9410 series - User manual
Configuring onboard digital outputs using ION Setup
To configure the meter's digital outputs using ION Setup:
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Click Onboard I/O > Digital Outputs and select a digital output tab. Configure the digital
output by selecting the parameter and clicking Edit. Enter the meter password if prompted.
Parameter
Source
Force ON
Force OFF*
Normal*
Polarity
PulseWidth
Assigned Port
State
* These parameters are only valid when pulse width is set to 0.
Configuring option module digital outputs using ION Setup
To configure the option module digital outputs using ION Setup:
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Click Expansion Module > Option I/O Modules and select the module tab that
corresponds to the option module with the digital output you want to configure.
4. Select the digital output channel and click Edit. The setup screen for that digital output is
7EN05-0336-09
Value/range
Description
Link this input to the value that drives the state of the
digital output.
Digital/Boolean
If Source is not linked, the digital output state is
driven by the Force ON, Force OFF values.
Link this input to a pulse that forces the digital output
Pulse
on for the PulseWidth duration, regardless of the
Source input.
Link this input to a pulse that forces the digital output
Pulse
off.
Pulsing this input will switch the driver of the digital
Pulse
output from Force ON to Source.
Specifies if the signal to the digital port is inverted or
Inverting/non-inverting
not inverted.
Specifies the duration of the pulse, in seconds.
0–2,000,000
Setting this parameter to 0 sets the digital output
continuously on.
The physical digital output port connection. Only
-
available ports are shown.
Open/Closed/Not
Indicates the status of the digital output.
Available
Inputs/Outputs
135