Page 4
Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
Page 5
In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
Page 6
(EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
Table of contents Table of contents Section 1 Introduction...............5 This manual..................5 Intended audience................5 Product documentation...............5 Product documentation set............5 Document revision history.............6 Related documentation..............6 Symbols and conventions..............7 Symbols..................7 Document conventions..............7 Functions, codes and symbols............8 Section 2 IEC 60870-5-103 data mappings........11 Overview...................11 Supported functions................11 Point list for RET615 Ver.4.0 TE01-08..........13 Indications and controls...............13...
Page 8
Table of contents LD0.MAPGAPC4 Multipurpose analog protection function (4)................19 LD0.MAPGAPC5 Multipurpose analog protection function (5)................19 LD0.MAPGAPC6 Multipurpose analog protection function (6)................19 LD0.XRGGIO130 Alarm and warning........20 LD0.PHPTOV3 Phase overvoltage protection - stage 3..20 LD0.PHPTOV2 Phase overvoltage protection - stage 2..20 LD0.PHPTOV1 Phase overvoltage protection - stage 1..20 LD0.PHPTUV3 Phase undervoltage protection - stage 3.....................21 LD0.PHPTUV2 Phase undervoltage protection - stage...
Page 10
Table of contents COMMON ADDRESS of ASDU..........38 Selection of standard information numbers in monitor direction..................38 System functions in monitor directions........38 Status indications in monitor direction........38 Supervision indications in monitor direction......39 Earth fault indications in monitor direction......39 Fault indications in monitor direction........39 Auto-reclosure indications in monitor direction.......40 Measurands in monitor direction..........41 Generic functions in monitor direction........41...
Section 1 1MRS756883 C Introduction Section 1 Introduction This manual The point list manual describes the outlook and properties of the data points specific to the IED. The manual should be used in conjunction with the corresponding communication protocol manual. Intended audience This manual addresses the communication system engineer or system integrator responsible for pre-engineering and engineering for communication setup in a...
B/2010-06-11 Content updated to correspond to the product version C/2012-05-11 Content updated to correspond to the product version Download the latest documents from the ABB Web site http://www.abb.com/substationautomation. 1.3.3 Related documentation Name of the document Document ID IEC 60870-5-103 Communication Protocol Manual...
Section 1 1MRS756883 C Introduction Symbols and conventions 1.4.1 Symbols The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.
Section 2 1MRS756883 C IEC 60870-5-103 data mappings Section 2 IEC 60870-5-103 data mappings Overview These tables show the default point definitions. The user is able to freely remap all these data. In that case PCM600 can provide an updated point list export of the new outlook.
Section 2 1MRS756883 C IEC 60870-5-103 data mappings Point list for RET615 Ver.4.0 TE01-08 2.3.1 Indications and controls Table 3: Explanations of the indications and controls table columns Column name Description IEC 61850 Original IED data object identification. Described in the IEC 61850 format as name Logical Device.Logical Node and thereafter .Data Object.Data Attribute.
Section 2 1MRS756883 C IEC 60870-5-103 data mappings IEC 61850 name SA name Description DPI value ASDU LD0.LEDPTRC1 .Op.general Global operate 10=Operate .Str.general Global start 10=Start 2.3.1.2 General Data(FUN=10) - 615-specific Table 5: General Data(FUN=10) - 615-specific IEC 61850 name SA name Description DPI value...
Section 2 1MRS756883 C IEC 60870-5-103 data mappings IEC 61850 name SA name Description DPI value ASDU .SPCS04.ctlVal Output control 4 10/01=On/Off .SPCS05.ctlVal Output control 5 10/01=On/Off .SPCS06.ctlVal Output control 6 10/01=On/Off .SPCS07.ctlVal Output control 7 10/01=On/Off .SPCS08.ctlVal Output control 8 10/01=On/Off .SPCS09.ctlVal Output control 9...
Section 2 1MRS756883 C IEC 60870-5-103 data mappings 2.3.1.15 LD0.MAPGAPC2 Multipurpose analog protection function (2) Table 18: LD0.MAPGAPC2 Multipurpose analog protection function (2) IEC 61850 name SA name Description DPI value ASDU LD0.MAPGAPC2 .Str.general START Stage Start 10=Start .Op.general OPERATE Stage Operate 10=Operate 2.3.1.16...
Section 2 1MRS756883 C IEC 60870-5-103 data mappings 2.3.1.43 LD0.PHHPTOC1 Phase overcurrent protection - high stage 1 Table 46: LD0.PHHPTOC1 Phase overcurrent protection - high stage 1 IEC 61850 name SA name Description DPI value ASDU LD0.PHHPTOC1 High stage (1) .Str.phsA -phsA start 10=Start...
Section 2 1MRS756883 C IEC 60870-5-103 data mappings IEC 61850 name SA name Description DPI value ASDU .SPCSO8.stVal LED 8 state 10=On .SPCSO9.stVal LED 9 state 10=On .SPCSO10.stVal LED 10 state 10=On .SPCSO11.stVal LED 11 state 10=On 2.3.2 Class 2 data measurands Class 2 data measurands use ASDU type 9, function type 10 and information number 236 for frame 6 and 237 for frame 7.
Section 2 1MRS756883 C IEC 60870-5-103 data mappings Table 68: Explanations of the class 2 data measurands table columns Column name Description IEC 61850 Original IED data object identification. Described in the IEC 61850 format as name Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical Node is the same as the application function block name.
Page 40
Section 2 1MRS756883 C IEC 60870-5-103 data mappings IEC 61850 name Description Scale ix (T-a) xi (T-b) .Tmp.mag Temperature 1000 .TmpRl.mag Relative temperature 1000 LD0.CMSTA1 Demand currents (1) LD0.CMSTA1 Phase-current demands .AvAmpsA.mag -phsA magnitude .AvAmpsB.mag -phsB magnitude .AvAmpsC.mag -phsC magnitude LD0.CMSTA2 Demand currents (2) LD0.CMSTA2 Phase-current demands...
Page 41
Section 2 1MRS756883 C IEC 60870-5-103 data mappings IEC 61850 name Description Scale ix (T-a) xi (T-b) .phsB.cVal.mag Bias current B .phsC.cVal.mag Bias current C LD0.XRGGIO130 RTD Input data LD0.XRGGIO130 .AnIn1.mag RTD input 1 10000 .AnIn2.mag RTD input 2 10000 .AnIn3.mag RTD input 3 10000...
Section 3 1MRS756883 C Interoperability profile for 615 series IEC 60870-5-103 Section 3 Interoperability profile for 615 series IEC 60870-5-103 Physical layer 3.1.1 Electrical interface ⊠ EIA RS-485 ⃞ Number of loads ......for one protection equipment NOTE - EIA RS-485 standard defines unit loads so that 32 of them can be operated on one line. For detailed information refer to clause 3 of EIA RS-485 standard.
Section 3 1MRS756883 C Interoperability profile for 615 series IEC 60870-5-103 Application layer 3.3.1 Transmission mode for application data Mode 1 (least significant octet first), as defined in 4.10 of IEC 60870-5-4, is used exclusively in this companion standard. 3.3.2 COMMON ADDRESS of ASDU ⊠...
Section 3 1MRS756883 C Interoperability profile for 615 series IEC 60870-5-103 ⃞ <27> Auxiliary input 1 ⃞ <28> Auxiliary input 2 ⃞ <29> Auxiliary input 3 ⃞ <30> Auxiliary input 4 Note <27>...<30>: Depending on Binary I/O options and application usage there may be additional auxiliary inputs available in the IED.
Section 3 1MRS756883 C Interoperability profile for 615 series IEC 60870-5-103 ⃞ <66> Start /pick-up L ⃞ <67> Start /pick-up N ⊠ <68> General trip ⃞ <69> Trip L ⃞ <70> Trip L ⃞ <71> Trip L ⃞ <72> Trip I>> (back-up operation) ⃞...
Section 3 1MRS756883 C Interoperability profile for 615 series IEC 60870-5-103 3.3.3.7 Measurands in monitor direction Semantics ⊠ <144> Measurand I ⊠ <145> Measurands I, V ⊠ <146> Measurands I, V, P, Q ⊠ <147> Measurands I ⊠ <148> Measurands I , P, Q, f L1,2,3 L1,2,3...
Section 3 1MRS756883 C Interoperability profile for 615 series IEC 60870-5-103 3.3.5 Basic application functions ⃞ Test mode ⃞ Blocking of monitor direction ⊠ Disturbance data ⃞ Generic services ⊠ Private data 3.3.6 Miscellaneous Measurands are transmitted as Class2 data using ASDU 3 or ASDU 9. The default MVAL scalings in 615 series devices is 2.4.
Section 4 1MRS756883 C Glossary Section 4 Glossary 615 series Series of numerical IEDs for low-end protection and supervision applications of utility substations, and industrial switchgear and equipment Electromagnetic compatibility Human-machine interface International Electrotechnical Commission IEC 60870-5-103 1. Communication standard for protective equipment 2.