hit counter script
Honeywell IFP-75 Installation & Operation Manual
Honeywell IFP-75 Installation & Operation Manual

Honeywell IFP-75 Installation & Operation Manual

Addressable fire alarm control panel
Hide thumbs Also See for IFP-75:
Table of Contents

Advertisement

Quick Links

IFP-75/IFP-75HV
Addressable Fire Alarm Control Panel
Installation/Operation Manual
Farenhyt™ Series
Document LS10147-001SK-E Rev: D
06/25/2021 ECN: 3220

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell IFP-75

  • Page 1 Farenhyt™ Series IFP-75/IFP-75HV Addressable Fire Alarm Control Panel Installation/Operation Manual Document LS10147-001SK-E Rev: D 06/25/2021 ECN: 3220...
  • Page 2 For this reason, the rate-of- rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect property, not life. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 3 Farenhyt™ is a trademark; and eVance®, Flexput®, Honeywell®, JumpStart®, Silent Knight® and SWIFT® are registered trademarks of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. Chrome™ and Google™ are trademarks of Google Inc. Firefox® is a registered trademark of The Mozilla Foundation.
  • Page 4 Electrical and electronic equipment contains materials, parts and substances, which can be dangerous to the environment and harmful to human health if the waste of electrical and electronic equipment (WEEE) is not disposed of correctly. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 5: Table Of Contents

    Section 4: Control Panel Installation ..........................24 4.1: Mounting the Control Panel Cabinet ................................24 4.1.1: Preventing Water Damage..................................24 4.1.2: Removing the IFP-75 Assembly from the Housing ..........................24 4.1.3: Dead Front Installation and Removal ..............................25 4.2: AC Connection.........................................26 4.3: Battery Power ........................................27 4.3.1: Battery Accessory Cabinet ...................................28...
  • Page 6 Section 8: Programming Overview ..........................74 8.1: JumpStart Auto-Programming ..................................74 8.1.1: Input Points......................................74 8.1.2: Output Points ......................................74 8.1.3: Running JumpStart Auto-Programming ...............................74 8.2: Mapping Overview ......................................75 8.2.1: Input Point Mapping .....................................76 8.2.2: Output Circuit Mapping..................................76 IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 7 10.4.9: Silence Alarms or Troubles ................................108 10.4.10: Reset alarms....................................108 10.4.11: Check Detector Sensitivity Through Point Status ..........................108 10.4.12: View Status of a Point ..................................109 10.4.13: View Alarms, Supervisories or Troubles............................109 10.4.14: View System Information................................109 IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 8 10.9.1: Recording an F-Key Macro ................................116 Section 11: Reporting ..............................117 11.1: Receivers Compatible with the Control Panel .............................117 11.2: SIA / IFP-75 Panels PI Modifier Reporting:..............................125 11.3: SIA– IFP-75 Panel Communicator: ................................126 Section 12: Testing and Troubleshooting........................127 12.1: Troubleshooting ......................................127 12.2: Troubleshooting Common Problems ................................127...
  • Page 9: Section 1: Introduction

    Section 1: Introduction The IFP-75 (red) / IFP-75B (black) are IFP-75 Fire Alarm Control / Communicators that operate as an Addressable Fire Alarm Control Panel System that complies with the requirements of UL 864 10th Edition Standard. NOTE: *All references to IFP-75 within this manual are applicable to the IFP-75, IFP-75B, IFP-75HV and IFP-75HVB unless otherwise specified.
  • Page 10: About This Manual

    Mapping is the process of specifying which outputs are activated when certain events occur in the System. Section 8, Figure 8.2 explains mapping in detail. Network System Consist of any combination of 32 panels of these model numbers: IFP-75, IFP-300, IFP-300ECS, IFP-2100 or IFP-2100,ECS, IFP-75. SWIFT Smart Wireless Integrated Fire Technology Table 1.1 Manual Terminology...
  • Page 11 RJ31X cord for connecting phone line to the . 7628 UL Listed End-of-line resistor. DF-50 Dead Front insert. CELL-MOD Cellular board with Plastic Enclosure CELL-CAB-SK Cellular board with Metal Enclosure, Lock & key Table 1.2 IFP-75 Compatible Products (Continued) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 12: Section 2: Agency Listings, Approvals, And Requirements

    10. If your building has specially wired alarm equipment connected to the telephone line, ensure the installation of this IFP-75 does not disable your alarm equipment. If you have questions about what device will disable alarm equipment, consult your Telephone Company or qualified installer.
  • Page 13: Underwriters Laboratories (Ul)

    Use both phone lines. Enable phone line monitors for both lines. You must program a phone number and a test time so that the IFP-75 shall automatically initiate and complete a test signal transmission sequence to its associated receiver at least once every 6 hrs. The AC Loss Hours option must be set from 1-3 hours.
  • Page 14: 6: Requirements For The Installation Of Carbon Monoxide (Co) Detection And Warning Equipment, Nfpa 720

    LCD Annunciator RA-2000 LCD Annunciator SK-NIC Network card SK-FML/ -FSL Fiber module IFP-75CB or IFP-75BCB Enclosure Cell-Mod/Cell-Cab-SK Cellular transmitter Y = YES, N = NO, O = OPTIONAL Table 2.1 NFPA Requirements for IFP-75 IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 15: Section 3: Prerequisites For Installation

    IFP-75 panel for the first time. 3.1 Inventory When the IFP-75 shipment is received, check that all the parts have been included in the shipment. The shipment consists of one of each of the following: •...
  • Page 16 55 mA, 95 mA Data Network Used for SK-NIC 24 VDC 21 mA Note: *Regulated NAC application. When programmed for releasing, NAC are Special Application. Table 3.1 Terminal Descriptions and Electrical Specifications (Continued) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 17: Wiring Specifications

    SBUS Devices Note: 1/4” spacing must t be maintained SLC IN/OUT between each of these circuit types; as well as between power limited and non-power-limited circuits. Battery Battery Figure 3.1 Wire Routing Example IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 18: Board Assembly Diagram

    Figure 3.2 shows the circuit boards, and annunciator. If you need to remove the control board for repair, remove the three mounting screws which hold the control board in the cabinet. Then, lift the control board out of the cabinet. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 19: Calculating Current Draw And Standby Battery

    If the current is above 2.5A, you will need to use a notification power expander(s) (such as, the 5496 NAC Expander). Use the expander(s) to distribute the power loads, so that the IFP-75 or the power expanders do not exceed their power rating.
  • Page 20 5865-4 LED Annunciator (8 max.) Standby: 35 mA (with reset and silence switches) Alarm: 145 mA 5865-3 LED Annunciator Standby: 35 mA Alarm: 145 mA Table 3.3 Current Calculation Worksheet for IDP Devices (Continued) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 21 Devices” column for each DNR used for correct current calculations. Note 6: The FACP can support 30 devices with LED’s ON. This current draw is added to the panel’s alarm current. Table 3.3 Current Calculation Worksheet for IDP Devices (Continued) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 22: 3: Current Draw Worksheet For Sd Slc Devices

    SK-NIC Network Interface Card (1 Max.) Standby/Alarm: 21mA SK-FML Fiber-Optic Multi Mode (1 Max.) Standby/Alarm: 53mA SK-FSL Fiber-Optic Single Mode (1 Max.) Standby/Alarm: 79mA Total System Current Table 3.4 Current Calculation Worksheet for SD Devices IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 23 Maximum Battery Standby Load Table 3.5 shows the maximum battery standby load for the IFP-75 based on 24 and 60 hours of standby. The standby load calculations of line D in the Current Draw Calculation Worksheet (Table 3.5) must be less than the number shown in Table 3.5 for the battery size used and standby hours required.
  • Page 24: Section 4: Control Panel Installation

    The IFP-75 cabinet base dimensions are: 12.531” W x 14.875” H. The IFP-75 panel should be located within a secured area, where it is accessible to the main drop wiring runs and where it can be easily tested and serviced. End-users responsible for maintaining the panel should be able to hear alarms and troubles. When you select a location, keep in mind that the panel itself is the main source of alarm and trouble annunciation.
  • Page 25: 3: Dead Front Installation And Removal

    Remove the two screws and star washers from the bottom of the cabinet. See Figure 4.2. Remove the dead front panel from the control panel cabinet. Reinsert the two annunciator screws. See Figure 4.2. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 26: Ac Connection

    POWER BEFORE SERVICING. THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAMAGED BY REMOVING AND/OR INSERTING CARDS, MODULES OR INTERCONNECTING CABLES WHILE THIS UNIT IS ENERGIZED. AC power for the IFP-75 is rated at 120VAC, 60Hz, 1.5A. AC power for the IFP-75HV is rated at 240VAC, 50/60Hz, 1A.
  • Page 27: Battery Power

    Connect the red wire from the control panel positive (+) terminal to the positive (+) side of Battery #1. Battery Jumper (P/N 140694) Shipped With Panel Black 12V Battery 12V Battery Figure 4.4 Battery Connection IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 28: 1: Battery Accessory Cabinet

    NOTE: Figure 4.7 is an example of how the wire connections can be routed. However, any other cabinet knock-outs (on either the main control panel or the RBB cabinet), that are not previously being used may be utilized to connect conduit between the two cabinets. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 29: Sbus Wiring

    938 ft. 1493 ft. 2362 ft. 0.600 309 ft. 781 ft. 1244 ft. 1969 ft. 0.700 265 ft. 670 ft. 1066 ft. 1687 ft. Table 4.2 Wire Distances Per Wire Gauge Using Copper Wire IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 30 Using this value, and referring to the Wiring Distance table, it can be found that the available options are: • 370 feet maximum using 22 Gauge wire • 938 feet maximum using 18 Gauge wire • 1493 feet maximum using 16 Gauge wire • 2362 feet maximum using 14 Gauge wire IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 31: 2: Wiring Configurations

    Control Panel 5495 or 5499 SBUS Device supervised power limited Figure 4.10 Powering SBUS Devices From 5495 or 5499 NOTE: The earth ground jumper on the 5495/5499 must be removed in this configuration. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 32: Ra-100 Remote Annunciator Installation

    RA-100 using any of the mounting holes shown in Figure 4.13. Mounting Holes Mounting Holes Figure 4.13 Back Box Mounting Holes Remove the knockout holes as needed for wires. See Figure 4.14 for backbox knockout locations. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 33 The optional Model RA-100TG/TR Trim Ring Kit is available for use when surface mounting. Remove the desired knock outs. See Figure 4.14. To mount the back box, insert a single screw into the key shaped mounting hole. Do not tighten all the way. See Figure 4.17. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 34: 2: Ra-100 Connection To The Panel

    Place the bezel over the back box and tighten the set screws on the bezel. 4.5.2 RA-100 Connection to the Panel Connect the RA-100 to the panel as shown in Figure 4.19. supervised power-limited Figure 4.19 Model RA-100 Connection to the Panel IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 35: Ra-1000 Remote Annunciator Installation

    Control Panel Installation 4.6 RA-1000 Remote Annunciator Installation The optional Model RA-1000 Remote Annunciator, is shown in Figure 4.20. Up to 8 annunciators can be added to the IFP-75 System. Figure 4.20 Model RA-1000 Remote Annunciator, Front View RA-1000 installation involves the following steps.
  • Page 36: 1: Mounting The Ra-1000

    If an electrical box is used, the box must be 1-3/8” back from the face of the wall to accommodate the annunciator. Studs used with an elec- trical box must be two by fours (or larger). IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 37 Attach second set of wires to top of back box. Secure the wires behind this screw. Insert wires at an angle into the first holes past the sheet rock. Figure 4.24 Flush Mounting the Back Box IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 38: Ra-2000 Remote Annunciator Installation

    Use the DIP switches on the back of the RA-2000 to assign an SBUS ID# to the RA-2000 (see Section 4.11.1). The RA-2000 module must be added to the System through programming. JumpStart Auto-Programming will add the module automatically (see Section 8.1). IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 39: 1: Mounting The Ra-2000

    Wire the annunciator board to the main control panel. As described in Section 4.7.2. Attach the annunciator and door assembly to the back box as shown in Figure 4.29 using the supplied screws. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 40 Attach the door assembly to the back box using screws provided. After the SBUS wiring to the annunciator is complete, replace the electronic assembly in the back box. Place the bezel over the back box and tighten the set screws on the bezel. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 41: 2: Ra-2000 Connection To The Panel

    Add the module to the System. JumpStart will add the module automatically (see Section 8.1). You can also add it manually (see Section 8.2.2). • Select a name, if desired. • Select options for the printer and the output port. See below. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 42: 5880 Led Driver Module

    The 5880 can drive up to 40 LEDs and has one PZT controller. The 5880 also has eight inputs for dry contact monitor- ing. Up to 8 5880s can be added to the IFP-75 System. The following sub-sections describe hardware installation. Refer to Section 6 for pro- gramming information.
  • Page 43: 2: Facp Connection

    NOTE: The circuit connected to “Open Collector Output” (last pin on P1) must be current-limited so that no more than 100 mA of current is allowed to flow into the Open Collector Transistor. Figure 4.37 5880 Board Layout IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 44: 4: Dry Contact Wiring

    They do ot appear on board assembly. Note: 5865 switches follow the main FACP, no installation or programming required. 5865-4 Board Assembly 5865-3 Board Assembly Figure 4.39 5865-3 and 5865-4 Assembly (front view) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 45: 1: Facp Connection

    The 5865 ships with a set of zone description labels that can be inserted into the 5865 board assembly. These labels can be used in a type- writer or can be written on by hand. Slide the labels under the Plexiglas as shown in Figure 4.42. The LEDs will show through the label when illuminated. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 46: Configuring Modules

    ID# to the module. Figure 4.43 shows all possible DIP switch positions and their correlation to a numerical ID. For example, to select ID 2, place DIP switch 2 in the up position. Figure 4.43 Possible module addresses Refer to Section 8.2 to edit, add, delete, and view the Module List. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 47: Telephone Connection

    4.12 Telephone Connection Connect the telephone lines as shown in Figure 4.44. The Model 7860 phone cord is available from Honeywell for this purpose. A number of programmable options are available for customizing telephone lines. These options are described in Section 9.6.
  • Page 48: 2: Auxiliary Power Installation

    If AC power is off for more than 15 seconds, the auxiliary door holder power will be disconnected to conserve the battery backup. When AC power is restored, power is immediately restored to the door holder circuits. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 49: On-Board Relays (Conventional)

    To install one or two programmable relays, follow these steps. Wire Relay 1 and/or Relay 2 as needed for your application. See Figure 4.48 for the location of the relay terminals. Configure the relay through programming (see Section 8.2). IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 50: Remote Station Applications

    All wiring supervised. 4.7K A 5496 must 4.7K Example be used for Model 3158 NAC circuits Keltron Receiving #2 not used. Equipment To each ground Figure 4.49 Keltron 3158 Connection to Control Panel IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 51: 2: City Box Connection Using The 5220 Module

    It is not possible to reset the remote indication until you clear the condition and reset the control panel. Note: NAC Circuit 2 Used as an Example. Either NAC Circuit Can Be Used. Non-Supervised Non-Power Limited Figure 4.50 City Box Connection IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 52: 3: Nfpa 72 Polarity Reversal

    Map the group to activate non silenceable, constant on in response to a system general alarm, and to discuss in response to a system trouble. Intended for connection to a polarity reversal circuit of a remote station receiving unit having compatible rating. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 53: 4: Using An Mr-201/T Control Relay From Air Products

    Program the NAC circuit for non silence NAC circuit (see Section 8.5). NOTE: If you need to transmit supervisories or trouble conditions, additional relay modules must be added. Use the Relay 1 to transmit supervisory conditions. Use the trouble relay to transmit trouble conditions. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 54: 5: Transmitter Activated By Dry Contacts

    Remote Station Transmitter Module using end-of-line resistors (ELRs) with a value determined by the transmitter manu- facturer. Power is also provided by the Remote Station Transmitter Manufacturer. Refer to the Remote Station Transmitter Manufacturer’s manual for details. Figure 4.54 IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 55: Section 5: Networking Common Communicator List

    5.1.2 Wiring Options to Connect Networked Panels A networked site is a logical group of IFP-75 panels that behave as though the logical group is one large control panel. Each building is referred to as a “site.” All panels in a site operate as a single panel. The control functions like reset, silence and alarm activation operate across the entire site.
  • Page 56: 1: Fiber Loop Modules

    The SK-NIC is designed to mount on the bracket inside the accessory cabinet. Use the following steps to properly mount the SK-NIC-KIT. Place the SK-NIC on the mounting bracket. Use the 6-pin cable included with SK-NIC to connect the IFP-75 to the SK-NIC. The 6-pin cable must be run in conduit. See Figure 5.1. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 57 FIRST CONTROL PANEL SK-NIC Figure 5.6 Twisted-Pair Wiring Configuration Fiber-Optic Multi-Mode Wiring between Multiple Panels Fiber-optic cable between multiple panels is shown in Figure 5.7. Class X is shown with a dotted line. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 58 Fiber In Class X PORT 2 Wiring NEXT CONTROL Fiber Out PANEL SK-NIC PORT 1 Fiber In FIRST PORT 2 CONTROL PANEL Fiber Out SK-NIC PORT 1 Figure 5.8 Fiber-Optic Wiring Single-Mode Example IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 59: Setting The Panel Id For Each Panel Network

    Use the DIP switch positions 1 through 5 to set the Network ID for each panel. See Figure 5.10 below for possible DIP switch settings. Figure 5.10 Network ID Settings IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 60: Section 6: Network Management

    This Section of the manual describes how to program the network options using the built-in annunciator. All options described in this Section can be programmed using the HFSS Honeywell Fire Software Suite. To edit the site assignments, the HFSS must be used.
  • Page 61: 4: Computer Access

    6.2.4 Computer Access The Installer located at the panel site can initiate the communications between the panel and a computer running the HFSS Honeywell Fire Software Suite (see also Section 10.5). In order for this communication to function properly, both the computer (running the software) and the control panel must have matching computer access numbers and computer codes.
  • Page 62: 6: Communicator Options

    The Receiver Numbers are populated based on the Panel Number and audited to allow only the 4 appropriate receivers. See Appendix C for a list of Receiver Numbers. Table 6.2 lists the available Format choices: Reporting Format Contact ID SIA500 SIA8 SIA20 Ethernet Cellular eVance UNUSED Table 6.2 Receiver Configuration IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 63: Sync Network Options

    Select 8 to access the Sync Network Options. Select from which panel to source the options. With the line selected Line 1 scrolls to show the date Scroll down to show checksum Figure 6.2 SYNC Network Options IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 64: Network Management Quick Reference

    Disable/Enable Buffer Point Status Set SLC Device Address SLC Single Device Locator SLC Multi-Device Locator I/O Point Control Event History Set Time & Date Network Diagnostics Table 6.3 Network Management Quick Reference List IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 65 Report Troubles Report Events by Point Primary Receiver Primary Account Test Primary Account Secondary Receiver Secondary Account Test Secondary Account Sync Network See Section 6.3 Options Table 6.3 Network Management Quick Reference List (Continued) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 66: Section 7: Idp, Sk, Sd And Swift Slc Device Installation

    Rate-of-rise thermal detector with 135° fixed temperature. White or Ivory I56-6533 IDP-HEAT-HT-W / IV Fixed high temperature thermal detector (190°F). White or Ivory I56-6533 Color Guide: -IV = Ivory color, -BL = Black, -WH = White, -WHITE-White Table 7.1 IDP SLC Devices IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 67: List Of Sk Slc Devices

    Rate-of-rise thermal detector with 135° fixed temperature. White I56-6529-00 IDP-HEAT-HT-W Fixed high temperature thermal detector (190°F). White I56-6529-00 Color Guide: -IV = Ivory color, -BL = Black, -WH = White, -WHITE-White Table 7.2 SK SLC Devices IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 68: List Of Sd Slc Devices

    SD500-SDM Addressable smoke detector module. I56-3546 SD500-LIM Line isolator module. Fits in a double gang box. I56-3543 SD505-DTS-K Remote test switch & LED indicator for the SD505-DUCTR 1700-09882 Table 7.3 SD SLC Devices IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 69: Swift Wireless Slc Devices

    7.4 SWIFT Wireless SLC Devices The WIDP-WGI Wireless Gateway acts as a bridge between a group of wireless fire devices and an SLC loop on the IFP-75. It is powered by the SLC loop or by a regulated, external 24VDC UL-listed power supply. The available wireless devices include a photo detector, a photo/heat detector, a fixed-temperature heat detector, a rate-of-rise detector, and a monitor module.
  • Page 70: 3: Wiring Slc In Class A And Class X Configuration

    NOTE 3: No t-taps allowed on the Class A and Class X SLC loops. Note: SD -Device max. Loop Resistance = 50 Ohms IDP/SK -Device max. Loop Resistance = 40 Ohms Figure 7.3 Class A SLC Configuration IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 71: Addressing Idpslc Devices

    Wire the device bases as shown in Figure 7.5. Set the address for each device as described in Section Figure 7.9. Figure 7.5 Heat or Smoke Detector Connection to the FACP (Class B) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 72: Addressing Sd Slc Devices

    For example, to select address 3, place DIP switches 1 and 2 in the up position. The range of valid addresses is 1-50. The zero, 0, is an invalid address. NOTE: Any device addressed over 50 will not be recognized by the panel. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 73: Wiring The Widp-Wgi

    7.10.1 SLC Connections The WIDP-WGI Wireless Gateway acts as a bridge between a group of wireless fire devices and an SLC loop on the IFP-75. It is powered by the SLC loops or by a regulated, external 24 VDC UL listed power supply. For details about wireless devices, system setup, and operation, see the SWIFT Smart Wireless Integrated Fire Technology Instruction Manual P/N, P/N: LS10036-000FH-E.
  • Page 74: Section 8: Programming Overview

    ENTER to accept. A series of messages display for the next several seconds. JumpStart scans the SLC loops for the devices. This process can take several minutes, depending on the number of devices attached. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 75: Mapping Overview

    Optional Input Zones. Special Sys Evts Figure 8.1 Mapping Overview NOTE: Mapping cannot be programmed through the annunciators. It can only be programmed through the HFSS Honeywell Fire Software Suite. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 76: 1: Input Point Mapping

    Figure 8.3 is a simple example showing how to assign notification and relay output circuits to groups. For an example of a simple floor above/floor below application, see Figure 8.5. Figure 8.3 Assigning Output Circuits to Groups (Example) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 77: 3: Event Mapping

    F2 Key Active Advisory Ground Fault Trouble F3 Key Active Phone Line Trouble F4 Key Active Reporting Account Trouble Table 8.2 Event Types Figure 8.4 Example of Zone Events Mapped to Output Groups and Patterns IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 78 Zone 2 Show Room Floor 2 Show Room Floor 2 Zone 1 Show Zone 1 Room Show Floor 1 Room Floor 1 Figure 8.5 Example of Zone Events Mapped to Output Groups and Patterns IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 79: 4: Mapping Led Points

    8.3 Programming Using the HFSS Software Suite You can use the HFSS Honeywell Fire Software Suite to program the control panel on-site (the personnel will need to be on-site during the upload or download process). The HFSS is a software package that lets you easily program the control panel using a Windows-based com- puter.
  • Page 80: 1: Entering / Exiting The Program Menu

    Select from a scrolling list. Use the up and down arrow to move through a list of available options. When the option you want to select is displayed, press ENTER. Table 8.3 Selecting the Options IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 81: Programming Menu Quick Reference

    Group Properties Dynamic Act/Template Group 00-23 Section 9.4.1 Override Cadence View Group Points Select Group Edit OPG Template Select template Modify name and which OPG’s are in template Table 8.4 Programming Quick Reference List IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 82 Select Module NON-LATCH Figure 9.5.1 1,2,3 SWITCH LATCH ZONE AUX2 NON-LATCH LATCH SYSTEM AUX1 NON-LATCH LATCH SYSTEM AUX2 NON-LATCH DETECTOR LATCH FIRE TAMPER NON-LATCH MANUAL RELEASE INTERLOCK Table 8.4 Programming Quick Reference List (Continued) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 83 Select Sensor DETECTOR Section 9.5.1 SDR BAS RLY BAS ACCLIMATE I-SdrBa (Intelligent Sounder Base) No Accessory SDR base RLY base HEAT HT I-SdrBa (Intelligent Sounder Base) Table 8.4 Programming Quick Reference List (Continued) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 84 Same as W-Detector Section 9.5.3 UNUSED Internal Power and Point # NOTIF OUTPUT Select Group, External Power B NOTIF Supervised Edit Name CONTROL Yes or No CIRCUIT Table 8.4 Programming Quick Reference List (Continued) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 85 Latch CO 4 WIRE SUP Non-Latch *Only applicable for RPS-1000 UNUSED Point 5880/5865 Enter Point # NOTIF OUTPUT Select Group (cont.) NOTIF Edit Name CONTROL CIRCUIT Table 8.4 Programming Quick Reference List (Continued) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 86 Night Start Enter time *6:00PM Days of the Week Select days *-MTWTF- Holidays 1 to 18 Enter dates *01/01, 07/04, Section 9.6.3 Holiday Days 12/24, 12/25 Table 8.4 Programming Quick Reference List (Continued) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 87 2. Available with SLC Family as SK. Family as IDP. 3 Available with SLC Family as SD. 4. Requires wireless gateway. 5. AUX SYNC setting is only applicable for the B200S /IV Sounder Base. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 88: Section 9: Programming

    This Section of the manual describes how to manually program the control panel from the built-in annunciator. Each subsection describes these Menu options. All options described in this Section can be performed using the HFSS Honeywell Fire Software Suite. NOTE: Before any customized programming is done, JumpStart Auto-Programming should be run first. After JumpStart is run, thoroughly test the System.
  • Page 89: 2: Adding A Module

    NOTE: See Appendix B for information to edit names. Edit Zone Properties Zone properties consist of, alarm delay characteristics, and heat detector sensitivity. Do steps 1 through 5 of Section 9.3.1. Press 2 to edit the properties of the selected zone. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 90 Alarm Delay Characteristics The programmed zone type is provided for user reference only. To modify the zone type, use the HFSS Honeywell Fire Software Suite. Table 9.2 list the delay choices and a description of each type. Then, press ENTER.
  • Page 91 See Appendix D.CO Single and Multi-Station Cadence (choose from Cadence Patterns 00 to 02, 23 for IDP or SK devices) For Local Zone, (choose Y or N, for Yes or No). NOTE: The B200S-WH / IV Sounder base provides the recommended CO cadence pattern. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 92: 2: View Zone Points

    The Edit Group Menu allows you to select the options for each Goup for the following items: • Template Override: Y or N. • If you select Yes to access the Template Override, the Template Override Cadence is available. • See Section 9.4.3 for more information. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 93: 2: View Group Points

    To select the type of device, press the up or down arrows. Refer to Table 9.4 under the column heading “Type Selection” for a list of choices. Type Function Latching Option Comments Selection UNUSED PHOTO DETECTOR Table 9.4 Point Programming for Internal SLC Module IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 94 ALRM CO/ALRM FIRE DETECTOR SUP CO/ALRM FIRE ALRM CO/SUP FIRE SUP CO/SUP FIRE Latching Detectors programmed as Supervisory can be latching or non-latching. Non Latching Table 9.4 Point Programming for Internal SLC Module (Continued) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 95 See Section 4.13.2 (subsection, Door Holder Power) to learn how this option operates. Table 9.4 Point Programming for Internal SLC Module (Continued) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 96: 2: Point Programming For The Internal Or External Power Module

    To select the Group, press the up or down arrows, then, press ENTER. 10. To edit the Point Name, press the right arrow to skip the Point Name Edit. See Section 9.5. 11. Repeat Steps 1 through 10 for all circuits. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 97 Latching or Non-latching used for Class A, 4-wire CO Supervisory detectors Select Group Group or Zone selection will appear depending on the type selected Edit Name Edit name. See Section 9.5.3 *Only applicable on RPS-1000 Table 9.5 Menu Choices for Internal/External Power Modules IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 98: 3: Point Programming For 5880 And 5865 Modules

    • 4 hour NOTE: AM and PM are only available if the panel “Clock Options” are set to AMPM mode. Otherwise, the clock is set in the military time and you cannot select AMPM. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 99 Number of Answer Rings This option is used in conjunction with the HFSS Honeywell Fire Software Suite. Use the option to determine the number of rings before the panel answers a call from the computer. The Range is 00-15 rings. This option is factory-programmed as 06 rings, which should be compat- ible for most installations, where the answering machine bypass feature is used.
  • Page 100 Answering Machine Bypass This option is used in conjunction with the HFSS Honeywell Fire Software Suite. This feature ensures that an answering machine will not interfere with communication between the panel and the computer. If an answering machine is used at the panel site, enable this feature; if an answering machine is not used, disable the feature.
  • Page 101: 2: Daytime/Nighttime Sensitivity

    Enter the month of the Holiday, then press ENTER. Enter the day of the month for the Holiday, then press ENTER. Repeat Steps 6 and 7 to add any remaining Holidays you want to program. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 102: 4: Time Options

    The System resound time period can be modified from the default value 24 hours to 4 hours. This setting adjusts when the FACP will auto- matically resound events after being silenced. Set this option to 4 hours when using SWIFT devices. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 103: 5: Miscellaneous Options

    To select each character of a word, press the up or down arrow. Then, press the right arrow key to move to the next character. After you enter the word or the sentence, press ENTER to move the cursor to line two of the custom banner. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 104: 8: Slc Family

    JumpStart Auto-Programming 9.6.8 SLC Family The IFP-75supports SD, SK Series, or Intelligent Device Protocol (IDP)SLC devices. You must configure the IFP-75 to accept the protocol of the devices you are installingYou cannot mix SLC devices of different protocols. Enter the Installer Code.
  • Page 105: Section 10: System Operation

    This feature allows the user to press the ACK key and display the oldest un-acknowledged event in the System. If you press the ACK key again, it will acknowledge the event. Then, it will automatically display the next oldest un-acknowledged event (and you do not need to press the arrow keys). IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 106: Menu System

    Disable / Enable Point Press 7 to Disable /Enable Point. Choose the Module. Use the up or down arrow key to choose Point and press ENTER. Press the right arrow key to disable or enable Point. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 107: 3: View Event History

    (newest) 500 events from every panel in the site will be displayed. When using the HFSS Honeywell Fire Software Suite, all 1,000 events from every panel in the network will be uploaded.
  • Page 108: 7: Conduct A Communicator Test

    From the Main Menu, press 2 to access the Point Functions. Press 2 to access the Point Status. Select the module where the point you want to check is located. Enter the number of the point you want to check and press ENTER. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 109: 12: View Status Of A Point

    A screen similar to those shown in Figure 10.3 will display. Figure 10.3 Checking Detector Sensitivity Compliance You can print the Detector Status by uploading the Detector Status to the HFSS Honeywell Fire Software Suite. Then, print the Detector Status from the HFSS Honeywell Fire Software Suite.
  • Page 110: Operation Mode Behavior

    The 3 and 4th line will show the status of which event types are active for each system (fire and CO). The Auto Display Event activates after two minutes of the annunciator inactivity. Figure 10.4 Highest Priority Event Display Figure 10.5 Event Types Screen This Screen will display when more than 3 Event Types are active. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 111: Panel Operation Mode Conditions

    (or activate the key) to restore the panel to normal. CO detector goes into alarm. If more than 3 categories are active at a single time, the screen will display as shown. Table 10.3 Panel Mode Operation Conditions IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 112 Once the trouble condition has been fixed, the system will restore itself automatically. A trouble condition with a CO detector Table 10.3 Panel Mode Operation Conditions (Continued) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 113: 1: Multi-Site Annunciator And Multi-Site User Access

    Zone operation requires an Interlock switch input in the System. The Single Interlock does not. An Interlock switch is typically a dry-contact pressure switch. NOTE 1: These releasing functions can only be done if the System has a 5496 Intelligent Power Module ncluded. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 114: 1: Single Interlock Zone Releasing

    If any single addressable detector is activated, the “Pre-Alert” output will activate and the “Pre-Alarm” output will deactivate. This alerts the user that the initial stages required for a release condition are present. (Also refer to Table 10.5.) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 115: 2: Double Interlock Zone Releasing

    When these conditions are met, the “Release” and “General Alarm” outputs will activate, and the “Alert” output will deactivate. Inputs Output Results 1st Addressable Detector 2nd Addressable Detector Manual Release Station Interlock/Pressure Switch Normal Pre-Alert Pre-Alert and General Alarm Release and General Alarm Table 10.6 Double Lock Zone Operation IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 116: Smoke Alarm Verification

    Disable/Enable Point or use the I/O Point Control to disable Output Groups or Individual Points or activate Individual Points. After you finished disabling or activating the Points/Output Groups, enter the F-Key Recording Menu again and select the ‘End F-KEY Recording’ option. The panel will return to the Idle screen. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 117: Section 11: Reporting

    F2 Mapping Inhibited Restoral 2002 FJNN002002 F3 Mapping Inhibited 2003 FTNN002003 F3 Mapping Inhibited Restoral 2003 FJNN002003 F4 Mapping Inhibited 2004 FTNN002004 F4 Mapping Inhibited Restoral 2004 FJNN002004 Fire Reset ORNN000000 Table 11.2 Reporting Formats Table IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 118 SBUS expander trouble restore Exp. ID ERNNXX0000 Exp. ID SLC class A supervision trouble Exp. ID ETNNXX0000 Exp. ID SLC class A supervision trouble restore Exp. ID ERNNXX0000 Exp. ID Table 11.2 Reporting Formats Table (Continued) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 119 Emergency # QHNN0E0000 220 + Emer- gency # Manual pull switch alarm Zone # FANN000ZZZ Zone # Manual pull switch alarm restore Zone # FHNN000ZZZ Zone # Table 11.2 Reporting Formats Table (Continued) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 120 Zone # SJNN000ZZZ Zone # Zone-based AUX1 switch alarm Zone # + 1000 UANN001ZZZ Zone # Zone-based AUX1 switch alarm restore Zone # + 1000 UHNN001ZZZ Zone # Table 11.2 Reporting Formats Table (Continued) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 121 ECS Alarm # Point Enabled pi Exp. ID QU Point # QUNNXXPPPP Exp. ID Point # ECS Supervisory/Tamper Alarm pi Exp. ID QS Point # QSNNXXPPPP Exp. ID Point # Table 11.2 Reporting Formats Table (Continued) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 122 Exp. ID FT Point # FTNNXXPPPP Exp. ID Point # Manual pull switch trouble restore pi Exp. ID FJ Point # FJNNXXPPPP Exp. ID Point # Table 11.2 Reporting Formats Table (Continued) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 123 System-based AUX2 switch enabled pi Exp. ID UU Point # UUNNXXPPPP Exp. ID Point # System-based AUX2 switch trouble pi Exp. ID UT Point # UTNNXXPPPP Exp. ID Point # Table 11.2 Reporting Formats Table (Continued) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 124 Zone-based AUX2 switch trouble restore pi Exp. ID UJ Point # UJNNXXPPPP Exp. ID Point # System-based Wireless Gateway pi Exp. ID UT Point # UTNNXXPPPP Exp. ID Point # Trouble Table 11.2 Reporting Formats Table (Continued) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 125: Sia / Ifp-75 Panels Pi Modifier Reporting

    Fire Trouble Zone EE-Z Fire Trouble-Nac Point Nac Circuit EE-ZZ /EE-Z pi98/FT7 Z=Pt. # Fire Trouble-Nac Zone Nac Circuit EE-ZZZ FT400 ZZZ=OPG# Table 11.3 :SIA- IFP-75 Panels - PI Modifier Reporting Examples IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 126: Sia- Ifp-75 Panel Communicator

    Fire Trouble Zone EE-PP-MM-ZZZZ FT22970001 MM = 00 Fire Trouble-NAC Point NAC Circuit 7 EE-PP-MM-ZZZZ FT22980007 ZZZZ=Pt. # Fire Trouble-NAC Zone NAC Circuit 7 EE-PP-MM-ZZZZ FT22980007 ZZZZ=OPG # Table 11.4 SIA Reporting Examples IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 127: Section 12: Testing And Troubleshooting

    • All active Notification Appliances sound. Measure the battery voltage while the Notification Appliances are sounding. Replace any battery with terminal voltage less than 85% of rat- ing. Reapply the AC power and RESET the System. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 128: 2: Event History

    Select the SLC loop. Enter up to 8 SLC addresses for the devices you wish to locate. The LEDs on the selected devices will start flashing. Press the left arrow key to exit SLC multi-locater function. IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 129: 3: I/O Point Control

    NAC 1 + NAC 2 - NAC 2 + SBUS - SBUS + SBUS A SBUS B SLC IN - SLC IN + SLC OUT - SLC OUT + Table 12.2 Earth Fault Resistance IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 130: Section 13: Installation Records

    Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Table 13.2 IDP/SK Detector Installation Record IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 131 Description Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Table 13.2 IDP/SK Detector Installation Record (Continued) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 132: Appendix A: Compatible Devices

    Strobe S241575-FC Strobe S2430-FC Strobe 130-3117C Mini Horn 130-3147C Mini Horn BLV-6 Vibrating Bell BLV-10 Vibrating Bell BLVCH Vibrating Chime H12/24-FC Horn H12/24W-FC Horn H12/24K-FC Horn HC12/24-FC Horn Table A.1 Compatible Notification Appliances IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 133 P24110-FC Horn/Strobe P24110W-FC Horn/Strobe P24110K-FC Horn/Strobe S2430W-FC Strobe S2430K-FC Strobe S2475-FC Strobe S2475W-FC Strobe S2475K-FC Strobe S24110-FC Strobe S24110W-FC Strobe S24110K-FC Strobe Horn Federal Signal VALS Horn/Strobe Table A.1 Compatible Notification Appliances (Continued) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 134 Multi Candella Strobe GESR-24 Multi Candella Strobe GEH-24 Horn ST24-30 Strobe ST24-60 Strobe ST24-75 Strobe ST24-110 Strobe ST24-1575 Strobe WGEC24-75W Weatherproof Horn/Strobe WGES24-75W Weatherproof Strobe WGMS-24-X Horn/Strobe Table A.1 Compatible Notification Appliances (Continued) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 135 2-Wire Horn/Strobe High Candela P2RK 2-Wire Horn/Strobe PC2RK 2-Wire Horn/Strobe P2RHK 2-Wire Horn/Strobe High Candela PC2RHK 2-Wire Horn/Strobe High Candela 4-Wire Horn/Strobe PC4R 4-Wire Horn/Strobe P4RH 4-Wire Horn/Strobe High Candela Table A.1 Compatible Notification Appliances (Continued) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 136 Strobe WHT Ceil CLR Lens 4x4 SGRL Strobe Red Wall 2x4 SGWL Strobe White Wall 2x4 P2RH-LF 2-Wire Low Frequency Sounder Strobe P2WH-LF 2-Wire Low Frequency Sounder Strobe HR-LF Low Frequency Sounder Table A.1 Compatible Notification Appliances (Continued) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 137 Horn/Strobe AS-24MCWH Horn/Strobe ASWP-2475W Horn/Strobe Weatherproof ASWP-2475C Horn/Strobe Weatherproof ASWP-24MCWH Horn/Strobe ASWP-24MCCH Horn/Strobe CH-70 Chime CH-90 Chime CH70-241575W Chime/Strobe CH70-24MCW Chime/Strobe CH70-24MCWH Chime/Strobe CH90-24MCC Chime/Strobe CH90-24MCCH Chime/Strobe Table A.1 Compatible Notification Appliances (Continued) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 138 Horn/Strobe ZNS-24MCCH Horn/Strobe RSS-121575W Strobe RSS-241575W Strobe RSS-24MCC Strobe RSS-24MCCR Strobe RSS-24MCCH Strobe RSS-24MCCHR Strobe RSS-24MCW Strobe RSS-24MCWH Strobe RSSP-121575W Strobe RSSP-241575W Strobe RSSR-2415W Strobe RSSR-2415C Strobe Table A.1 Compatible Notification Appliances (Continued) IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 139: A.2: Two-Wire Smoke Detectors

    • Do not mix detectors of different models unless the system is specifically intended to be installed in that configuration. • Control unit Smoke Reset Time must be programmed for a number greater than or equal to the maximum reset time of the smoke detector IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 140 20 / loop 2400AT 20 / loop 2400TH 20 / loop 2451 (B401B) 20 / loop 2451DH (DH 400) 20 / loop 2451TH (B401B) 20 / loop Table A.2 Compatible Two-Wire Smoke Detectors IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 141: A.3: Four Wire Smoke Detectors/Devices (Ul Listed)

    Loop Test/Maintenance Mod. System Sensor RRS-MOD Reversing Relay/Sync Module System Sensor 6424 Projected Beam 28.4 System Sensor Beam 1224(S) Projected Beam 38.5 * Contact manufacturer for current draws Table A.3 Compatible Four-Wire Smoke Detectors IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 142: A.4: Door Holders (Ul Listed)

    Wall High-Fidelity Speaker Strobe, High Candela, Plain, Red SPSCWH-P Ceiling High-Fidelity Speaker Strobe, High Candela, Plain, White SPSW-ALERT Wall High-Fidelity Speaker Strobe, Amber Lens, ALERT, White SPSW-CLR-ALERT Wall High-Fidelity Speaker Strobe, Clear Lens, ALERT, White Table A.6 Compatible Low-Frequency Speakers IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 143: A.7: Compatible 520Hz Low Frequency Bases

    Model Number Description B200S-LF-WH / IV Low Frequency Intelligent Sounder Base. White or Ivory B200SR-LF-WH / IV Low Frequency Intelligent Sounder Base. White or Ivory IV = Ivory color Table A.7 Compatible Low-Frequency Bases IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 144: Appendix B: Editing Text Using The Built-In Programmer

    NOTE: After three seconds of no change, the System will automatically accept the letter. Also, if you press the next number, the System will automatically accept previous choice. Figure B.1 Edit Name Example IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 145: Appendix C: Expanded Receiver/Panel Relationship

    The available Receiver Number will correspond with the panel number you entered. The Receiver Numbers are populated based on the panel number and they are audited to allow only the 4 appropriate receivers. See Section 6.2.6. Panel Available Receiver Numbers Table C.1 Receiver/Panel Relationship IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 146: Appendix D: Cadence Patterns

    Appendix D: Cadence Patterns Figure D.1 shows the Cadence Patterns available for use with the control panel. Figure D.1 Cadence Patterns IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 147: Appendix E: Panel Security

    Ensure the Ethernet cable is removed from the FACP when not being utilized for configuration or for reporting purposes. Security and Data Protection Communication Security - Level 1 Stored Data Security - Level 0 Physical Security - Level 1 Access Control Security - Level 1 IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 148 Notes IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 149 Model IFP-75 Basic Operating Instructions IFP-75 These Instructions must be framed and displayed next to the panel in accordance with NFPA 72 fire code for Local Protected Fire Alarm Systems. Test the System in accordance to NFPA 72. Operation Task to Perform Silence Alarms and Press SILENCE then enter a code if prompted.
  • Page 151 Return Material Authorization form. The replacement part shall come from Manufacturer's stock and may be new or refurbished. THE FOREGOING IS DISTRIBUTOR'S SOLE AND EXCLUSIVE REMEDY IN THE EVENT OF A WARRANTY CLAIM. Warn-HL-08-2009.fm IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021...
  • Page 152 Honeywell Fire Systems 12 Clintonville Road Northford, CT 06472-1610 203-484-7161 LS10147-001SK-E | D | 06-21 www.farenhyt.com ©2021 Honeywell International Inc.

This manual is also suitable for:

Farenhyt seriesIfp-75hv

Table of Contents

Save PDF