properly to
avoid a false low battery
condition). If the battery tab has
already been removed and the
unit is powered up, press the
Test switch for less than 3
seconds to activate the
enrollment process.
4. The device attempts enrollment (green LED flashes about 8 seconds). If successful, the
green LED lights steady for 3 seconds and the detector chirps indicating a successful
enrollment.
If the LED does not light steady, enrollment failed. Retry by pressing Test switch for less
than 3 seconds.Supervision: Detector supervision is factory set for 1 minute and is not
programmable.
5. To assign zone descriptors for each of the zones and/or change device type or zone
response type, select the zone then select Edit and make the desired changes. Press
Save when done.
24-Hour Enrollment Deletion
Use this procedure within 24 hours of initial enrollment to delete this device from the
controller. This allows reenrollment in a specific controller in case enrollment in that
controller failed (i.e., the device inadvertently enrolled in a different controller). This resets
the device to factory default settings and removes the communication link data in the
controller in which it is enrolled, allowing the device to be reenrolled in the desired
controller.
NOTE: Pressing and holding the test button (while powering the detector) will arm the
detector to perform a reset to factory defaults.
TO SILENCE THE DETECTOR
Press the test switch. The detector sounds again after 5 minutes if the alarm condition
continues.
NOTE: The detector can only be silenced once per event.
Guide d'installation rapide
This device is intended for use with Honeywell controls that support SiX series devices
including the SiXCO. Check the control for compatibility with this device. This device
occupies one control panel zone.
Voir les instructions d'installation complètes (800-23974 -
https://mywebtech.honeywell.com/) et les limites de cet
insert de système d'alarme au monoxyde de carbone (800-
15144FC 12/15)
CARACTÉRISTIQUES
Signalement de la fin de vie du détecteur de CO (détecteur
devant être remplacé)
• 10-year life Carbon Monoxide (CO) sensor
• CO Maintenance Reporting
• Détection de pile faible
• Une seule fois pour tout : Tous les détecteurs de fumée du
système programmés comme « Une seule fois pour tout »
retentiront.
POWER UP
•
Remove battery pull tabs. Be sure batteries are seated
properly to avoid a low battery condition after 15 seconds.
•
Upon power up, Green LED Blinks every 2 secs / Sounder is
Silent.
4. The device attempts enrollment (green LED flashes about 8 seconds). If successful, the
green LED lights steady for 3 seconds and the detector chirps indicating a successful
enrollment.
If the LED does not light steady, enrollment failed. Retry by pressing Test switch for less
than 3 seconds.Supervision: Detector supervision is factory set for 1 minute and is not
programmable.
5. To assign zone descriptors for each of the zones and/or change device type or zone
response type, select the zone then select Edit and make the desired changes. Press
Save when done.
24-Hour Enrollment Deletion
Use this procedure within 24 hours of initial enrollment to delete this device from the
controller. This allows reenrollment in a specific controller in case enrollment in that
controller failed (i.e., the device inadvertently enrolled in a different controller). This resets
the device to factory default settings and removes the communication link data in the
controller in which it is enrolled, allowing the device to be reenrolled in the desired
controller.
NOTE:
Pressing and holding test button (while powering the detector) will arm the
detector to perform a reset to factory defaults.
POUR FAIRE TAIRE LE DÉTECTEUR
Appuyez sur le bouton de test. Le détecteur sonne de nouveau après 5 minutes si la
condition d'alarme est toujours présente.
NOTE: The detector can only be silenced once per event.
ENRÔLEMENT
IMPORTANT NOTES:
• The Carbon Monoxide (CO) has a
unique MAC ID number (serial
number) and is used for
enrollment.
• Once enrolled, the device cannot
be used with another system until
it is removed from the current
controller. See the 24-hour
Enrollment Deletion section below
or the controller's instructions.
Enroll the Device Services (CO)
1. Remove the detector from the
base plate (tamper switch must
be faulted when enrolling).
2. Put the control panel in Zone
Programming mode.
For Lyric Controller: Security >
installer code > Program >
(scroll down) > SiX
Programming
3. Pull the battery tab to activate
enrollment process (be sure
batteries are seated properly to
avoid a false low battery
condition). If the battery tab has
already been removed and the
unit is powered up, press Test
switch for less than 3 seconds to
activate the enrollment process.