Self-Diagnosis Function And Checking Points - Fujitsu AOYR14LCL Service Instruction

Wall mounted type inverter, refrigerant r410a, indoor/outdoor unit
Table of Contents

Advertisement

Self - diagnosis function and Checking points
Error Indication
Error
Operation
Timer
(Protection)
(RED)
(GREEN)
OFF
0.5 sec
Serial reverse transfer error
2 times
at starting up operation
0.5 sec
Serial reverse transfer error
3 times
during the operation
0.5 sec
Serial forward transfer error
4 times
at starting up operation
0.5 sec
Serial forward transfer error
5 times
during the operation
0.5 sec
0.5 sec
Room temperature therm-
2 times
2 times
istor defective
0.5 sec
Indoor heat exchanger
3 times
thermistor error
At the start up, the indoor unit does not receive the signal for 10 consecutive seconds from the time when the power relay was ON.
>Permanent stop after 30 seconds.
[Diagnosis Point]
Check the indoor /outdoor cable connection (in order). If the cable wiring is not abnormal, measure the voltage of the outdoor
unit terminals and diagnose the defective location.
(Refer to the after mentioned [Serial Signal Diagnosis] for the voltage measuring method and diagnosis method.)
When the indoor unit does not receive the signal for 10 consecutive seconds during the operation
seconds.
[Diagnosis Point]
Check the indoor /outdoor cable connection (in order). If the cable wiring is not abnormal, measure the voltage of the outdoor
unit terminals and diagnose the defective location.
(Refer to the after mentioned [Serial Signal Diagnosis] for the voltage measuring method and diagnosis method.)
The outdoor unit does not receive the signal for 10 consecutive seconds from the time when the power relay was ON.
>Outdoor unit stops.
[Diagnosis Point]
Check the indoor /outdoor cable connection (in order). If the cable wiring is not abnormal, measure the voltage of the outdoor
unit terminals and diagnose the defective location.
(Refer to the after mentioned [Serial Signal Diagnosis] for the voltage measuring method and diagnosis method.)
When the outdoor unit does not receive the signal for 10 consecutive seconds during the operation > Outdoor unit stops.
[Diagnosis Point]
Check the indoor /outdoor cable connection (in order). If the cable wiring is not abnormal, measure the voltage of the outdoor
unit terminals and diagnose the defective location.
(Refer to the after mentioned [Serial Signal Diagnosis] for the voltage measuring method and diagnosis method.)
The room temperature thermistor detective a abnormai temperature when the power was turned on. > Remote control does not
operate.
[Diagnosis Point]
Check thermistor resistance value (Refer to "Themistor characteristics table").
Controller PCB defective.
The detection value of the indoor heat exchanger thermistor is either open or shoted when the power is ON. > Remote control dose
not operate.
[Diagnosis Point]
Check thermistor resistance value (Refer to "Themistor characteristics table").
Controller PCB defective.
Diagnosis Method
>Permanent stop after 30