If the spine module RS-232 port is connected to a terminal emulation program, the user will be able to
Note
view the switch boot process. Be certain to use a null-modem/crossover serial cable for the console port.
The settings for the terminal emulation device should be:
Figure 2-16 SFS 7024 RS-232 Connector
Verify the IP address with the command line interface (CLI) command showChassisIpAddr
Step 3
command. The system returns the information similar to the following:
Changing the SFS 7024 IP Address and Default Gateway via the CLI
Note
The following tasks must be performed for both the upper and lower hemispheres of the SFS 7024
The CLI can be accessed via Telnet, SSH, or through the SFS 7024 RS232 serial ports.
Connect null-modem/crossover serial cables to the RS-232 ports of the SFS 7024. If using a terminal
Step 1
emulation device, the settings should be:
Cisco SFS 7024 InfiniBand Server Switch Hardware Users Guide
30
8 data bits
–
–
no parity bits
–
1 stop bit
–
56K baud
Use VT100 emulation.
–
Flow control = XON/XOFF
–
Spine 3 (Unmanaged)
Spine 2 (Managed)
Spine 1 (Managed)
S PS
PS
5
Chassis IP Address:
8 data bits
–
no parity bits
–
1 stop bit
–
PS
PS
4
3
2
192.168.100.9
Net mask: 0xffffff00
Fan
3
Fan
PS
1
1
Chapter
.
OL-8794-04