Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
Page 5
In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
Page 6
(EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
Section 1 1MRS756881 B Introduction Section 1 Introduction This manual The point list manual describes the outlook and properties of the data points specific to the IED. The manual should be used in conjunction with the corresponding communication protocol manual. Intended audience This manual addresses the communication system engineer or system integrator responsible for pre-engineering and engineering for communication setup in a...
Some of the manuals are not available yet. 1.3.2 Document revision history Document revision/date Product version History A/2009-07-03 First release B/2010-06-11 Content updated to correspond to the product version Download the latest documents from the ABB web site http:// www.abb.com/substationautomation. RET615 Point List Manual...
Section 1 1MRS756881 B Introduction 1.3.3 Related documentation Name of the document Document ID DNP3 Communication Protocol Manual 1MRS756709 Symbols and conventions 1.4.1 Safety indication symbols The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.
Section 1 1MRS756881 B Introduction The corresponding parameter values are "On" and "Off". • IED input/output messages and monitored data names are shown in Courier font, for example: When the function starts, the START output is set to TRUE. 1.4.3 Functions, codes and symbols Table 1: RET615 Functions, codes and symbols...
Page 14
Section 1 1MRS756881 B Introduction Function IEC 61850 IEC 60617 IEC-ANSI Three-phase overvoltage PHPTOV1 3U> (1) 59 (1) protection, instance 1 Three-phase overvoltage PHPTOV2 3U> (2) 59 (2) protection, instance 2 Three-phase thermal overload protection for power transformers, T2PTTR1 3Ith>T two time constants Stabilized and instantaneous differential protection for 2W –...
Page 15
Section 1 1MRS756881 B Introduction Function IEC 61850 IEC 60617 IEC-ANSI Disturbance recorder RDRE1 Three-phase current CMMXU1 measurement, instance 1 Three-phase current CMMXU2 3I(B) 3I(B) measurement, instance 2 Sequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0 Residual current measurement, RESCMMXU1 instance 1 Residual current measurement,...
Section 2 1MRS756881 B DNP3 data mappings Section 2 DNP3 data mappings Overview This document describes the DNP3 data points and structures available in RET615 Ver. 3.0. The data points are unmapped as a default.The point lists describe a superset of all data available through the standard configurations A, B, C, D, E, F, G, and H including the optional functionalities.
Implementation table and the point list tables, provides a complete configuration/interoperability guide for communicating with a device. Table 5: Device profile document DNP3 device profile document Vendor name: ABB Oy Device name: RET615 Highest DNP level supported: Device function: For requests: Level 2+ ○...
Page 30
Section 3 1MRS756881 B DNP3 protocol implementation DNP3 device profile document ○ Sometimes ● Configurable as: "Only when reporting event data", or "When reporting event data or multi-fragment messages" Timeouts while waiting for: Data link ○ None ○ Fixed at ____ ○...
Section 3 1MRS756881 B DNP3 protocol implementation DNP3 device profile document ○ Configurable ○ When device restarts ○ Only certain objects ○ When status flags change ○ Sometimes (attach explanation) ○ ENABLE/DISABLE UNSOLICITED No other options are permitted. function codes supported Default counter object/variation: Counters roll over at: ●...
Page 32
Section 3 1MRS756881 B DNP3 protocol implementation Table 6: Implementation table OBJECT REQUEST (Library will parse) RESPONSE (Library will respond with) Object Variation Function codes Qualifier codes number number Description Function codes (dec) Qualifier codes (hex) (dec) (hex) Binary 1 (read) 00, 01 (start-stop) input –...
Page 33
Section 3 1MRS756881 B DNP3 protocol implementation OBJECT REQUEST (Library will parse) RESPONSE (Library will respond with) 16-bit 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop) 2 (default) analog 06 (no range, or all) 17, 28 (index) input 07, 08 (limited qty) 17, 28 (index) 32-bit...
Page 34
Section 3 1MRS756881 B DNP3 protocol implementation OBJECT REQUEST (Library will parse) RESPONSE (Library will respond with) Time delay 129 (response) 07 (limited qty) fine (qty = 1) Not defined Class 0 1 (read) 06 (no range, or all) data Class 1 1 (read) 06 (no range, or all)
Section 4 1MRS756881 B Glossary Section 4 Glossary Application function block library Circuit breaker CROB Control relay output block Common time of occurrence. The time and date CTO object is an information object that represents the absolute time of day. Data attribute DNP3 A distributed network protocol originally developed by...