Permanent process image for BackgroundTask (I/O
variables)
Additional configurable process image for each cyclic
task (I/O variables)
Address space for each PROFIBUS DP station
SINAMICS Integrated (PROFIBUS Integrated) address
space
Address space for each PROFINET device
Maximum consistency range
Onboard PROFINET interface X150
Logical address space: Logical addresses can be assigned in STEP 7 within this space.
Physical address space: Address space with assigned data.
The address space contains all the logical addresses, i.e. also diagnostic addresses, I-device, etc.
Number of slaves/devices
Table 5-11
Maximum number of slaves per PROFIBUS interface 64
Maximum number of devices for PROFINET
5.4.3
Onboard I/Os
Digital inputs
Table 5-12
Number of inputs
Input voltage
•
•
•
Electrical isolation
Current consumption typical at 1 signal level
Input delay, typical (hardware)
•
•
SIMOTION D410-2
Equipment Manual, 07/2021, A5E33446720B
For controller-controller direct data exchange 254 bytes
For I-device
Number of slaves/devices
Technical data for digital inputs
Rated value
For signal "1"
For signal "0"
2)
1)
Signal "0" → "1"
Signal "1" → "0"
5.4 Interfaces and performance features
64 bytes
yes
244 Byte
512 Byte
1400 Byte
1024 bytes (as of V4.4)
254 bytes (< V4.4)
64
5
•
24 VDC
•
15 ... 30 V
•
-3 ... +5 V
Yes (via optocoupler)
3.5 mA at 24 V
5 mA at 24 V
3)
•
50 μs
•
150 μs
Technical data
87