hit counter script
Honeywell Unitary Installation Instructions Manual
Honeywell Unitary Installation Instructions Manual

Honeywell Unitary Installation Instructions Manual

Controller-230 vac
Table of Contents

Advertisement

Quick Links

Unitary
CONTROLLER-230 VAC
General ............................................................................... 3
Trademark Information ..................................................... 3
Product Description............................................................ 3
Controller Part Numbers .................................................. 4
Dimensions ............................................................................ 4
Unitary Controller Large........................................................ 4
Unitary Controller Small........................................................ 5
Network Security ............................................................. 5
General Safety Instructions.......................................... 5
Specifications ................................................................... 6
Electrical ................................................................................. 6
Operational Environment................................................. 6
Hardware................................................................................. 6
Communications ................................................................. 6
T1L Communication........................................................... 7
Supported Devices* ............................................................ 7
Weight and Dimensions.................................................... 7
Universal IO*.......................................................................... 7
Wire Gauge Range............................................................... 8
Chopper Output (CHP) ...................................................... 8
Relays ....................................................................................... 8
Hardware overview.......................................................... 9
System Overview............................................................... 10
Service Button.................................................................... 11
Mounting ........................................................................ 11
Before Installation............................................................ 11
DIN Rail Mounting ........................................................... 11
Wall Mounting ................................................................... 12
Power Supply................................................................. 13
General Information ........................................................ 13
Chopper Wiring.................................................................. 13
Chopper Wiring Example............................................... 14
Grounding............................................................................ 14
Input / Output Wiring ................................................. 15
Wiring Requirements ...................................................... 15
Internal Wiring Example ................................................ 16
Terminal Connections..................................................... 18
UIO Wiring Examples ...................................................... 20
DO CHP Wiring Example ............................................... 21
Auxiliary Wiring Examples ........................................... 22
DO Relay Wiring Examples ........................................... 22
Network Concepts ........................................................ 23
The RS-485 Standard ..................................................... 23
TIA/EIA 485 Cable Specifications ................................. 23
IP Network Topologies .................................................... 23
Daisy Chain Topology ..................................................... 23
Ring Topology..................................................................... 23
® U.S. Registered Trademark
Copyright © 2024 Honeywell Inc. • All Rights Reserved
INSTALLATION INSTRUCTIONS
BACnet™ IP Controller................................................. 24
Connecting to an IP network ........................................ 24
DHCP IP Configuration................................................... 24
Link-local addressing...................................................... 24
BACnet™ MS/TP Wiring.............................................. 25
Auto Baud rate functionality......................................... 25
Termination Resistors ..................................................... 25
Shield Termination ........................................................... 25
BACnet™ MS/TP Wiring Example............................... 26
Example........................................................................................... 26
BACnet™ MS/TP Controller ....................................... 27
BACnet™ MS/TP Limitations ....................................... 27
Physical Limitation............................................................... 27
AutoMAC limitation .............................................................. 27
Automatic MAC Addressing .......................................... 27
Setting the MS/TP MAC Address................................ 27
Setting the Device Instance Number ............................ 28
T1L Communication and standard .......................... 29
Daisy Chain Topology...................................................... 29
Ring Topology..................................................................... 29
Modbus RTU................................................................... 30
Wiring Topology ................................................................. 30
Cables and Shielding....................................................... 30
Modbus RS-485 Repeaters........................................... 30
Modbus Client Specifications...................................... 30
Modbus Compliance........................................................ 30
Modbus Considerations ................................................. 31
Sylk™ ................................................................................ 32
Supported Sylk™ devices................................................ 32
Sylk™ Wiring Example ..................................................... 33
Troubleshooting............................................................ 34
LED Interface...................................................................... 35
Controller LED Status ..................................................... 35
Bluetooth LED Status...................................................... 36
BACnet™ MS/TP LED Status........................................ 36
Modbus LED Status......................................................... 36
T1L LED Status.................................................................. 37
Service Pin LED Status ................................................... 37
Regulatory Information .............................................. 38
FCC Regulation.................................................................. 38
ISED non-interference disclaimer ............................. 38
Professional Installation Warning.................................. 38
Wireless Connectivity .......................................................... 38
Standards and Compliance ......................................... 39
Approvals and Certifications ........................................ 39
Electronic Equipment directive................................... 39
31-00610-01

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell Unitary

  • Page 1: Table Of Contents

    IP Network Topologies ............ 23 Approvals and Certifications ........39 Daisy Chain Topology ............. 23 WEEE Directive 2012/19/EC Waste Electrical and Ring Topology..............23 Electronic Equipment directive........39 31-00610-01 ® U.S. Registered Trademark Copyright © 2024 Honeywell Inc. • All Rights Reserved...
  • Page 2 HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Article 33 Communication ..........39 NI1000 TK5000 DIN B............52 PT100 Characteristics............53 Appendix ................. 40 PT1000 Characteristics ............. 54 Sensor Input Accuracy ........... 40 PT3000 Characteristics ............. 60 Recognition of Sensor Failure of Sensor Inputs .. 41 Actuators Wiring Examples........
  • Page 3: General

    Table 2 Accessories/Replacement Parts Part Number Description CW-Cov-L-Unitary Terminal cover for the L-version of the unitary controller (sold in pack of 10) CW-Cov-S-Unitary Terminal cover for the S-version of the unitary controller (sold in pack of 10) 10BASE-T1L-ADAPT IP-T1L single pair media adapter that allows converting 10BASE-T traffic to 10BASE-T1L...
  • Page 4: Controller Part Numbers

    Table 2 Accessories/Replacement Parts Part Number Description SCRW-TB-UNI-L Set of removable terminal blocks covering all models of Unitary controllers IO-JUMPER-4-10 4-pin relay output Jumper Bar to connect 4 relays IN terminals (sold in pack of 10) Controller Part Numbers UN- R...
  • Page 5: Unitary Controller Small

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Unitary Controller Small 0.38 inches (9.6 mm) 11 12 13 14 15 18 19 21 22 23 4.55 inches 18 19 21 22 23 11 12 13 14 15 NC1NO1 IN1 NC2 NO2 IN2 NC3 NO3 IN3 NC4 NO4 IN4 (115.6 mm)
  • Page 6: Specifications

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS SPECIFICATIONS Table 4 Operational Environment Protection IP20, NEMA 1 Electrical Pollution degree Table 3 Electrical Specification Additional tests Ball Pressure and Glow wire test Parameter Specification conducted Rated input voltage 230 VAC ± 10 %...
  • Page 7: T1L Communication

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS T1L Communication Weight and Dimensions Table 7 T1L Specifications Table 9 Weight And Dimensions Parameter Specification Parameter Specification 10BASE-T1L 802.3cg-2019 Standard Large - 8.5 x 4.79 x 2.1 inches (216 x...
  • Page 8: Wire Gauge Range

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Wire Gauge Range Table 14 Fuse for Relays Current Voltage Holder Fuse Part Input Rate Rate Part Table 11 Wire Gauge Range Number Number Parameter Specification 021812.5 12.5 01500520H 26-18 AWG...
  • Page 9: Hardware Overview

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS HARDWARE OVERVIEW 230 VAC DO Chopper Universal BACnet IP Model Power Supply Relays (4x) Output (4x) Inputs/Outputs (4x) Relay Output Jumper RJ45 Ethernet 1 RJ45 Ethernet 2 Service button BACnet MS/TP Model...
  • Page 10: System Overview

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS System Overview Legend BACnet BACnet MS/TP Sylk™ Bus Niagara 4 Supervisor Modbus RTU DALI Ethernet Switch BACnet Plant Controller T1L Switch BACnet MS/TP BACnet BACnet MS/TP BACnet Sylk Unitary controller Unitary controller...
  • Page 11: Service Button

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Service Button IMPORTANT: Fig. 4 shows the hardware overview with the location of   US requirement, only: This device must be the service button, not the dedicated events. It is installed in a UL-listed enclosure offering...
  • Page 12: Wall Mounting

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS 3. Hold the controller as shown in below image and 3. Remove the controller from the wall and drill four Mount the controller onto the DIN rail. holes at the marked locations.
  • Page 13: Power Supply

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS POWER SUPPLY Chopper Wiring All wiring must comply with applicable electrical codes General Information and ordinances, or as specified on installation wiring diagrams. Controller wiring is terminated to the screw To prevent a risk of injury due to electrical shock and/or terminal blocks located on the device.
  • Page 14: Chopper Wiring Example

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Chopper Wiring Example Earth Grounded This equipment must be earthed (grounded). 11 12 13 14 15 18 19 21 22 23 32 33 34 35 36 37 38 FUSE 11 12 13 14 15...
  • Page 15: Input / Output Wiring

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS INPUT / OUTPUT WIRING Wiring Requirements NOTE: When attaching two or more wires to the same terminal, other than 14 AWG (2.0 mm ), be sure to twist them together. Deviation from this rule can result in improper electrical contact.
  • Page 16: Internal Wiring Example

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Internal Wiring Example Internal Wiring Large controller 230 VAC 11 12 13 14 15 18 19 21 22 23 32 33 34 35 36 37 38 11 12 13 14 15...
  • Page 17 HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Internal Wiring Small controller 230 VAC 21 22 23 NC1 NO1 IN1 NC2 NO2 IN2 NC3 NO3 IN3 NC4 NO4 IN4 POWER 230V DO RELAY DO CHP -28V Isolated +28V +21V...
  • Page 18: Terminal Connections

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Terminal Connections Table 15 Terminal Connections Terminal Label Description Power 230 V Neutral Earth ground (connected to building earth ground)   DO Relay Normally Closed 1 Normally Open 1 Universal signal input / output 1...
  • Page 19 HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Table 15 Terminal Connections Terminal Label Description Universal signal input / output 1 Common Universal signal input / output 2 Universal signal input / output 3 Common Universal signal input / output 4...
  • Page 20: Uio Wiring Examples

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS UIO Wiring Examples 11 12 13 14 15 18 19 21 22 23 32 33 34 35 36 37 38 11 12 13 14 15 18 19 21 22 23 32 33 34 35 36 37 38...
  • Page 21: Do Chp Wiring Example

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS DO CHP Wiring Example 21 22 23 37 38 21 22 23 37 38 NC1 NO1 IN1 NC2 NO2 IN2 NC3 NO3 IN3 NC4 NO4 IN4 IO13 C IO14 IO15 C IO16...
  • Page 22: Auxiliary Wiring Examples

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Auxiliary Wiring Examples 11 12 13 14 15 18 19 21 22 23 32 33 34 35 36 37 38 18 19 21 22 23 11 12 13 14 15 32 33 34 35 36 37 38...
  • Page 23: Network Concepts

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS NETWORK CONCEPTS IP Network Topologies • Recommended cable: CAT5, CAT6 etc. The RS-485 Standard • Maximum distance between two controllers or a controller and switch should be less than 328 ft According to the RS-485 standard (TIA/EIA 485: (100 m).
  • Page 24: Bacnet™ Ip Controller

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS BACNET™ IP CONTROLLER Every Unitary controller has a physical MAC address printed on the device. The physical MAC address of the controller is listed using the "arp -a" function on the command prompt of a Windows computer.
  • Page 25: Bacnet™ Ms/Tp Wiring

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS BACNET™ MS/TP WIRING Termination Resistors Matched terminating resistors are required at each end The MS/TP models of the Honeywell Unitary controllers of a segment bus wired across (+) and (-). Use matched use the BACnet™...
  • Page 26: Bacnet™ Ms/Tp Wiring Example

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS BACnet MS/TP Wiring Example BACnet MS/TP CONTROLLER BACnet MS/TP CONTROLLER BACnet MS/TP CONTROLLER Shield SHLD SHLD SHLD RS485 RS485 RS485 Reference Shield PLANT CONTROLLERS Fig. 22 Connection to a BACnet™ MS/TP Bus NOTE: •...
  • Page 27: Bacnet™ Ms/Tp Controller

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS BACNET™ MS/TP CONTROLLER All Honeywell Unitary controllers are BACnet™ MS/TP clients. Every client performs periodic polling for the possible appearance of new clients. Each client “knows” BACnet™ MS/TP Limitations the identity of the “next” client (for example, that...
  • Page 28: Setting The Device Instance Number

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS All ON All OFF Fig. 25 MS/TP MAC Address Details To set the MAC address of a Honeywell Unitary controller BACnet™ MS/TP: 1. Find an unused MAC address on the BACnet™...
  • Page 29: T1L Communication And Standard

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS T1L COMMUNICATION AND Ring Topology STANDARD In case Unitary controllers are connected in a redundant ring. In that case, you must have one spanning tree protocol supported Ethernet switch as a The standard Ethernet, 4-wire solution has evolved into part of the ring.
  • Page 30: Modbus Rtu

    1 and 65534. SERVER Fig. 30 Prohibited Wiring Topology (example) Modbus Compliance As per the Modbus standard, the Unitary controller is a Cables and Shielding conditionally compliant “regular” Modbus device. Use shielded twisted pair cable J-Y-(St)-Y 4 x 2 x 0.8 and...
  • Page 31: Modbus Considerations

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Modbus Considerations The RS-485 interface suitable for Modbus communication is 2-wire with shield non-isolated, hence the following considerations apply: • Maximum Modbus length (“L”): 4000 feet (1200 meters) for 9.6 – 78.8 kbps or 2600 feet (790 meters) for 115.2 kbps.
  • Page 32: Sylk

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS SYLK™ NOTE: • Shielded cable is recommended if there is a need Sylk™ compatible wall modules such as TR120 can be to reduce the effect of electrical noise. connected to the controller's Sylk™ (terminals 50 and •...
  • Page 33: Sylk™ Wiring Example

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Sylk™ Wiring Example 21 22 23 37 38 21 22 23 37 38 IO13 C IO14 IO15 C IO16 NC1 NO1 IN1 NC2 NO2 IN2 NC3 NO3 IN3 NC4 NO4 IN4...
  • Page 34: Troubleshooting

    Check if the Status LED's behavior is changed if you switch the power OFF/ON. If this does not solve the problem, contact your reseller. The Unitary controller features a BACnet™ device manager that can be used to analyze the controller’s function and communication for troubleshooting purposes.
  • Page 35: Led Interface

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS LED Interface BACnet RJ45 (IP) Model MODBUS LED STATUS LED SERVICE PIN LED SERVICE BUTTON LED BACnet MS/TP Model MS/TP LED MODBUS LED STATUS LED SERVICE PIN LED SERVICE BUTTON LED...
  • Page 36: Bluetooth Led Status

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Bluetooth LED Status Table 23 Bluetooth LED Status LED Status Visual Mode BLE disabled Green LED BLE normal operation and connected permanent ON Green LED, 2 blinks in 1 sec followed by...
  • Page 37: T1L Led Status

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS T1L LED Status Table 26 T1L LED Status LED Status Visual Mode Green LED Link is up, Valid IP address is configured. permanent OFF Communication is healthy. Yellow LED Link is up, No valid IP address is configured.
  • Page 38: Regulatory Information

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS REGULATORY INFORMATION (2) This device must accept any interference, including interference that may cause undesired operation of the device. FCC Regulation This device complies with the Canadian ICES-003 Class This device complies with Part 15 of the FCC Rules.
  • Page 39: Standards And Compliance

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Table 29 BLE Certification Numbers above 0.1 % weight by weight (w/w) shall provide the recipient of the article with sufficient information, available to the supplier, to allow safe use of the...
  • Page 40: Appendix

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS APPENDIX Sensor Input Accuracy The controller's internal sensor inputs support both 10 K NTC Ω and 20 K NTC Ω sensors. The following table lists the typical minimum accuracies of the hardware and software for these temperature sensors.
  • Page 41: Recognition Of Sensor Failure Of Sensor Inputs

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Recognition of Sensor Failure of Sensor Inputs The thresholds at which the sensor fails, that is, sensor breaks (SB) and short-circuits (SC), are recognized, depending upon the given sensor type. In the event of a recognized sensor failure, the sensor assumes the safety values configured in Table 31 on page 40.
  • Page 42: Sensor Characteristics

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Sensor Characteristics The characteristics (resistance in relation to temperature) of the sensors and the resultant voltage are listed on the following pages. The stated values do not include failures due to sensor failures, wiring resistance or wiring failures, mis readings due to a meter connected to measure resistance or voltage at the input.
  • Page 43 HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Table 33 10 K NTC TYPE II Characteristics (Continued) Terminal Terminal Temp. Temp. Resistance Temp. Temp. Resistance Voltage Voltage [°F] [°C] [KΩ] [°F] [°C] [KΩ] 33.8 31.027 5.189 91.4 7.098 2.159 93.2...
  • Page 44: 10 K Ntc Type Iii Characteristics

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS 10 K NTC TYPE III Characteristics Table 34 10 K NTC TYPE III Characteristics Temp. Temp. Temp. [°F] Resistance [Ω] Temp. [°F] Resistance [Ω] [°C] [°C] -37.2 203.6K 40.6 5479 -34.4 173.6K...
  • Page 45: 10 K3A1 Characteristics

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS 10 K3A1 Characteristics Table 35 10 K3A1 Characteristics Temp. Temp. Resistance Temp. Temp. Resistance [°F] [°C] [Ω] [°F] [°C] [Ω] 336098 26.6 38110 -38.2 314553 28.4 36184 -36.4 294524 30.2 34366 -34.6...
  • Page 46 HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Table 35 10 K3A1 Characteristics (Continued) Temp. Temp. Resistance Temp. Temp. Resistance [°F] [°C] [Ω] [°F] [°C] [Ω] 42317 89.6 7402 24.8 40151 91.4 7097 93.2 6807 159.8 1693 6530 161.6 1637 96.8...
  • Page 47: 20 K Ntc Characteristics

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Table 35 10 K3A1 Characteristics (Continued) Temp. Temp. Resistance Temp. Temp. Resistance [°F] [°C] [Ω] [°F] [°C] [Ω] 156.2 1813 222.8 1752 224.6 226.4 242.6 228.2 244.4 246.2 231.8 233.6 249.8 235.4...
  • Page 48 HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Table 36 20 K NTC Characteristics (Continued) Temp. Temp. Resistance Terminal Temp. Temp. Resistance Terminal [°F] [°C] [KΩ] voltage [V] [°F] [°C] [KΩ] Voltage [V] -20.2 8.41 42.8 51.1 -18.4 8.38 44.6...
  • Page 49 HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Table 36 20 K NTC Characteristics (Continued) Temp. Temp. Resistance Terminal Temp. Temp. Resistance Terminal [°F] [°C] [KΩ] voltage [V] [°F] [°C] [KΩ] Voltage [V] 109.4 8.98 2.57 174.2 2.24 0.818 111.2...
  • Page 50 HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Table 36 20 K NTC Characteristics (Continued) Temp. Temp. Resistance Terminal Temp. Temp. Resistance Terminal [°F] [°C] [KΩ] voltage [V] [°F] [°C] [KΩ] Voltage [V] 240.8 0.68 0.266 0.31 0.122 242.6 0.66...
  • Page 51: Nickel Class B Din 43760 Sensors

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Nickel Class B DIN 43760 Sensors T(R) = a´+b´(1+c´R)½ +d´R5+e´R7 dT < 0.12 K (higher order equations on request) The characteristic of the nickel temperature sensor is specified as per DIN 43760. The large Temperature...
  • Page 52: Ni1000 Tk5000 Din B

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS NI1000 TK5000 DIN B R-T Characteristics of Ni1000 TK5000 DIN B. Table 38 NI1000 TK5000 Sensor Specification Sensor Type Nominal Resistance Sensitivity : 1000 Ω Ni1000 TK5000 DIN B TC: 5000 ppm/K Table 39 R-T Characteristics (according to supplier‘s specifications and based on DIN 43760, resistance values...
  • Page 53: Pt100 Characteristics

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS PT100 Characteristics Table 40 PT100 Characteristics Temp. [°F] Temp.[°C] Resistance [Ω] -34.44 -28.89 -23.33 -17.78 -12.22 -6.67 -1.11 0.00 4.44 10.00 15.56 21.11 25.00 26.67 32.22 37.78 43.33 48.89 54.44 60.00 65.56...
  • Page 54: Pt1000 Characteristics

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS PT1000 Characteristics Table 41 PT1000 Characteristics Terminal Temp. Temp. Resistance Terminal Temp. Temp. Resistance Voltage [°F] [°C] [KΩ] Voltage [V] [°F] [°C] [KΩ] 0.312 0.367 -56.2 0.314 10.4 0.369 -54.4 0.315 12.2...
  • Page 55 HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Table 41 PT1000 Characteristics (Continued) Terminal Temp. Temp. Resistance Terminal Temp. Temp. Resistance Voltage [°F] [°C] [KΩ] Voltage [V] [°F] [°C] [KΩ] 75.2 1093 0.42 145.4 1244 0.476 1097 0.422 147.2 1248 0.477...
  • Page 56 HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Table 41 PT1000 Characteristics (Continued) Terminal Temp. Temp. Resistance Terminal Temp. Temp. Resistance Voltage [°F] [°C] [KΩ] Voltage [V] [°F] [°C] [KΩ] 143.6 1240 0.474 213.8 1389 0.528 215.6 1393 0.53 1536 0.581...
  • Page 57 HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Table 41 PT1000 Characteristics (Continued) Terminal Temp. Temp. Resistance Terminal Temp. Temp. Resistance Voltage [°F] [°C] [KΩ] Voltage [V] [°F] [°C] [KΩ] 282.2 1532 0.58 350.6 1674 0.63 352.4 1677 0.631 420.8...
  • Page 58 HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Table 41 PT1000 Characteristics (Continued) Terminal Temp. Temp. Resistance Terminal Temp. Temp. Resistance Voltage [°F] [°C] [KΩ] Voltage [V] [°F] [°C] [KΩ] 1813 0.679 487.4 1952 0.727 489.2 1955 0.728 557.6 2092 0.775...
  • Page 59 HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS Table 41 PT1000 Characteristics (Continued) Terminal Temp. Temp. Resistance Terminal Temp. Temp. Resistance Voltage [°F] [°C] [KΩ] Voltage [V] [°F] [°C] [KΩ] 555.8 2088 0.774 624.2 2223 0.82 2226 0.821 690.8 2353 0.863...
  • Page 60: Pt3000 Characteristics

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS PT3000 Characteristics Table 42 PT3000 Characteristics Terminal Temp. Temp. Resistance Terminal Temp. Temp. Resistance Voltage [°F] [°C] [KΩ] Voltage [V] [°F] [°C] [KΩ] 2.82 1.02 3.74 1.31 2.87 1.03 3.78 1.32 2.91...
  • Page 61: Actuators Wiring Examples

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS ACTUATORS WIRING EXAMPLES M6410C & M7410A/C Wiring Example M6410C & You can connect the actuator to whichever chopper output port M7410A/C 24V short stroke linear valve & 24VAC 50/60 Hz PICV actuator max., 100mA...
  • Page 62: Ml6420A Wiring Example

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS ML6420A Wiring Example You can connect the actuator to whichever Chopper output port. ML6420A There is no cable on the actuator, the 24V large linear valve actuator cable is selected by the electrician.
  • Page 63: M400/M800 & Mt4/Mt8 Wiring Example

    HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS M400/M800 & MT4/MT8 Wiring Example M400/M800 & You can connect the actuator to whichever Chopper output port MT4/MT8 Fig. 35 M400/M800 & MT4/MT8 wiring example 31-00610-01...
  • Page 64: Abbreviations

    The material in this document is for information purposes only. The content and the product described are subject to change without notice. Honeywell makes no representations or warranties with respect to this document. In no event shall Honeywell be liable for technical or editorial omissions or mistakes in this document, nor shall it be liable for any damages, direct or incidental, arising out of or related to the use of this document.

Table of Contents