Summary of Contents for Toshiba TOSVERT VF-S15 Series
Page 1
1. Read this manual before installing or operating. Keep this instruction manual on hand of the end user, and make use of this manual in maintenance and inspection. 2. All information contained in this manual will be changed without notice. Please contact your Toshiba distributor to confirm the latest information.
Page 2
E6581911 Introduction Thank you for purchasing TOSVERT VF-S15 series Inverter. ® Before using CANopen communication function, carefully read this function manual in order to completely and correctly utilize its excellent performance. After reading this function manual, please keep it handy for future reference.
E6581911 Table of Contents 1. Scope ..............................4 1.1. Overview ........................... 4 2. Names and functions of main parts ....................4 2.1. Name of main parts ........................4 2.2. LED indicator (CiA 303-3) ......................5 2.3. CAN LED indicator ........................5 2.4.
Page 4
E6581911 7. Example communication ........................37 7.1. Asynchlonous communication....................37 7.2. SYNC communication ......................39 8. Specifications ........................... 41 8.1. Data and operating specification ..................... 41 8.2. CANopen device specification ....................41 8.3. Connecting of CANopen communication option ..............42 - 3 -...
E6581911 1. Scope 1.1. Overview Thank you for purchasing TOSVERT VF-S15 inverter. VF-S15 can connect with open field network ® ® CANopen network and data communications with the VF-S15 CANopen option supports up to 64 nodes for one segment. ® By using CANopen function, the monitor of run/stop and the setting change of the parameter become possible from the network, and it can cope with various applications.
E6581911 2.2. LED indicator (CiA 303-3) ® CAN LED indicate CANopen communication Status and Error condition. 2.3. CAN LED indicator RUN status LED display. Those functions are below table. CAN RUN Status Green LED State Description CAN ERR Status Red LED Blinking The device is in state PRE-OPERATIONAL...
E6581911 2.4. Command & Setpoint selection (Local/Remote) ® CANopen communication command and setpoint are activated on Remote mode. Inverters have some switches to select the command and setpoint location. Following figure shows the diagram. Refer to the inverter instruction manual for the parameter in detail. cmod Input terminal function Input terminal function...
E6581911 2.6. Network configuration Make up the network as follows. - Transmission/reception signals (CAN_H, CAN_L) Make up the communication path by connecting twisted cables with shield. - Signal common (CAN_GND) GND is the signal common. - Grounding the shield of cable (CAN_SHLD) Connect the all shield lines of network cable.
E6581911 2.7. Bus cable length (CiA 303-1) Bus cable length depends on the below items. a) Number of the slave b) Cable type c) Bit rate Master R Slave ・ ・ ・ Slave Slave Slave Slave AC parameters : 120 ohm impedance and 5ns/m specific line delay Number of Node and Bit rate.
E6581911 2.8. Example of SCAN time Below table is the recommended scan time depend on the number of the drive and the baud rate. 1 unit : Tx 8byte(4word) / Rx 8byte(4word) ・・・ total 129bit (include stub 5 bits) Delay : 3.5ms Margin : 80% SCAN time (ms) Drive Unit No.
E6581911 3. Parameters 3.1. Command and Freq. Reference setting Set up the inverter parameters as follows when command via CiA 402 profile. From CANopen network, the drive parameters can be commanded directory. The latest commanded parameters are activated when same run command / frequency reference command.
E6581911 3.2. Communication parameters Default P No. Parameter function Note Value Number of motor poles for 2: 4 pole f856 communication 0: Terminal board, Panel keypad or FA00 reset command rests the drive. CANopen (CiA 402, FA04) and COM option (CiA 402, FA06) reset command f898 Inverter reset mode selection only reset fault condition.
Page 13
E6581911 Receive: COB-ID entry #1400 subidx 01 c711 PDO1 High word If the setting is default setting, COB-ID is 0x00000200 below value. c712 Low word COB-ID=0x00000200+Node- RPDO transmission type #1400 subidx 02 Asynchronous c713 0x0FF Transmit :COB-ID #1800 subidx 01 c714 High word If the setting is default setting, COB-ID is...
Page 14
E6581911 Default P No. Parameter function Note Value #1600 subidx 00 Receive PDO1 Number of command c750 PDO1 0x02 assignment: Number of objects assigned objects #1600 subidx 01 Command Index No. Command 1 0x6040 c751 0x6040: Controlword #1600 subidx 02 Command Index No. c752 Command 2 0x6042...
Page 15
E6581911 Warning Set up “Communication error trip function (c100 ~ c103)” to stop the inverter when CANopen communication is deactivated. When CANopen state is “OPERATIONAL”, the CANopen communication parameters Mandatory can not be changed. Set the CANopen state to “PRE-OPERATIONAL.” action When the parameters are changed, the power must be cycled to the VF-S15 for the changes to take effect.
E6581911 4. Communication Object Object Dictionary has mainly 3 object set. ・Communication Profile Area (Index 1000 to 1FFFh) ・Manufacturer Specific Profile Area (Index 2000 to 5FFFh) ・Standard Device Profile Area (Index 6000 to 9FFFh) 4.1. Communication Profile (DS 301) 4.1.1. Communication Profile (1000 to 11FFh) These object are CANopen communication configuration settings for example Node-ID etc..
Node Guarding protocol is deactivated on the drive (Guard Time = 0). 0x01 ID object: Number of objects 1018 ID object: Supplier ID 0x00000284 0x00000284 : Toshiba Schneider Inverter Co. 4.1.2. SDO sever object SDO COB-ID object type is only read. Index Access Type Default value...
E6581911 4.1.3. PDO object PDO1 to PDO3 and PDO21. PDO set RPDO TPDO Note Controlword Statusword COB-ID is variable mapping. vl_target_velocity vl_velocity_actual_value PDO1 TPDO1 : 0x00000180+Node-ID variable mapping variable mapping RPDO2 : 0x00000200+Node-ID variable mapping variable mapping variable mapping variable mapping COB-ID is variable mapping.
Page 19
E6581911 0x02 Receive PDO21: Number of objects Receive PDO21 COB-ID entry The default value is 0x80000500 (parameter data c741) 0x80000500 +Node-ID. If set other than 0x80000500 except bit31, new set 1414 + Node-ID data is used for COB-ID(=new data). Bit31 is an enable/disable flag of RPDO21 data set. Receive PDO21: Transmission type 0x0FF “asynchronous”...
E6581911 4.1.5. TPDO object Index Access Type Default value Description (Hex) index 0x05 Transmit PDO1: Number of entries Transmit PDO1: COB-ID The default value is 0x00000180 (parameter data c713) 0x00000180 +Node-ID. If set other than 0x00000180 except bit31, new + Node-ID set data is used for COB-ID(=new data).
E6581911 Index Access Type Default value Description (Hex) index Transmit PDO1 assignment: Number of objects assigned Set 0(=Disable) before changing Sub-index 01-04 of this 0x02 Object, and set Sub-index 01-04 values of the corresponding sub-indices then set the number of mapped objects (=Enable).
E6581911 5. Drive profile Using CiA 402 Drive profile, form CANopen network, the drive can be controlled. When using the drive profile command, please set the command mode selection to CANopen (cmod=3), Frequency setting mode selection 1 to CANopen (fmod=6) and f856 Number of motor poles for communication ( ) parameters.
E6581911 5.1.1. Object 603Fh: Error Code Below table describes the relations of the error code and inverter error. Inverter Inverter Error trip error Meaning Inverter condition code code name 0000h No error 0x0E Motor overload 0x15 Main unit RAM fault err2 0x16 Main unit ROM fault...
E6581911 5.1.2. Object 6040h: Controlword ms = manufacturer-specific; r = reserved; oms = operation mode specific; h = halt; fr = fault reset; eo = enable operation; qs = quick stop; ev = enable voltage; so = switch on Bold bits shall be supported, other may be supported. From any state START Fault reaction active...
Page 27
E6581911 Transition events and action (CiA DS402-2 DSP V3.0 Table 26) Transition Event(s) Action(s) Automatic transition after power-on or reset Drive device self-test and/or self application initialisation shall be performed. Automatic transition Communication shall be activated. Shutdown command from control device or local None signal Switch on command received from control device...
E6581911 5.1.7. Object 6046: vl_velocity_min_max_amount This object indicates the configured minimum and maximum amount of velocity (unit min ). The vl_velocity_max amount sub-object is mapped internally to the vl_velocity_max positive and vl_velocity_max negative values. The vl_velocity_min amount sub-object is mapped internally to the vl_velocity_min positive and vl_velocity_min negative values.
E6581911 5.1.12. Object 6060: Modes of operation This object shall indicate the requested operation mode. With the VF-S15, only velocity mode is supported as the operation mode, therefore any request to this object would make no sense. Value Definition -128 to -1 Manufacture-specific operation modes No mode change/no mode assigned Profile position mode...
E6581911 6.2.1. Read object (Upload object) Sending below data, the object data can be read. Send data to read object COB-ID Data0 Data1 Data2 Data3 Data4 Data5 Data6 Data7 0x600+ Obj. No. Node-ID index Response data for read object (byte) COB-ID Data0 Data1...
E6581911 6.2.3. Abort code The abort code in the below table are set in the error response data. Abort Code Contents 0503 0000 Toggle bit not alternated. 0504 0000 SDO protocol timed out. 0504 0001 Client/server command specifier not valid or unknown. 0504 0002 Invalid block size (block mode only).
E6581911 6.3. PDO communication Using PDO (Process Data Object) communication, send and receive inverter command and monitor data with synchronously or asynchronously. 6.3.1. TxPDO and RxPDO communication type TxPDO (Inverter send PDO) can be set below condition in table. TxPDO1 Transmission type : Object 1800h subindex 02 TxPDO2 Transmission type : Object 1801h subindex 02 TxPDO3 Transmission type : Object 1802h subindex 02 TxPDO21 Transmission type : Object 1814h subindex 02...
E6581911 6.3.2. RTR (Remote Transfer Request) communication When set RTR setting into TxPDO Transmission type (1800h, 1801h, 1802h, 1814h subindex 02), sending the RTR (Remote Transfer Request) message, Inverter send TxPDO message. TxPDO1 RTR message data COB-ID Data0 Data1 Data2 Data3 Data4 Data5...
E6581911 6.4. Communication disconnection detection function ® VF-S15 CANopen supports Heartbeat service and Node Guarding service to detect the communication disconnection. Heartbeat service and Node Guarding service function can not be active at the same time. ・ Heartbeat service ・ Heartbeat Consumer Watching the heartbeat message of the specific Node-ID, and checking the interval time, the inverter can detect the network abnormal condition.
E6581911 7. Example communication 7.1. Asynchlonous communication This is a example communication to control run/stop the inverter and set frequency command. Termination resister Factory Parameter Function Comments setting 3: command from CANopen cmod Command mode setting 6: command from CANopen fmod Frequency command selection 1 ~ 127...
E6581911 7.2. SYNC communication This is a sample communication using SYNC message. Factory Parameter Function Comments setting Command from CANopen Network cmod Command mode selection Command from CANopen Network fmod Frequency setting mode selection 1 ~ 127 c701 Node-ID Board rate CAN baud rate setting 4: 500k c702...
Page 41
E6581911 5. SYNC (Update RxPDO received data to control data) INV - PC COB-ID Data0 Data1 Data2 Data3 Data4 Data5 Data6 Data7 0x080 ← 6. RxPDO1 (Change to “Switch on” state) INV - PC COB-ID Data0 Data1 Data2 Data3 Data4 Data5 Data6 Data7...
E6581911 8. Specifications 8.1. Data and operating specification Item Specification CiA DS301 V4.02 Communication Profile CiA DR 303-3 V1.3 Indicator specification CiA DSP 402 Ver1.1 Drives and motion control device profile, Velocity mode Communication medium CAN (ISO 11898) 8.2. CANopen device specification Item Specification Comments...