Commissioning
The units are supplied with the factory default settings, shown below, which render commissioning, apart from
zoning, unnecessary in many applications. To allocate to zone(s), effected via the MLS Bus signals, and
make use of the programmable settings, an infrared commissioning tool (QuickSet Pro) is required.
A ten-second time delay is selectable to aid commissioning.
Sensitivity to Movement
While the factory settings will be correct for many applications, the sensitivity can be adjusted if required.
ON Sensitivity: This sets the detector's range when the lights are ON. Choose setting from 1-100 where 1 is
lowest and 100 is maximum. (Note: Choose the lowest level possible to give adequate detection.)
OFF Sensitivity: This sets the detector's range when the lights are OFF. Choose % setting from 10% to
100% where 10% = 10% of ON Sensitivity and 100% = same as ON Sensitivity. This is an approximation and
should be tested on site during commissioning.
Like all programmable parameters, the sensitivity settings will be retained in the event of a power failure and
can be re-programmed any number of times.
Factory Default Settings
These are the settings to which the units have been programmed before they leave the factory.
Parameter
Power Up
Response
Off Delay
On Sensitivity
Off Sensitivity
Bus Connect
1st Zone
2nd Zone
3rd Zone
4th Zone
Corridor 1 Begin/End
Corridor 2 Begin/End
Global 1 Rx
Global 2 Rx
Manual I/P
Start Lamps
Entry Scene
Lamp Max
Dimming
Fade to Off
When Vacant
Bright-Out
Pcell Rly
Set-Point Low
Set-Point High
Options
On/Off
Auto, Manual/Bus, Manual only
1min-96hrs, 10 secs (walk test), Disabled
0-100
100-10% in 10% increments
Yes/No
Address 1-100, -- (no zone), Comn 1-3
Address 1-100, --, Comn 1-3
Address 1-100, --, Comn 1-3
Address 1-100, --, Comn 1-3
00-100, --, Building
00-100, --, Building
Yes/No
Yes/No
Local/Share
Max/Min
Scenes 1-6
100-10%
Regulate 100-50%
No/Yes
Off, 9 Exit Scenes (3 options x 3 durations)
No/Yes
Disabled/Passive/Active
0-1023
0-1023
Default
Setting
ON
AUTO
20 min
19
100%
Yes
--
--
--
--
--
--
NO
NO
LOCAL
MAX
01
100%
100%
NO
OFF
NO
Disabled
766
1022
4
Options
Each of these settings
can be re-programmed,
if desired, by use of the
infrared programming
tool QuickSet Pro.
- Manual Input is only
available via the
Wireless OneSwitch
facility of the
MLS2500DWL(F) and
MLS2500DALIWL(F).
See Application Note
AN4021 for further
information