hit counter script
Siemens RUGGEDCOM RS910L Installation Manual
Siemens RUGGEDCOM RS910L Installation Manual

Siemens RUGGEDCOM RS910L Installation Manual

Hide thumbs Also See for RUGGEDCOM RS910L:

Advertisement

Quick Links

RUGGEDCOM RS910L
Installation Guide
08/2017
RC1030-EN-03
Preface
Introduction
Installing the Device
Communication Ports
Technical Specifications
Dimension Drawings
Certification
1
2
3
4
5
6

Advertisement

Table of Contents
loading

Summary of Contents for Siemens RUGGEDCOM RS910L

  • Page 1 Preface Introduction Installing the Device RUGGEDCOM RS910L Communication Ports Technical Specifications Dimension Drawings Installation Guide Certification 08/2017 RC1030-EN-03...
  • Page 2: Security Information

    Warranty Siemens warrants this product for a period of five (5) years from the date of purchase, conditional upon the return to factory for maintenance during the warranty term. This product contains no user-serviceable parts. Attempted service by unauthorized personnel shall render all warranties null and void.
  • Page 3 RUGGEDCOM RS910L Installation Guide Contacting Siemens Address Telephone E-mail Siemens Canada Ltd Toll-free: 1 888 264 0006 ruggedcom.info.i-ia@siemens.com Industry Sector Tel: +1 905 856 5288 300 Applewood Crescent Fax: +1 905 856 1995 Concord, Ontario www.siemens.com/ruggedcom Canada, L4K 5C7...
  • Page 4 RUGGEDCOM RS910L Installation Guide...
  • Page 5 RUGGEDCOM RS910L   Installation Guide Table of Contents Table of Contents Preface ......................Alerts ..............................vii Related Documents ..........................viii Accessing Documentation ........................viii Training ............................viii Customer Support ..........................viii Chapter 1 Introduction ..................... 1.1  Feature Highlights ........................1 1.2    Description ........................... 2 Chapter 2 Installing the Device ..................
  • Page 6   RUGGEDCOM RS910L Table of Contents Installation Guide 3.3.3  EoVDSL Performance ......................22 Chapter 4 Technical Specifications .................. 4.1  Power Supply Specifications ......................25 4.2  Failsafe Relay Specifications ......................26 4.3  Copper Ethernet Port Specifications ....................26 4.4  Fiber Optic Ethernet Port Specifications ..................27 4.5  Serial Port Specifications ......................
  • Page 7 Installation Guide Preface Preface This guide describes the RUGGEDCOM RS910L. It describes the major features of the device, installation, commissioning and important technical specifications. It is intended for use by network technical support personnel who are responsible for the installation, commissioning and maintenance of the device.
  • Page 8: Related Documents

    Siemens Sales representative. Customer Support Customer support is available 24 hours, 7 days a week for all Siemens customers. For technical support or general information, contact Siemens Customer Support through any of the following methods: Online Visit http://www.siemens.com/automation/support-request...
  • Page 9 RUGGEDCOM RS910L   Installation Guide Preface • Ask questions or share knowledge with fellow Siemens customers and the support community Customer Support...
  • Page 10   RUGGEDCOM RS910L Preface Installation Guide Customer Support...
  • Page 11: Introduction

    2), optional conformal coating and a galvanized steel enclosure allows the RUGGEDCOM RS910L to be placed in almost any location. The RUGGEDCOM RS910L can be mounted on a DIN rail or panel for efficient use of cabinet space. The integrated power supply supports a wide range of voltages (88-300 VDC or 85-264 VAC) for worldwide operability, as well as dual-redundant, reversible polarity, 24 VDC and 48 VDC power supply inputs for high availability applications requiring dual or backup power inputs.
  • Page 12: Description

    • Terminal blocks for reliable maintenance free connections • CSA/UL 60950-1 safety approved to 85 °C (185 °F) Section 1.2 Description The RUGGEDCOM RS910L features various ports, controls and indicator LEDs on the front panel for connecting, configuring and troubleshooting the device. Description...
  • Page 13: Communication Ports

    Section 2.8, “Connecting to the Device”. Communication Ports Receive and transmit data, as well as provide access to the RUGGEDCOM ROS Web interface. For more information about the various ports available for the RUGGEDCOM RS910L, refer to Chapter 3, Communication Ports. Failsafe Alarm Relay Latches to default state when a power disruption or other alarm condition occurs.
  • Page 14 Chapter 1 RUGGEDCOM RS910L Introduction Installation Guide Description...
  • Page 15: Installing The Device

    This product contains no user-serviceable parts. Attempted service by unauthorized personnel shall render all warranties null and void. Changes or modifications not expressly approved by Siemens Canada Ltd could invalidate specifications, test results, and agency approvals, and void the user's authority to operate the equipment.
  • Page 16: Certification

    Section 2.4 Installing the Device in Hazardous Locations The RUGGEDCOM RS910L is designed to comply with the safety standards for Class I, Division 2 hazardous locations where concentrations of flammable gases, vapors or liquids may be present, as opposed to normal operating environments.
  • Page 17: Mounting The Device

    Section 2.5 Mounting the Device The RUGGEDCOM RS910L is designed for maximum mounting and display flexibility. It can be equipped with adapters that allow it to be installed on a 35 mm (1.4 in) DIN rail or affixed to a panel.
  • Page 18: Mounting The Device On A Din Rail

    Chapter 2 RUGGEDCOM RS910L Installing the Device Installation Guide NOTE For detailed dimensions of the device with either DIN rail or panel hardware installed, refer to Chapter 5, Dimension Drawings. CONTENTS • Section 2.5.1, “Mounting the Device on a DIN Rail” •...
  • Page 19: Mounting The Device To A Panel

    Section 2.5.2 Mounting the Device to a Panel For panel installations, the RUGGEDCOM RS910L can be equipped with panel adapters on the top and bottom of the chassis. The adapters allow the device to be attached to a panel using screws.
  • Page 20: Connecting Power

    1. Normally Closed    2. Common    3. Normally Open Section 2.7 Connecting Power The RUGGEDCOM RS910L supports power input from a single high AC/DC or low DC power supply. IMPORTANT! • For 110/230 VAC rated equipment, an appropriately rated AC circuit breaker must be installed.
  • Page 21 RUGGEDCOM RS910L Chapter 2 Installation Guide Installing the Device CAUTION! Electrical hazard – risk of damage to equipment. Before testing the dielectric strength (HIPOT) in the field, remove the braided ground cable connected to the surge ground terminal and chassis ground.
  • Page 22: Connecting Low Dc Power

    Section 2.7.2 Connecting Low DC Power RUGGEDCOM RS910L's equipped with 24 or 48 V power supply inputs feature reverse polarity protection and dual power supply inputs allowing the device to accept redundant connections to a single DC power supply. To connect a low DC power supply to the device, do the following: NOTE Torque all terminal connections to 0.6 N·m (5 lbf-in).
  • Page 23: Connecting To The Device

    Connecting to the Device The following describes the various methods for accessing the RUGGEDCOM ROS console and Web interfaces on the device. For more detailed instructions, refer to the RUGGEDCOM ROS User Guide for the RUGGEDCOM RS910L. IMPORTANT! Ethernet cables should be only be connected/disconnected in a non-hazardous area, or when the device is not energized.
  • Page 24 Chapter 2 RUGGEDCOM RS910L Installing the Device Installation Guide IMPORTANT! The serial console port is intended to be used only as a temporary connection during initial configuration or troubleshooting, and should only be used in a safe area (as defined by IEC 60079-0, Edition 6.0).
  • Page 25: Configuring The Device

    RUGGEDCOM RS910L Chapter 2 Installation Guide Installing the Device Section 2.9 Configuring the Device Once the device is installed and connected to the network, it must be configured. All configuration management is done via the RUGGEDCOM ROS interface. For more information about configuring the device, refer to the RUGGEDCOM ROS User Guide associated with the installed software release.
  • Page 26 Chapter 2 RUGGEDCOM RS910L Installing the Device Installation Guide Configuring the Device...
  • Page 27: Communication Ports

    RUGGEDCOM RS910L Chapter 3 Installation Guide Communication Ports Communication Ports The RUGGEDCOM RS910L can be equipped with various types of communication ports to enhance its abilities and performance. Figure 9: Port Assignment 1. Ports 1 and 2    2. Ports 3 and 4    3. Port 9 Port...
  • Page 28: Copper Ethernet Ports

    Section 3.1 Copper Ethernet Ports The RUGGEDCOM RS910L supports multiple 10/100Base-TX Ethernet ports that allow connection to standard Category 5 (CAT-5) unshielded twisted-pair (UTP) cables with RJ45 male connectors. The RJ45 receptacles are directly connected to the chassis ground on the device and can accept CAT-5 shielded twisted-pair (STP) cables.
  • Page 29: Fiber Optic Ethernet Ports

    RUGGEDCOM RS910L Chapter 3 Installation Guide Communication Ports Section 3.2 Fiber Optic Ethernet Ports Fiber optic Ethernet ports are available with either MTRJ (Mechanical Transfer Registered Jack), LC (Lucent Connector), SC (Standard or Subscriber Connector) or ST (Straight Tip) connectors. Make sure the Transmit (Tx) and Receive (Rx) connections of each port are properly connected and matched to establish a proper link.
  • Page 30 Master and pushed to the Slave. Data flowing from the Master to the Slave is designated downstream, while data flowing from the Slave to the Master is designated upstream. Siemens supports two types of EoVDSL: • Universal EoVDSL Universal EoVDSL ports are Master/Slave selectable and offer symmetric data rates (upstream and downstream) up to 35 Mbps.
  • Page 31: Eovdsl Wiring

    Section 3.3.2 Configuration and Setup If the RUGGEDCOM RS910L and another device both have Universal EoVDSL ports, configure one device to be the Master and the other the Slave. If both devices have a Long-Reach EoVDSL port, no Master/Slave configuration is necessary, since the ports will already be fixed as Master or Slave.
  • Page 32: Eovdsl Performance

    Once configured and connected together, each device will attempt to achieve the maximum speed based on the line length and conditions. The RUGGEDCOM RS910L's Link/Act LED may flash on and off several times before setting on a final link speed and declaring the port up.
  • Page 33 RUGGEDCOM RS910L Chapter 3 Installation Guide Communication Ports Distance Downstream/Upstream (Mbps) 0.9 km (2953 ft) 1.0 km (3280 ft) 1.3 km (4265 ft) 1.7 km (5577 ft) 2.0 km (6562 ft) 2.5 km (8202 ft) Long-Reach EoVDSL Performance Characteristics On No. 24 AWG Polyethylene Insulated Cable (PIC) twisted-pair wiring, the following performance is typical with...
  • Page 34 Chapter 3 RUGGEDCOM RS910L Communication Ports Installation Guide EoVDSL Performance...
  • Page 35: Technical Specifications

    RUGGEDCOM RS910L Chapter 4 Installation Guide Technical Specifications Technical Specifications This section provides important technical specifications related to the device. CONTENTS • Section 4.1, “Power Supply Specifications” • Section 4.2, “Failsafe Relay Specifications” • Section 4.3, “Copper Ethernet Port Specifications” • Section 4.4, “Fiber Optic Ethernet Port Specifications”...
  • Page 36: Failsafe Relay Specifications

    Chapter 4 RUGGEDCOM RS910L Technical Specifications Installation Guide Input Range Internal Maximum Power Power Supply Type Isolation Fuse Rating Consumption Minimum Maximum 37 VDC 72 VDC 3.15 A(T) 1.5 kVDC 10 W (T) denotes time-delay fuse. Power consumption varies based on configuration.
  • Page 37: Fiber Optic Ethernet Port Specifications

    Section 4.4 Fiber Optic Ethernet Port Specifications The following details the specifications for fiber Ethernet ports that can be ordered with the RUGGEDCOM RS910L. NOTE • All optical power numbers are listed as dBm averages. To convert from average to peak add 3 dBm.
  • Page 38: Serial Port Specifications

    1300 50/125 1300 -22.5 Typical. Section 4.5 Serial Port Specifications The following details the specifications for serial ports that can be ordered with the RUGGEDCOM RS910L. Copper Serial Ports Baud Rate 300 to 230 kbps Connector DB9 or RJ45 Isolation 2.5 kV...
  • Page 39: Mechanical Specifications

    RUGGEDCOM RS910L Chapter 4 Installation Guide Technical Specifications Section 4.7 Mechanical Specifications Dimensions Refer to Chapter 5, Dimension Drawings Weight 1.2 kg (2.7 lbs) Ingress Protection IP40 (1 mm or 0.04 in objects) Enclosure 20 AWG Galvanized Steel Mechanical Specifications...
  • Page 40 Chapter 4 RUGGEDCOM RS910L Technical Specifications Installation Guide Mechanical Specifications...
  • Page 41: Dimension Drawings

    RUGGEDCOM RS910L Chapter 5 Installation Guide Dimension Drawings Dimension Drawings NOTE All dimensions are in millimeters, unless otherwise stated. 65.3 116.59 7.87 Figure 17: Overall Dimensions...
  • Page 42 Chapter 5 RUGGEDCOM RS910L Dimension Drawings Installation Guide 128.4 13.64 101.6 11.2 78.74 120.65 Figure 18: Panel and DIN Rail Mount Dimensions...
  • Page 43: Certification

    RUGGEDCOM RS910L Chapter 6 Installation Guide Certification Certification The RUGGEDCOM RS910L device has been thoroughly tested to guarantee its conformance with recognized standards and has received approval from recognized regulatory agencies. CONTENTS • Section 6.1, “Approvals” • Section 6.2, “EMC and Environmental Type Tests”...
  • Page 44: Fda/Cdrh

    • Title 21 Code of Federal Regulations (CFR) – Chapter I – Sub-chapter J – Radiological Health Section 6.1.4 ISED This device is declared by Siemens Canada Ltd to meet the requirements of the following ISED (Innovation Science and Economic Development Canada) standard: • CAN ICES-3 (A)/NMB-3 (A) Section 6.1.5...
  • Page 45: Other Approvals

    • IEC 61000-6-2 Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity for Industrial Environments Section 6.2 EMC and Environmental Type Tests The RUGGEDCOM RS910L has passed the following Electromagnetic Compatibility (EMC) and environmental tests. EMC Type Tests Test Description...
  • Page 46 EMC Immunity Type Tests per IEEE 1613 NOTE The RUGGEDCOM RS910L meets Class 2 requirements for an all-fiber configuration and Class 1 requirements for copper ports. Class 1 allows for temporary communication loss, while Class 2 requires error-free and interrupted communications.
  • Page 47: Environmental Type Tests

    RUGGEDCOM RS910L Chapter 6 Installation Guide Certification Description Test Levels Oscillatory Signal Ports 2.5 kV Common Mode @ 1 MHz DC Power Ports 2.5 kV Common and Differential Mode @ 1 MHz AC Power Ports 2.5 kV Common and Differential Mode @ 1 MHz...
  • Page 48 Chapter 6 RUGGEDCOM RS910L Certification Installation Guide EMC and Environmental Type Tests...

Table of Contents