hit counter script
Download Print this page

Honeywell F57A Original Manual page 2

Flush-mount commercial electronic air cleaner
Hide thumbs Also See for F57A:

Advertisement

F57A,B FLUSH-MOUNT COMMERCIAL ELECTRONIC AIR CLEANER
SPECIFICATIONS
IMPORTANT
The specifications given in this publication do not
include normal manufacturing tolerances. There-
fore, this unit may not exactly match the listed
specifications. This product is tested and calibrated
under closely controlled conditions, and some
minor differences in performance can be expected
if those conditions are changed.
Models:
F57A Flush-Mount Commercial Electronic Air Cleaner:
contains two FC37B heavy duty commercial cells, power
supply assembly, prefilter, inlet-outlet grille, power and
speed control switch, performance selection switch, col-
lector test button, 3-speed motor driven fan, interlock
switch for the access grille, vinyl trim flanges, exhaust
air vent and LED indication of system operation.
F57B Flush-Mount Commercial Electronic Air Cleaner:
same as F57A, except with only one FC37B heavy duty
commercial cell.
Product
Voltage/
Code
Frequency
F57A1093
120V/60 Hz
F57A1101
220-240V/
50 Hz
F57A1101RC
F57B1067
120V/60 Hz
F57B1075
220-240V/
50 Hz
F57B1075RC
Color: Off-white.
Electrical Ratings: Voltage and Frequency: 120 Va.c.,
60 Hz; 220–240 Va.c., 50 Hz.
Current and Power Consumption:
120 Va.c., 60 Hz 220–240 Va.c., 50 Hz
Fan
Setting
A
F57A HI
3.9
315
MED
3.2
300
LOW
2.4
200
F57B HI
4.3
255
MED
2.1
185
LOW
1.2
85
68-0083—07
Rated Air
Remote
Volume
Control
875 CFM
3
(1500 m
/hr)
460 CFM
3
(780 m
/hr)
W
A
W
1.8
315
1.4
250
1.2
205
1.9
275
1.0
150
0.7
100
Air Flow Capacity:
120 Va.c., 60 Hz
Fan
Setting
cfm
F57A HI
1030
MED
690
LOW
555
F57B HI
485
MED
280
LOW
175
Efficiency:
Up to 95% efficiency using the Dust Spot Method measur-
ing atmospheric dust, according to the American Soci-
ety of Heating, Refrigeration, and Air Conditioning
Engineers (ASHRAE) Standard 52.1-92.
Motor:
F57A: 1/12 hp; sealed ball bearing.
F57B: 1/10 hp; sealed ball bearing.
Motor lubrication is not required.
Ambient Temperature Rating:
Shipping and Storage: minus 20°F to plus 150° F
(minus 29° C to plus 66° C).
Operating: this equipment is intended for use at ambient
temperatures which are usually not higher than 77° F
(25° C) but occasionally may be as high as 104° F
(40° C) for brief periods.
Dimensions:
See Fig. 1 and 2 for dimensions.
Shipping and Installation Weight:
Heavy duty commercial
cell (each)
Shipping weight
Installed weight
Approvals:
Underwriters Laboratories Inc. Listed: File no. E30954,
Guide no. AGGZ.
Replacement Parts and Accessories:
See "Parts List" on page 19.
2
220–240 Va.c., 50 Hz
3
3
m
/min
cfm
m
29
875
25
20
730
21
16
640
18
14
460
13
8
375
11
5
260
7
F57A
F57B
l b
kg
l b
9.5
4.3
9.5
106.0 48.1
64.0
83.0
37.6
54.0
/min
kg
4.3
29.0
24.5

Advertisement

loading