Desigo Fire Safety Compact / Cerberus PRO Compact Enclosure ....... 17 6.2.2 GCNET (VNT) Enclosure ..................... 17 6.2.3 Network Enclosure ...................... 17 PROGRAMMING THE SCALANCE XC206-2SFP-MM MULTIMODE AND XC206-2SFP-SM SINGLE MODE ETHERNET FIBER SWITCH ................18 Fiber Switch Introduction....................18 Primary Setup Tool ......................19 7.2.1 Installation ........................
Page 3
Adding An XLS, Desigo Modular, or Cerberus Pro Modular .......... 42 Fiber Optic Switch Setup....................43 9.3.1 Add A Switch ....................... 43 9.3.2 Delete A Switch ......................44 9.3.3 Update a Switch ......................45 CYBER SECURITY DISCLAIMER ................46 Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
Page 4
Table of Figures and Tables Figure 1–1: Scalance XC206-2SFP-MM Multimode and XC206-2SFP-SM Single Mode Ethernet Fiber Switch……………………………………………………………………………………………………………5 Figure 2–1: SFP Adapater ......................... 7 Figure 3–1: Installation on the VNT-MP in a CAB-2 / CAB-3 Enclosure for non-VNT Applications ... 10 Figure 4–1: Class B Switch Fiber Connection ..................
Figure 1–1: Scalance XC206-2SFP-MM Multimode and XC206-2SFP-SM Single Mode Ethernet Fiber Switch The Model Scalance XC206-2SFP-MM Multimode and XC206-2SFP-SM Single Mode Ethernet Fiber Switch (as shown in Table 1-1) from Siemens Industry, Inc. is used to maintain a Class X ring or Class B wiring for communications between the following: 1.
Page 6
In Class X, the fiber switch that is connected to the primary Management Station is designated as the ring master. There is no difference in installation, configuration, and operation of single mode or multimode fiber optic switches except the type of fiber used. Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
To install the SFP transceiver, ensure that power is disconnected from the switch. For required specification for the fiber, refer to the section Fiber Connections. For details on installation, refer to the Siemens SIMATIC NET/Industrial Ethernet/PROFINET/ Primary Setup Tool/Configuration Manual, P/N C79000-G8976-C204-07.
NOTE: If a C-Plug with an existing configuration is inserted into a different switch, the configuration on the C-Plug will overwrite the existing switch configuration. For details on installation, refer to the Siemens SIMATIC NET/Industrial Ethernet switches SCALANCE XC-200/Operating Instructions, P/N C79000-G8976-C442-11.
INSTALLATION WARNING: Remove all system power before installation, first battery then AC. (To power up, connect the AC first, then the battery. Depending on the application, the Scalance XC206-2SFP-MM or XC206-2SFP-SM can be mounted in the following methods: For Desigo CC/Cerberus DMS applications, and for legacy NCC applications, in the Network Enclosure, Model NTWRK-ENCL.
XC206-2SFP-MM/-SM on the Network Enclosure. 3.3.2 Mounting on the VNT-MP in a CAB-2 / CAB-3 Enclosure The VNT-MP can be used to mount the Scalance XC206-2SFP-MM/-SM fiber switch in CAB- 2 and CAB-3 Enclosures in three different configurations: ...
Desigo CC/Cerberus DMS, legacy NCC, Desigo Fire Safety Compact/Cerberus PRO Compact, and/or Desigo Fire Safety Modular/Cerberus PRO Modular GCNET must be within 20 feet in closed conduit within the same room. Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
Scalance XC-200 Operating Instructions, P/N C79000-G8976-C442-11, for additional information on fiber optic switches. Overview of Class B and Class X Fiber Connection Figure 4–1: Class B Switch Fiber Connection Figure 4–2: Class X Switch Fiber Connection Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
Class B Wiring Applications Figure 4-3 illustrates a conceptual Class B fiber network with Scalance XC206-2SFP-MM/-SM switches in the following representative configurations: In a GCNET Building Enclosure In a Network Enclosure with a colocated Desigo Fire Safety Compact/Cerberus PRO Compact.
Class X Wiring Applications Figure 4-4 illustrates a conceptual Class X fiber network with Scalance XC206-2SFP-MM/-SM switches in the following representative configurations: In a Desigo Fire Safety Modular/Cerberus PRO Modular GCNET FCC Enclosure with a colocated Desigo CC Client ...
Management Only from Ethernet RS485 Station Management Station Desigo CC / Cerberus DMS Scalance MOSA XC206-2SFP Server / Distributed Server / -MM/-SM Figure 4–6: Representative Class B Monitoring-Only Example – Control on Other Panels Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
All connections are supervised and power limited unless stated otherwise. For power, the fiber switch may be connected to a: PSC-12, P/N 315-033060 PAD-4, P/N 315-050217 PAD-5, Document ID A6V101030358 NOTE: Input Voltage: Regulated 24VDC Input Current: 265mA @ 24VDC Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
If the X204-2 or X204-2LD is installed in a Desigo Fire Safety Modular/Cerberus PRO Modular VNT Enclosure, it may be directly replaced with the XC206-2SPF-MM or XC206-2SPF-SM. Otherwise, the XC206-2SPF-MM or XC206-2SPF-SM must be installed in the Network Enclosure, Document ID A6V12412370. Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
MULTIMODE AND XC206-2SFP-SM SINGLE MODE ETHERNET FIBER SWITCH This section describes how to assign an IP address to the Scalance XC206-2SFP-MM Multimode or XC206-2SFP-SM Single Mode Ethernet Fiber Switch and the methods used for determining IP addresses to assign to the switches. It also describes how to configure one of the switches as the Redundancy Manager.
IP address, then the Primary Setup tool is not needed. 7.2.1 Installation For the installation instructions, refer to the Siemens SIMATIC NET/Industrial Ethernet/PROFINET/Primary Setup Tool/Configuration Manual, P/N C79000-G8976-C204-07, which is provided with the Scalance switch. 7.2.2...
Page 20
Select the Assign IP Parameters option button and enter the IP address for the device • in the IP address box. In the Subnet mask box, enter 255.255.255.0 as the Subnet mask. • Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
Page 21
Select the device you want to configure in the left half of the program window. Click Download. The IP Address is downloaded to the fiber switch. Figure 7–5: Download IP Address Configuration to Switch Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
The High password policy (default) requires at least eight characters including at least one digit, one uppercase letter, and one special character for a new password. Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
Page 23
After successful login and changing the password, the image Scalance XC206-2SFP is shown with its status and prompt to select one item of the menu on the left: Information, System, Layer 2, Layer 3, Security. Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
Page 24
Figure 7–8: XC206-2SFP Start Page For the detailed explanation of each WEB interface item, open Help by clicking the ? mark in the top right corner. You can save the favorite pages by clicking the Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
After the next restart, the downloaded firmware is activated and used. Bootloader shows the version of the boot software stored on the device. Firmware_Running shows the firmware version currently being used on the device. Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
Down is changed to an inactive state, or the port monitored for Up is changed to an active state. In the Redundancy tab, the checkbox can be enabled to signal the error if the redundancy of the connection is lost. Click Set Values. Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
For the complete list of the events and configuration, refer to the Online Help ~ events_help_en.htm. If Fault is enabled, when a device detects an error, the top left LED labeled F lights up. Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
Page 28
Navigate to Menu > System > Events > Severity Filters tab to specify the severity of events to be logged as Info, Warning, or Critical. Figure 7–14: Switch Event Severity Filters Refer to Online Help ~ events_help_en.htm ~ evt_severity_help_en.htm for more information. Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
2. In the Traps tab, specify the Trap Receiver Address = IP address of the Management Station to which this switch will send traps. 3. Click Create. 4. Enable the Trap checkbox and click Set Values to load this configuration to the switch. Refer to Online Help for more information snmp_general_help_en.htm. Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
1. Write Current configuration to the PLUG, if the status of the PLUG is NOT ACCEPTED or FACTORY. 2. Erase PLUG to factory default. Figure 7–17: C-PLUG Management For more details, see the online Help. Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
Ports 7 and 8, for the corresponding model of the Transceiver SFP991-1LD for Single mode or SFP991-1 for Multi-mode fiber, its revision, Serial Number, and other actual value readings. For more details, see the online Help. Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
On this page, the functionality of the black button on the Scalance XC206-2SFP switch can be enabled (default) or disabled for the button pressing: Restore Factory Defaults Set Fault Mask Figure 7–19: SELECT / SET Button Configuration Refer to Online Help for more information. Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
Select Redundancy Type = Ring. Select Redundancy Mode = HRP Manager only on one switch in the network. Select HRP Client (or Automatic Redundancy Detection) on all the other of the switches on the network. Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
Page 34
HRP rings, where two neighboring switches within the same ring are configured as standby master and standby slave and are connected via parallel cables to two switches in another ring. Figure 7–21: Ring Redundancy Configuration For details, see the Online Help redundancy_standby_help_en.htm. Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
PC. You can make the entries required for this on Menu > System > Load & Save in the HTTP tab. The table describes the possible entries in the System Load & Save via the HTTP feature. Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
The LEDs status on the top left of the screen are the exact same as that shown on the fiber switches. Red LEDs indicate an error. Green LEDs indicate that the switch is running properly. Green LEDs also indicates ports that have an Ethernet connection to them. Figure 7–22: Fiber Switch Diagnostic Indicators Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
To configure SNMP on Desigo CC/Cerberus DMS for monitoring to the Scalance switch, refer to SNMP Configuration Guidelines for Scalance Switches. Once SNMP has been configured, to configure ring, fault, or sabotage event monitoring, refer to Industrial Ethernet Switches Scalance XC-200, P/N C79000-G8976-C442-11. Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
IP address in the range 192.168.1.60 - 192.168.1.63 with the subnet mask of 255.255.255.0. Figure 9–1: IP Address Setup Configure Windows XP, Windows 7, or Windows 10 on NCC machine with Firewall set to • OFF. Set up the SNMP protocol as follows: • Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
NCC System Settings. At the Multiple NCC Configuration Options, make sure that the following are checked: Control Vectoring • TCP/IP used for NCC link • Inhibit automatic data base exchange Click Done when finished. • Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
Page 40
NCCs in an entire complex that are communicating with the NCC. To add a new NCC, MXL, XLS, Desigo Fire Safety Modular, or Cerberus PRO Modular • node into the NCC, click Add. Figure 9–5: NCC Network Node Map Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
Choose the Type of NCC-G Node as either This Unit or Remote Unit. • Type the TCP/IP Network Address as the IP address of the NCC PC. • Click Save. • Figure 9–6: Adding An NCC Node Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
• Choose XLS as the Node Type. • Choose the Node numbers of the NCC as the Default NCC-G Control Setting. • Click Save. • Figure 9–7: Adding An XLS/Desigo Modular/Cerberus Pro Modular Node Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
4. For the Ring Redundant Manager, select either Master or Client to agree with the setting, Ring Redundancy Manager. 5. Click Add to complete the changes or click Cancel to leave the settings as they were. Figure 9–9: Adding A Fiber Optic Switch Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
3. A message box displays as shown in Figure 9-10 to confirm the deletion. 4. Click OK to delete the selected switch or click Cancel to leave the settings as they were. Figure 9–10: Deleting A Fiber Optic Switch Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
4. You can update the IP address and/or the Ring Redundant Manager setting. 5. Click Update to complete the changes or click Cancel to leave the settings as they were. Figure 9–11: Updating A Fiber Optic Switch Siemens Industry, Inc. A6V12198161_en--_a Smart Infrastructure...
CYBERSECURITY DISCLAIMER Siemens provides a portfolio of products, solutions, systems and services that includes security functions that support the secure operation of plants, systems, machines and networks. In the field of Building Technologies, this includes building automation and control, fire safety, security management as well as physical security systems.