Flush-mount commercial electronic air cleaner
Hide thumbs Also See for F57A:
Table of Contents

Advertisement

1
1
SUSPENDED
CEILING
1
BE SURE TO TWIST THE SUPPORT WIRE A MIINIMUM OF FOUR TIMES TO PROPERLY BEAR WEIGHT.
THERE MUST BE 14 IN. (356 MM) BETWEEN SUSPENDED CEILING AND TRUE CEILING.
2
Reinforce the suspended ceiling T-bars with the wire,
placing the wires to evenly distribute the F57 weight.
Securely attach wires to both the suspended ceiling and
the true ceiling, and to the T-bars. Twist the wire at least
four times.
Place F57 into cleared area with grille side facing the
floor. Lift F57 into space until grille side is above
suspended ceiling level. Reach in and attach the rubber
mounting spacers to the T-bars at the mounting shoulder
locations.
Attach four support shoulders to the F57. Bend the tab on
F57A,B FLUSH-MOUNTED COMMERCIAL ELECTRONIC AIR CLEANER
TRUE CEILING
1
2
F57B
1
SUSPENDED
CEILING
SUPPORT
SHOULDER
POSITIONS
VINYL FLANGE
Fig. 6. Typical F57B mounting procedures.
T-BAR/DROP CEILING SUPPORT SYSTEM
24 IN.
(610 MM)
PLACE WIRE SUPPORTS AS CLOSE AS POSSIBLE
TO F57B SUPPORT SHOULDER POSITIONS,
APPROXIMATELY 1 IN. (25 MM) FROM ENDS.
F57B
the mounting shoulders to secure them to the F57.
Attach vinyl flanges to the bottom of the F57 frame to
cover any space that appears between the F57 and the
suspended ceiling.
Settle the F57 on the mounting spacers on the reinforced
T-bars.
Locate the holes just above the four vinyl flanges. Drill
1/4-in. (6.4 mm) holes through the T-bars at these
locations. Slip a panhead bolt through each hole, and
fasten with a self-locking nut.
9
24 IN.
(610 MM)
IF NEEDED, REMOVE T-BAR
TO CREATE 24 X 24 IN.
(610 X 610 MM) SPACE.
BEND TABS TO
HOLD MOUNT
ON AIR CLEANER
SUPPORT
SHOULDER
(1 OF 4)
MOUNTING
SPACER (1 OF 4)
REINFORCED
T-BAR
M5675
68-0083-7 Revised 11-07