Alternative language versions are available for download from the Honeywell Analytics website www.honeywellanalytics.com Alternatieve talen versies zijn electronisch beschikbaar via onze web pagina van Honeywell Analytics: www.honeywellanalytics.com Les versions alternatives de langue sont disponibles pour le téléchargement du website www.honeywellanalytics.com de Honeywell Analytics Las versions alternativas de la lengua están disponibles para la transferencia...
Page 3
For your safety, it is required to calibrate the detector periodically (See Section 4 Calibration). Honeywell Analytics can take no responsibility for use of its equipment if it is not used in accordance with the instructions stated in the relevant manual. If further details are required but not provided in this manual, contact Honeywell Analytics or their agent.
Page 4
No gas will be detected while in the set-up mode or the gas exposure status review mode. • The desktop USB memory card reader and data logging kit are not certified intrinsically safe and must not be used in potentially hazardous atmospheres. X4 Series...
Page 6
Chaque jour, avant toute utilisation, tester la sensibilité sur une concentration connue de méthane équivalente à 25-50% LEL. La précision doit être comprise dans une plage de +/-20% de concentration réelle. a précision peut être corrigée en effectuant un étalonnage approprié du détecteur. X4 Series...
Page 7
Honeywell analytics charger (part number 2566-0484) when charging the sealed rechargeable battery pack (part number 2566-0482 for Minimax4 series and part number 2566-0462 for impulse X4 series). use of any other charger will void the intrinsic safety certification of the instrument.
Page 8
Warning use only the Honeywell analytics supplied ac adapter (part number 2566-0483) to connect to the cradle charger (part number 2566-0484). aVErtissEMEnt utiliser uniquement l’adaptateur à courant alternatif Honeywell analytics fourni (référence 2566-0483) pour connecter l’instrument au chargeur socle (référence 2566-0484).
4--. Span Gas Information ........6 4--. Span Gas Setting ........... 4--4. Gas Search and Countdown ...... 4--5. Span Calibration Result ........8 5. Set-Up Mode ..............29 5-1. Entering the Set-Up Mode ........30 5-2. Changing the Detector Set-Up .......31 5-3. Exiting the Set-Up Mode.........31 X4 Series...
Page 10
C-2. Accuracy Statement ..........47 C-3. Declaration ..............48 C--1. Declaration for the Minimax4 series ....48 C--. Declaration for the ImpulseX4 series .....49 Appendix D ................50 D-1. Specifications ............50 D-1-1. Specifications for the Minimax4 series ...50 D-1-. Specifications for the ImpulseX4 series ..51 X4 Series...
1. Introduction The X4 series is an easy to use personal gas detector, designed for monitoring the atmosphere for potentially hazardous levels of flammables, oxygen, carbon monoxide, and hydrogen sulfide. It uses a front-mounted LCD display to show readings of the gases being measured and other useful information. A loud audible alarm and bright visual alarm are used to warn users when the concentrations of measured gases exceed the alarm set points.
(for flammable and toxic) mode in a low light area, press the UP or DOWN button once. Zero Calibration Icon Span Calibration Icon Gas Label Icon Deficiency Alarm Icon Excess Alarm Icon X4 Series...
1-4. Standard Accessories The items listed below are included with the X4 series. For damaged or missing parts, contact Honeywell Analytics or their agent. Part No. Description 2566-0424 Calibration Certificate 2566-0422 Quick Start Guide 2566-0433 Alkaline Batteries (1.5V AA), Energizer E91 or EN91 ®...
“Data Fu” message and the “Delete no” prompt will not be displayed). Press the UP or DOWN buttons to scroll to “no” or “YES” and press the ON/OFF button to select. X4 Series...
2-2. Turning the Detector Off To turn off the detector, press and hold the ON/OFF button while in the measuring mode. A countdown will be displayed for 5 seconds, and then the detector will beep and turn off. X4 Series...
O deficiency) alarm set points • Display the STEL and TWA alarm set points (for CO & H S only). Level 1 Level 2 stEL *Examples shown for default settings of each gas for the Minimax4 series. X4 Series...
5 seconds. note If the Self-Test has failed, repeat the Self-Test. If a second failure occurs, contact Honeywell Analytics or their agent 3-2. Measuring Mode The detector may be used as either a “diffusion” or “sample-draw” type monitoring device. In normal operation, the detector is worn on the belt or held by hand. Once turned on, the detector monitors continuously.
15% of the applied gas concentration, a span calibration should be performed, under conditions of standard temperature (15°C to 5°C), humidity and pressure. Follow local regulations and/or your company’s policy on the frequency of bump testing. For more information on test gas, contact your local Honeywell Analytics representative. 3-4. Gas Alarms...
2 alarms are set to the same value, the level 2 alarm action overrides the level 1 alarm. The maximum value of the level 2 alarm in %Vol for flammable gas varies depending on the gas. (See Appendix B-2 Flammable Lower Explosive Limit.) X4 Series...
Page 20
When the reading returns to a normal level, the audible, visual and vibrating alarms will stop. If the measured reading exceeds the range of the sensor, the full-scale value will blink. See Section 5 Set-up Mode for more information on Latching/Non- Latching Alarms X4 Series...
Current Date Current date in MM DD - YY format (US) or DD MM - YY format (EU) Current Time Current time in HH:MM:SS format (24 hour format) * Examples shown for the status review for the Minimax4 series X4 Series...
Memory card readers can be purchased from Honeywell Analytics or from a local source of your choice. Card Readers must be able to read both MMC (MultiMediaCard) and SD (SecureDigital) cards.
Page 23
When the data Logging icon is either blinking or not displayed, it indicates that no data is being logged. To install or remove the memory card, see Section 6- Installing or Removing the Memory Card. X4 Series...
The detector will initiate a ZERO calibration showing a blinking ZERO Calibration icon and a countdown from ‘00’ to ‘000’. Countdown • When the ZERO calibration has been completed successfully for all sensors, the Test Pass icon will blink for 5 seconds. X4 Series...
Fail note If any sensor has failed, repeat the ZERO calibration ensuring that the detector is in fresh air. If a second failure occurs, contact Honeywell Analytics or their agent. Warning under proper calibration procedures, repetitive calibration failures could indicate that the sensor is either approaching its end of life, or it has been seriously contaminated, or both.
If the user fails to input the correct pass code 3 times consecutively, the detector will return to measuring mode. notE For lost pass code, contact Honeywell Analytics or their agent. 4-3-2. Span Gas Information The SPAN gas information will be displayed.
If no gas is detected within 30 seconds, the detector will give a single beep and a single flash, indicate an error “Err” for all gases on the LCD display, blink the Test Fail icon for 5 seconds, and then exit calibration mode. X4 Series...
Page 28
Repeat the SPAN calibration ensuring that the calibration gas used is of the correct concentration, there is sufficient gas in the cylinder and the flow rate is correct. If a second failure occurs, contact Honeywell Analytics or their agent. all Pass...
Enables or disables the pass code protection and changes the current pass code as required. (Factory default pass code protection setting is “oFF”. The factory default pass code is “000”.) note To proceed, the detector prompts the user to enter the current valid pass code. X4 Series...
If the Pass Code Protection feature has been activated, the detector prompts the user to enter the pass code. (See Section 4--1 Pass Code Input.) X4 Series...
5-3. Exiting the Set-Up Mode In set-up mode, if no button is pressed within 0 seconds, or both the UP and DOWN buttons are pressed together and held for seconds, the detector will revert back to the measuring mode. X4 Series...
Dispose of batteries according to local or national regulations. • Insert battery holder into the detector, turn the locking tab 90° clockwise, and return the locking tab to its original position. Lift Pull Turn 90º X4 Series...
2566-0482 for Minimax4 series and part number 2566-0462 for impulse X4 series). use of any other charger will void the intrinsic safety certification of the instrument. use only the Honeywell analytics supplied aC adaptor (part number 2566-0483) to connect to the charger (part number 2566-0484).
Clean the exterior of the detector with a clean damp cloth. • Clean the sensor grilles with a soft brush. 6-4. Replacing the Expired Sensor If the sensor reaches the end of its recommended life, contact Honeywell Analytics or their agent to arrange sensor replacement service. X4 Series...
(*) are not certified intrinsically safe and must not be used in potentially hazardous atmospheres. See Section 1-4 Standard Accessories for the part numbers of the standard (included) items. For inquiry see the Contacting Honeywell Analytics section on page 5. X4 Series...
ImpulseX-3-OFXH 2 gas Impulse X4 with O , Flammable sensors ImpulseX-2-OFXX 1 gas Impulse X4 with Flammable sensor ImpulseX-1-XFXX 1 gas Impulse X4 with O sensor ImpulseX-1-OXXX For inquiry see the Contacting Honeywell Analytics section on page 5. X4 Series...
(Exp / CO / H wait for 10 seconds < 3 Gas Calibration > Span Gas Search balance No Gas Found span gas search No gas for up to 30 seconds found Span Calibration 60 seconds countdown with span calibration icon blinking X4 Series...
< 1 Gas Calibration > Span Gas Search balance No Gas Detected span gas search No gas for up to 30 seconds detected Span Calibration 60 seconds countdown with span calibration icon blinking Span Cal. Span Cal. Success Fail Span Cal. Fail X4 Series...
Year data to save and scroll to to save and scroll to the next setting the next setting (US / MM / DD / YY) (EU / DD / MM / YY) < UP > or < DOWN > X4 Series...
User ID No 001 ~ 999 Setting ---------------------- < ON/OFF > < UP > to activate the function to increase < ON/OFF > < DOWN > to save the new number to decrease < UP > or < DOWN > X4 Series...
On/Off --------------------- to activate the function < ON/OFF > to save the status < ON/OFF > scroll to the next gas to save H S status / Exp / CO / < UP > or < DOWN > X4 Series...
When the detector is exposed to such shocks, a check should be performed on the sensors to verify accuracy (and a calibration performed if necessary). X4 Series...
For measuring other gases listed in the table, the detector should be calibrated with the target gas at relevant concentration and the proper Correction Factor needs to be set depending on the standard to be used. X4 Series...
Appendix C C-1. Warranty All products are designed and manufactured to the latest internationally recognized standards by Honeywell Analytics under a Quality Management system that is certified to ISO 9001:000. Device Warranty Terms 24 months from date of switch on / installation provided this takes place prior to the ‘Activate Before’...
To achieve optimal accuracy, the detector should be periodically supplied with a known concentration test gas, and if the readings are outside of 15% of the applied gas concentration, a span calibration should be performed, under conditions of standard temperature (15°C to 5°C), humidity and pressure. X4 Series...
Dimensions 124 mm (H) x 76 mm (W) x 36 mm (D) (4.9 in x 3.0 in x 1.4 in) Weight 210 g w/o batteries, 258 g w/batteries (7.4 oz w/o batteries, 9.1 oz w/batteries) Warranty 2 years X4 Series...
124 mm (H) x 76 mm (W) x 36 mm (D) (4.9 in x 3.0 in x 1.4 in) Weight 210 g w/o batteries, 258 g w/batteries (7.4 oz w/o batteries, 9.1 oz w/batteries) Warranty 2 years Energizer is a trademark of the Eveready Battery Company, Inc. X4 Series...