13.3 Setup Menu Set
•
Push simultaneously L/R and F for few seconds to access to the menu (Nenu flashing).
Select by arrows
•
Select by arrows
•
You have access to the parameter on Set menu.
•
Select by arrows
•
If the parameter is Write/Read (W/R) press F (parameter flashing) then select by
•
arrows
UP and DOWN the required velue, press F to set the new value.
Push simultaneously L/R and F for few seconds to Exit from the menu
•
Set Firing type:
Parameter
Parameter
Display
Name
Φιρ
Fir
Sample Values and Note
4= Phase Angle
20 = Soft Start + Phase Angle
35=Delay Triggering + Burst Firing
Ramp Up Settings:
This parameter have two functions: if the firing mode is Phase Angle Time to reach the full angle of
firing. The Unit starts in phase angle mode with a ramp starting from zero up to full voltage in a
presetted and Adjustable time.The time is setted by this parameter
Parameter
Parameter
Display
Name
ρΠ_υ
rP_u
Sample Values and Note
Only with Fir = Phase Angle
Set HB sensitivity:
This parameter defines the threshold of resistance that activates the HB alarm
This value is in percentage respect the nominal resistance load value
Parameter
Parameter
Display
Name
Ηβ_σ
Hb_S
Set HB Delay:
Parameter
Parameter
Display
Name
Ηβ_δ
Hb_S
Set FeedBack type:
Set then press F.
UP and DOWN :
UP and DOWN :
as password
10
UP and DOWN the required parameter.
Default
Contents
UM
Value
Firing mode
SW
Selection
*Default Value if not specified in the Order Code
ΠΑ
ΠΑΣτ
βΦδτ
Default
Contents
UM
Value
Sofstart -
%
Ramp Up
ΠΑ
Default
Contents
UM
Value
HB sensitivity
%
This parameter set a delay to have HB alarm active
Default
Contents
UM
Value
HB delay
sec
This parameter selects the Feed-back type.
HCL-1PH
then press F.
Min
Max
Min
Value
Value
Value
UM
DEC
DEC
UM
*
0
1024
0
20
Min
Max
Min
Value
Value
Value
UM
DEC
DEC
UM
100
0
255
0
Min
Max
Min
Value
Value
Value
UM
DEC
DEC
UM
100
0
100
0
Min
Max
Min
Value
Value
Value
UM
DEC
DEC
UM
20
0
255
0
26
User's Manual
Max
Par.
Value
Type
UM
1024 R/W
Max
Par.
Value
Type
UM
R/W
255
Max
Par.
Value
Type
UM
R/W
100
Max
Par.
Value
Type
UM
R/W
255