• Always install stabilizer brackets on the rack cabinet. • Always install the heaviest devices in the bottom of the rack cabinet. • Always install servers and optional devices starting from the bottom of the rack cabinet. R003 ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
Page 8
Do not connect a power cord from a device that is installed in one rack cabinet to a power device that is installed in a different rack cabinet. R009 CAUTION: ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
Chapter 2. Specifications See this section for information about ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet. Dimension and weight Dimension • Length: 1200 mm (47.24 inch) • Width: – Without the wheeled tray: 345 mm (13.58 inch) – With the wheeled tray: 512.5 mm (20.18 inch) •...
Page 14
ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
Page 16
Table 2. Components in the hardware box 20 M6 screws One socket wrench 16 flange nuts One spud socket wrench 15 cable ties 20 G-type cage nuts One combination wrench Two bolt-down brackets ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
Page 18
Figure 4. Opening the door 2. Remove the four shipping brackets that secure the cabinet to the pallet. Figure 5. Removing shipping brackets ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
Two options are available when moving the cabinet: Casters S037 CAUTION: The weight of this part or unit is more than 55 kg (121.2 lb). It takes specially trained persons, a lifting device, or both to safely lift this part or unit. Complete the following steps to move the cabinet to the designated site: Step 1.
• Make sure that more than two people are handling the cabinet while sliding it down from the ramp board. • Do not stand in the path of the cabinet. Crane lifter ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
Page 21
Attention - Drop hazard. Complete the following steps to lift and move the cabinet to the designated site: Step 1. Remove the four plugs from the four corners on the top of the cabinet frame. Figure 9. Lifting the rack cabinet Step 2.
Page 22
5) into the hexagonal head of the foot, and turn it clockwise until the foot makes firm contact with the floor. Figure 11. Adjusting the rack cabinet foot c. Once the leveling foot makes firm contact with the floor, tighten the nut that fixes it. ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
Page 23
Figure 12. Tightening the nut 2. To secure the cabinet to the ground, you can install the bolt-down brackets that is included in the hardware box (see in “Hardware box” on page 5). Figure 13. Installing the bolt-down brackets Chapter 4 Moving the rack cabinet...
Page 24
ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
Page 26
Figure 15. Grounding cable from the cabinet frame Grounding cable from the cabinet door This is an optional grounding cable. ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
Page 27
Figure 16. Grounding cable from the cabinet door Grounding cable from the side panel This is an optional grounding cable. Chapter 5 Managing cables...
Page 28
Figure 17. Grounding cable from the side panel ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
Page 30
② Press on the release latch. ③ Remove the inner rail from the outer rail. Step 2. Install the inner rails to the enclosure. Figure 19. Installing the inner rails to the enclosure ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
Page 31
① Align the mounting holes in the inner rail with the corresponding rail mounting pins on the side of the enclosure. ② Push the inner rail as shown until the mounting pins on the enclosure lock into place with the inner rail.
Page 32
Step 8. Rotate the E1 enclosure clockwise so that the right side is facing down. Have one person hold on the front side, while the other hold on the rear side. ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
Page 33
Figure 23. Rotating SE350 E1 Enclosure Step 9. Install the E1 Enclosure into the rack. Figure 24. Slide the E1 Enclosure into the rails in the rack. Chapter 6 Installing optional kits...
Page 34
Step 10. (Optional) Open the rack release latches and tighten the screws to firmly secure the rail before moving or placing the rack cabinet in a vibration-prone area. Figure 25. Securing the enclosure Rack release latches Front screw Remove SE350 E1 enclosure from the rack ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
Figure 26. Removing SE350 E1 enclosure ① Disconnect all the cables that are connected to the enclosure, and slide the enclosure out until it stops. ② Press the release latches to disengage the inner rails. ③ Have one person hold the front end of the enclosure, while the other person removes the enclosure. Install the rail kit and SR250 A A b b o o u u t t t t h h i i s s t t a a s s k k See the following table to identify the components that come with the rail kit.
Page 36
① Pull the inner rail outward until the release latch becomes visible. ② Press on the release latch. ③ Remove the inner rail from the outer rail. Step 2. Install the inner rails to the server. ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
Page 37
Figure 28. Installing the inner rails to the enclosure ① Align the mounting holes in the inner rail with the corresponding rail mounting pins on the side of the server. ② Push the inner rail as shown until the mounting pins on the server lock into place with the inner rail.
Page 38
① Open the front bracket and align the front end of the outer rail to the EIA flange. ② Pull the outer rail into the EIA flange until the pins are inserted into the corresponding holes. ③ Close the front bracket to secure the rail. ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
Page 39
Step 6. Repeat the previous two steps to install the left outer rail to the upper EIA flange. Step 7. (Optional) If you need to ship the rack cabinet with servers installed or place the rack cabinet in a vibration-prone area, install two M6 screws into the mounting flanges between the two rear pins on both sides.
Install the rail kit and SR670 A A b b o o u u t t t t h h i i s s t t a a s s k k ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
Page 41
The cabinet supports up to two units of SR670 and corresponding rail kit. For optimal use of space, it is advised to determine the location to install the rail kits based on the number of units that are installed. • One unit: 1-3U •...
Page 42
Note: Do not fully remove the rack mounting brackets as they are required to secure the server into the vertical rack. Step 2. Secure the mounting glides to the server. Figure 37. Securing the mounting glides ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
Page 43
① Align the key hole slots in the glides to the T-head pins on both sides of the server, and slide the mounting glides forward until the pins are secured in the slots. ② Align the two holes on the mounting glide to the threaded standoffs on the front end of the server.
Page 44
Do NOT over-tighten the screws as the rack EIA flange could be deformed. Step 5. Rotate the server 90 degree clockwise so that the right side is facing down. ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
Page 45
Figure 40. Rotating the server Step 6. Lift the server with two people, and slide it into the C-channels. Figure 41. Installing the server into the rack cabinet Step 7. Tighten both the upper and lower captive thumb screws. Chapter 6 Installing optional kits...
Page 46
Figure 42. Securing the rack mounting brackets Step 8. Secure each rack mounting bracket with two M5 x 20 mm screws. ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
Figure 43. Securing the rack mounting brackets Install the DPI universal rack power distribution unit Follow the instructions in this section to install the DPI universal rack power distribution unit. A A b b o o u u t t t t h h i i s s t t a a s s k k See the following table to identify the components that come with the rail kit.
Page 48
Secure the power distribution unit to one side of the horizontal mounting plate with two screws. Figure 44. Securing the power distribution unit Step 2. Install the bracket to the rack. ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
Installing switches See this section to learn how to install switches into ThinkSystem Micro DataCenter 6U 800mm Deep Rack Cabinet. This rack cabinet supports the following switches. See the corresponding links for installation instructions. • https://systemx.lenovofiles.com/help/topic/com.lenovo.thinksystem.ne0152t.doc/ts_ne0152t.html • https://systemx.lenovofiles.com/help/topic/com.lenovo.thinksystem.ne1032t.doc/ts_ne1032t.html • https://systemx.lenovofiles.com/help/topic/com.lenovo.thinksystem.ne2572.doc/ts_ne2572.html •...
See this section to learn how to install uninterruptible power systems (UPS). Following the instructions in the following link to do removal, installation, or to update compatible software for 5P1500R-L (120V) and 5P1550GR-L (230V). https://www.eaton.com/us/en-us/catalog/backup-power-ups-surge-it-power-distribution/eaton-5p- ups.resources.html ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
P P r r o o c c e e d d u u r r e e 1. If necessary, insert the key and turn it clockwise to unlock the door. 2. Pull the lower end of the handle up and clockwise; then, open the door. ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
Page 53
Figure 49. Opening the door A A f f t t e e r r t t h h i i s s t t a a s s k k i i s s c c o o m m p p l l e e t t e e d d Step 1.
P P r r o o c c e e d d u u r r e e Step 1. Align the door to the frame hinges, and push the shafts in to secure the door to the frame. Figure 51. Installing the door ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
A A f f t t e e r r t t h h i i s s t t a a s s k k i i s s c c o o m m p p l l e e t t e e d d 1.
Page 56
P P r r o o c c e e d d u u r r e e Step 1. Pull up and hold both of the hinge shafts to disengage the door from the cabinet frame; then, remove the door. ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
Page 57
Figure 54. Removing the door Step 2. Remove the screws that secure the hinges to the cabinet frame. Step 3. Rotate both hinges 180 degree, switch the top and bottom hinges; then, install them to the opposite side of the frame. Chapter 7 Hardware removal, installation and conversion...
Page 58
Remove the two screws that secure the door position monitor device to the cabinet frame. Figure 56. Removing the door position monitor device Install the device to the equivalent location on the opposite side on the cabinet frame. ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
Page 59
Figure 57. Installing the door position monitor device Remove the device from the door, and install it to the equivalent location on the opposite side of the door. Figure 58. Removing and installing the door position monitor device Step 5. Remove the screws that secure the handle to the door;...
Page 60
Figure 59. Installing the handle brackets Step 6. Align the door to the frame hinges, and push the shafts in to secure the door to the frame. ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
Page 61
Figure 60. Installing the door A A f f t t e e r r t t h h i i s s t t a a s s k k i i s s c c o o m m p p l l e e t t e e d d 1.
Download the latest version of the User Guide from the applicable product page of . To https://www.apc.com find a product page, enter the part number (NBRK0250) into the search field. You can also find the ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
documentation on https://www.se.com : enter the part number in the search field, and select Documents and Software under Product information. Remove the door position monitor device A A b b o o u u t t t t h h i i s s t t a a s s k k 1.
Page 64
Close the cabinet door, and turn the door handle counterclockwise to secure it. Figure 65. Closing the cabinet door b. If necessary, insert the key and turn it counterclockwise to lock the door. ThinkSystem Micro DataCenter 6U 1200mm Deep Rack Cabinet User Guide...
Appendix A. Getting help and technical assistance If you need help, service, or technical assistance or just want more information about Lenovo products, you will find a wide variety of sources available from Lenovo to assist you. On the World Wide Web, up-to-date information about Lenovo systems, optional devices, services, and support are available at: http://datacentersupport.lenovo.com...
Gathering information needed to call Support If you believe that you require warranty service for your Lenovo product, the service technicians will be able to assist you more efficiently if you prepare before you call. You can also see http:// for more information about your product warranty.
Lenovo representative for information on the products and services currently available in your area. Any reference to a Lenovo product, program, or service is not intended to state or imply that only that Lenovo product, program, or service may be used. Any functionally equivalent product, program, or service that does not infringe any Lenovo intellectual property right may be used instead.
Trademarks Lenovo, the Lenovo logo, Micro DataCenter, ThinkSystem, Flex System, System x, NeXtScale System, and X Architecture are trademarks of Lenovo in the United States, other countries, or both. Intel and Intel Xeon are trademarks of Intel Corporation in the United States, other countries, or both.