Antes de instalar este producto, lea la información de seguridad. Läs säkerhetsinformationen innan du installerar den här produkten. Safety statement Read this section carefully before operating any task on the cabinet. R001 CAUTION: To ensure safety, all configurations of the rack cabinet must be certified by a nationally recognized testing laboratory to verify compliance with country-specific safety regulations.
Page 8
S036 18 - 32 kg (39 - 70 lb) 32 - 55 kg (70 - 121 lb) > 55 kg (121 lb) CAUTION: Use safe practices when lifting. R006 CAUTION: Do not place any object on top of a rack-mounted device unless that rack-mounted device is intended for use as a shelf.
Page 16
Hardware box Figure 3. Components in the hardware box Table 2. Components in the hardware box 20 M6 screws One socket wrench 16 flange nuts One spud socket wrench 20 G-type cage nuts 15 cable ties One combination wrench Two bolt-down brackets ThinkSystem Micro DataCenter 6U 800mm Deep Rack Cabinet User Guide...
Page 18
Figure 4. Opening the door 2. Remove the four shipping brackets that secure the cabinet to the pallet. Figure 5. Removing shipping brackets Two options are available when moving the cabinet: ThinkSystem Micro DataCenter 6U 800mm Deep Rack Cabinet User Guide...
Casters S037 CAUTION: The weight of this part or unit is more than 55 kg (121.2 lb). It takes specially trained persons, a lifting device, or both to safely lift this part or unit. Complete the following steps to move the cabinet to the designated site: Step 1.
Figure 7. Adjusting the rack cabinet feet Step 2. Make sure the ramp board is lowered and balanced, and then push the cabinet from the rear until it reaches the designated site. Figure 8. Sliding the cabinet down from the pallet Notes: •...
Page 21
Attention - Drop hazard. Complete the following steps to lift and move the cabinet to the designated site: Step 1. Remove the four plugs from the four corners on the top of the cabinet frame. Figure 9. Lifting the rack cabinet Step 2.
Page 22
b. Insert the open end of the combination wrench in the hardware box (see “Hardware box” on page 6) into the hexagonal head of the foot, and turn it clockwise until the foot makes firm contact with the floor. Figure 11. Adjusting the rack cabinet foot c.
Page 23
Figure 13. Installing the bolt-down brackets Chapter 4 Moving the rack cabinet...
Page 24
ThinkSystem Micro DataCenter 6U 800mm Deep Rack Cabinet User Guide...
Page 26
Figure 15. Grounding cable from the cabinet frame Grounding cable from the cabinet door This is an optional grounding cable. ThinkSystem Micro DataCenter 6U 800mm Deep Rack Cabinet User Guide...
Page 27
Figure 16. Grounding cable from the cabinet door Grounding cable from the side panel This is an optional grounding cable. Chapter 5 Managing cables...
Page 28
Figure 17. Grounding cable from the side panel ThinkSystem Micro DataCenter 6U 800mm Deep Rack Cabinet User Guide...
Page 30
P P r r o o c c e e d d u u r r e e Step 1. Remove the inner rails. Figure 18. Removing the inner rails ① Pull the inner rail outward until the release latch becomes visible. ②...
Page 31
Figure 19. Installing the inner rails to the enclosure ① Align the mounting holes in the inner rail with the corresponding rail mounting pins on the side of the enclosure. ② Push the inner rail as shown until the mounting pins on the enclosure lock into place with the inner rail.
Page 32
Figure 21. Removing compute nodes ① Press on the release button. ② Slide the node out from the enclosure. Step 6. Install the rear mounting bracket of the right outer rail to the lower EIA flange. Figure 22. Installing the rear mounting bracket to the EIA flange ①...
Page 33
Figure 23. Installing the front mounting bracket to the EIA flange Note: Make sure the rail stays horizontal. ① Open the front bracket and align the front end of the outer rail to the EIA flange. ② Pull the outer rail into the EIA flange until the pins are inserted into the corresponding holes. ③...
Page 34
Figure 25. Rotating SE350 E2 Enclosure Step 11. Install the E2 Enclosure into the rack. Figure 26. Installing SE350 E2 Enclosure Note: Make sure the top of the enclosure is facing right. ① Lift and align the enclosure to the slide rails. Position the enclosure as shown, and slide it into the rack.
Page 35
③ Push the enclosure all the way into the rack until it clicks into locked position. Step 12. (Optional) Open the rack release latches and tighten the screws to firmly secure the rail before moving or placing the rack cabinet in a vibration-prone area. Figure 27.
① (Optional) To reduce the weight of the enclosure, disconnect the power adapter cables from the nodes and remove the nodes. ② Disconnect all the cables that are connected to the enclosure, and slide the enclosure out until it stops. ③...
Page 37
Figure 29. Removing the inner rails ① Pull the inner rail outward until the release latch becomes visible. ② Press on the release latch. ③ Remove the inner rail from the outer rail. Step 2. Install the inner rails to the server. Chapter 6 Installing optional kits...
Page 38
Figure 30. Installing the inner rails to the enclosure ① Align the mounting holes in the inner rail with the corresponding rail mounting pins on the side of the server. ② Push the inner rail as shown until the mounting pins on the server lock into place with the inner rail.
Page 39
Step 4. Install the rear mounting bracket of the right outer rail to the lower EIA flange. Figure 32. Installing the rear mounting bracket to the EIA flange ① Align the rear pins on the outer rails to the EIA flange. ②...
Page 40
Step 6. Repeat the previous two steps to install the left outer rail to the upper EIA flange. Step 7. (Optional) If you need to ship the rack cabinet with servers installed or place the rack cabinet in a vibration-prone area, install two M6 screws into the mounting flanges between the two rear pins on both sides.
Figure 36. Securing the server Rack release latches Front screw Remove the server from the rack Figure 37. Removing SR250 ① Disconnect all the cables that are connected to the server, and slide the server out until it stops. ② Press the release latches to disengage the inner rails. ③...
Page 42
• When moving or replacing the cabinet after installation, contact a qualified installer specified by Lenovo service. Installation or movement of the product must be carried out by a skilled professional. If an unqualified person moves and installs the product, it may cause safety risks.
Page 43
Figure 38. Mounting bolt location on the wall Step 2. Remove the six screws that secure the two wheeled trays. Chapter 6 Installing optional kits...
Page 44
Figure 39. Removing the wheeled trays Step 3. Loosen the two M12 nuts on the feet on one long side of the cabinet. Figure 40. Loosening the nuts Step 4. Slide the lower wall mounting bracket in, and tighten the nuts to secure the brackets. Step 5.
Page 45
Figure 41. Securing the lower bracket Step 8. Connect the two eyebolts and two keyholes in the upper wall mounting bracket to the hook of a crane lifter, and make sure the cord length allows an angle more than 75˚. Step 9.
Page 46
Figure 42. Installing wall mount nails Step 12. Repeat the previous step on the other three spots on the wall. Step 13. Lift the cabinet with two people, and align the key-shaped holes on the upper bracket to the two top nails;...
Figure 43. Installing the cabinet to the wall Install the DPI universal rack power distribution unit Follow the instructions in this section to install the DPI universal rack power distribution unit. A A b b o o u u t t t t h h i i s s t t a a s s k k See the following table to identify the components that come with the rail kit.
Page 48
One small mounting plate One cable management bracket One horizontal mounting plate One power distribution unit One 1U blank filler panel P P r r o o c c e e d d u u r r e e Step 1. Secure the power distribution unit to one side of the horizontal mounting plate with two screws.
Installing switches See this section to learn how to install switches into ThinkSystem Micro DataCenter 6U 800mm Deep Rack Cabinet. This rack cabinet supports the following switches. See the corresponding links for installation instructions. • https://systemx.lenovofiles.com/help/topic/com.lenovo.thinksystem.ne0152t.doc/ts_ne0152t.html • https://systemx.lenovofiles.com/help/topic/com.lenovo.thinksystem.ne1032t.doc/ts_ne1032t.html • https://systemx.lenovofiles.com/help/topic/com.lenovo.thinksystem.ne2572.doc/ts_ne2572.html •...
Note: Before installing NE1032T and NE1072T RackSwitch with corresponding rail-kit into the rack cabinet, tilt them slightly so that they can slide through the cabinet frame. Figure 46. Tilting the switch to fit in the cabinet Installing uninterruptible power systems (UPS) See this section to learn how to install uninterruptible power systems (UPS).
Step 1. Align the bottom of the panel to the slot on the bottom of the cabinet frame, and pivot the top of the panel towards the cabinet frame. Figure 48. Installing the side panel Step 2. Insert the key and turn it clockwise to secure the panel to the cabinet frame. Removing, installing and reversing the doors Follow the instructions in this section to remove, install, and reverse the doors.
Page 53
Figure 49. Opening the door P P r r o o c c e e d d u u r r e e Step 1. Pull up and hold both of the hinge shafts to disengage the door from the cabinet frame; then, remove the door.
Figure 50. Removing the door Install the door A A b b o o u u t t t t h h i i s s t t a a s s k k Note: For safety, this task must be done by two people. P P r r o o c c e e d d u u r r e e Step 1.
A A f f t t e e r r t t h h i i s s t t a a s s k k i i s s c c o o m m p p l l e e t t e e d d 1.
Page 56
Figure 53. Opening the door P P r r o o c c e e d d u u r r e e Step 1. Pull up and hold both of the hinge shafts to disengage the door from the cabinet frame; then, remove the door.
Page 57
Figure 54. Removing the door Step 2. Remove the screws that secure the hinges to the cabinet frame. Step 3. Rotate both hinges 180 degree, switch the top and bottom hinges; then, install them to the opposite side of the frame. Figure 55.
Page 58
Step 4. If the cabinet comes with door position monitor devices, complete the following steps to remove and reinstall the devices. Remove the two screws that secure the door position monitor device to the cabinet frame. Figure 56. Removing the door position monitor device Install the device to the equivalent location on the opposite side on the cabinet frame.
Page 59
Figure 58. Removing and installing the door position monitor device Step 5. Remove the screws that secure the handle to the door; then, rotate the door 180 degree while keeping the handle in the original orientation, and secure the handle to the door with screws. Figure 59.
Page 60
Step 6. Align the door to the frame hinges, and push the shafts in to secure the door to the frame. Figure 60. Installing the door A A f f t t e e r r t t h h i i s s t t a a s s k k i i s s c c o o m m p p l l e e t t e e d d 1.
See this section for replacement of the door position monitor device. Note: This component is a Third Party Option parts. Not with standing anything to the contrary, third party options are excluded from Lenovo Statement of Limited Warranty. See https://support.lenovo.com/us/en/ for details.
Remove the door position monitor device Follow the instructions in this section to remove the door position monitor device. A A b b o o u u t t t t h h i i s s t t a a s s k k 1.
Figure 64. Removing door position monitor device Install the door position monitor device P P r r o o c c e e d d u u r r e e Step 1. Secure the device to the cabinet frame with two screws. Figure 65.
Page 64
Figure 66. Closing the cabinet door 2. If necessary, insert the key and turn it counterclockwise to lock the door. ThinkSystem Micro DataCenter 6U 800mm Deep Rack Cabinet User Guide...
Appendix A. Getting help and technical assistance If you need help, service, or technical assistance or just want more information about Lenovo products, you will find a wide variety of sources available from Lenovo to assist you. On the World Wide Web, up-to-date information about Lenovo systems, optional devices, services, and support are available at: http://datacentersupport.lenovo.com...
Gathering information needed to call Support If you believe that you require warranty service for your Lenovo product, the service technicians will be able to assist you more efficiently if you prepare before you call. You can also see http:// for more information about your product warranty.
Lenovo representative for information on the products and services currently available in your area. Any reference to a Lenovo product, program, or service is not intended to state or imply that only that Lenovo product, program, or service may be used. Any functionally equivalent product, program, or service that does not infringe any Lenovo intellectual property right may be used instead.
Trademarks Lenovo, the Lenovo logo, Micro DataCenter, ThinkSystem, Flex System, System x, NeXtScale System, and X Architecture are trademarks of Lenovo in the United States, other countries, or both. Intel and Intel Xeon are trademarks of Intel Corporation in the United States, other countries, or both.