1. Safety Precautions Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing. Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating and main circuit for the model installed. ...
Page 3
WARNING 24. Tighten the flare nut with torque wrench according to specified method. If the flare nut is over tightened, after a long period, the flare may break and cause refrigerant gas leakage. 25. After completion of installation, confirm there is no leakage of refrigerant gas. It may generate toxic gas when the refrigerant contacts with fire.
Item Unit Outdoor Unit ø Three Power Source (Phase, Voltage, Cycle) Condition A35W7 A7W35 A2W35 (Ambient/Water) Input Power Cooling: 2.21 Heating: 1.86 Heating: 2.51 Maximum Input Power For Heatpump System 6.85 Power Supply 1 : Phase (Ø) / Max. Current (A) / Max. Input Power (W) 3Ø...
Item Unit Indoor Unit Volume Expansion Vessel Capacity of Integrated Electric Heater / OLP TEMP kW / °C 9.00 / 80 Tank Volume (Spec / Nett) 200 / 185 Max. Tank Water Set Temperature °C Tank Coil Surface Heat / Cool Maximum Working Pressure Tank Circuit...
Item Unit Outdoor Unit ø Three Power Source (Phase, Voltage, Cycle) Condition A35W7 A7W35 A2W35 (Ambient/Water) Input Power Cooling: 3.56 Heating: 2.53 Heating: 3.49 Maximum Input Power For Heatpump System 7.91 Power Supply 1 : Phase (Ø) / Max. Current (A) / Max. Input Power (W) 3Ø...
Page 9
Item Unit Indoor Unit Protection Device Residual Current Circuit Breaker (25) Volume Expansion Vessel Capacity of Integrated Electric Heater / OLP TEMP kW / °C 9.00 / 80 Tank Volume (Spec / Nett) 200 / 185 Max. Tank Water Set Temperature °C Tank Coil Surface Heat / Cool...
Item Unit Outdoor Unit ø Three Power Source (Phase, Voltage, Cycle) Condition A35W7 A7W35 A2W35 (Ambient/Water) Input Power Cooling: 4.76 Heating: 3.71 Heating: 5.16 Maximum Input Power For Heatpump System 10.27 Power Supply 1 : Phase (Ø) / Max. Current (A) / Max. Input Power (W) 3Ø...
Item Unit Indoor Unit Protection Device Residual Current Circuit Breaker (25) Volume Expansion Vessel Capacity of Integrated Electric Heater / OLP TEMP kW / °C 9.00 / 80 Tank Volume (Spec / Nett) 200 / 185 Max. Tank Water Set Temperature °C Tank Coil Surface Heat / Cool...
Page 14
Item Unit Outdoor Unit ø Three Power Source (Phase, Voltage, Cycle) Condition A35W7 A7W35 A2W35 (Ambient/Water) Input Power Cooling: 2.21 Heating: 1.86 Heating: 2.51 Maximum Input Power For Heatpump System 4.94 Power Supply 1 : Phase (Ø) / Max. Current (A) / Max. Input Power (W) 3Ø...
Page 15
Item Unit Indoor Unit Protection Device Residual Current Circuit Breaker (25) Volume Expansion Vessel Capacity of Integrated Electric Heater / OLP TEMP kW / °C 9.00 / 80 Tank Volume (Spec / Nett) 200 / 185 Max. Tank Water Set Temperature °C Tank Coil Surface Heat / Cool...
Page 17
Item Unit Outdoor Unit ø Three Power Source (Phase, Voltage, Cycle) Condition A35W7 A7W35 A2W35 (Ambient/Water) Input Power Cooling: 3.51 Heating: 2.53 Heating: 3.31 Maximum Input Power For Heatpump System 5.85 Power Supply 1 : Phase (Ø) / Max. Current (A) / Max. Input Power (W) 3Ø...
Page 18
Item Unit Indoor Unit Protection Device Residual Current Circuit Breaker (25) Volume Expansion Vessel Capacity of Integrated Electric Heater / OLP TEMP kW / °C 9.00 / 80 Tank Volume (Spec / Nett) 200 / 185 Max. Tank Water Set Temperature °C Tank Coil Surface Heat / Cool...
Page 20
Item Unit Outdoor Unit ø Three Power Source (Phase, Voltage, Cycle) Condition A35W7 A7W35 A2W35 (Ambient/Water) Input Power Cooling: 4.76 Heating: 3.74 Heating: 3.96 Maximum Input Power For Heatpump System 6.59 Power Supply 1 : Phase (Ø) / Max. Current (A) / Max. Input Power (W) 3Ø...
Page 21
Item Unit Indoor Unit Protection Device Residual Current Circuit Breaker (25) Volume Expansion Vessel Capacity of Integrated Electric Heater / OLP TEMP kW / °C 9.00 / 80 Tank Volume (Spec / Nett) 200 / 185 Max. Tank Water Set Temperature °C Tank Coil Surface Heat / Cool...
Page 22
3. Features Inverter Technology Energy saving High Efficiency Environment Protection Non-ozone depletion substances refrigerant (R410A) Long Installation Piping Long piping up to 30 meter with height difference 20 meter Flexible 4-way piping for outdoor unit Easy to use control panel Auto mode Holiday mode...
Page 23
4.1.4 Main Components cdef 1 Control Panel c Air Purge Valve Connector name Water Inlet 2 Water Pump d Pressure Relief Valve (From Space Heating/Cooling) 3 Control Board Cover e Flow Switch 4 PCB, Printed Circuit Board Water Pressure Gauge Water Outlet Three Phase RCCB Top Front Plate...
Page 24
Outdoor Unit Air inlet (rear) Air inlet (side) Air outlet Air inlet (side) Air outlet...
Page 26
Outdoor Unit <Top View> Space necessary for installation (140) 10 cm 10 cm 100 cm Anchor Bolt Pitch 355 x 260 <Side View> <Side View> <Front View> Unit: mm...
Page 27
6. Refrigeration and Water Cycle Diagram OUTDOOR UNIT INDOOR UNIT FLOOR HEATING AIR PURGE WATER OUTLET VALVE 3-WAY PRESSURE RELIEF VALVE VALVE WATER OUTLET TEMP. SENSOR EXPANSION FLOW SWITCH STRAINER VALVE STRAINER BACKUP HEATER ANODE BAR SANITARY HOT WATER OUTLET REFRIGERANT HEX WATER OUTLET TEMP.
Page 30
15.3.1 System Capacity Rank Setting Before Tank Unit operate, its Capacity Rank have to match with connected Outdoor Unit. See below table for detail. Model Capacity Rank Tank Unit Outdoor Unit UX09*E8* UX12*E8* UX16*E8* ADC0916*E8* UD09*E8* UD12*E8* UD16*E8* The Capacity Rank can be set by Control Panel Press SET and SERVICE buttons simultaneously for 5 seconds.
Page 31
19. Technical Data 19.1 Operation Characteristics 19.1.1 WH-ADC0916G9E8 WH-UX09FE8 Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7 m 14.000...
Page 32
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C Piping length : 7 m 10.000 9.000 8.000 7.000 6.000 5.000 Outdoor Temperature (°C) 5.500 4.500 3.500...
Page 33
Heating Characteristics at Different Piping Length Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7 m 10.000 9.000 8.000 7.000 6.000 5.000 Piping Length (m) 3.000 2.500 2.000...
Page 34
Cooling Characteristics at Different Piping Length Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C Piping length : 7 m 9.000 8.000 7.000 6.000 5.000 4.000 Piping Length (m) 2.500 2.400 2.300...
Page 35
19.1.2 WH-ADC0916G9E8 WH-UX12FE8 Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7 m 15.000 14.000 13.000 12.000 11.000...
Page 36
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C Piping length : 7 m 11.000 10.000 9.000 8.000 7.000 6.000 Outdoor Temperature (°C) 5.500 4.500 3.500...
Page 37
Heating Characteristics at Different Piping Length Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7 m 13.000 12.000 11.000 10.000 9.000 8.000 Piping Length (m) 4.000 3.500 3.000...
Page 38
Cooling Characteristics at Different Piping Length Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C Piping length : 7 m 11.000 10.000 9.000 8.000 7.000 6.000 Piping Length (m) 3.800 3.700 3.600...
Page 39
19.1.3 WH-ADC0916G9E8 WH-UX16FE8 Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7 m 18.000 17.000 16.000 15.000 14.000...
Page 40
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C Piping length : 7 m 14.500 13.000 11.500 10.000 8.500 7.000 Outdoor Temperature (°C) 5.000 4.300 3.600...
Page 41
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 18°C Piping length : 7 m 15.500 14.000 12.500 11.000 9.500 8.000 Outdoor Temperature (°C) 4.500 3.800 3.100...
Page 42
Heating Characteristics at Different Piping Length Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7 m 18.000 17.000 16.000 15.000 14.000 13.000 Piping Length (m) 4.200 4.000 3.800...
Page 43
Cooling Characteristics at Different Piping Length Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C Piping length : 7 m 13.000 12.400 11.800 11.200 10.600 10.000 Piping Length (m) 5.000 4.900 4.800...
Page 44
19.1.4 WH-ADC0916G9E8 WH-UD09FE8 Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7 m 9.200 9.000 8.800 8.600 8.400...
Page 45
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C Piping length : 7 m 10.000 9.000 8.000 7.000 6.000 5.000 Outdoor Temperature (°C) 3.000 2.500 2.000...
Page 46
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 19°C Indoor water outlet temperature : 14°C Piping length : 7 m 12.000 11.000 10.000 9.000 8.000 7.000 Outdoor Temperature (°C) 3.500 3.000 2.500...
Page 47
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 23°C Indoor water outlet temperature : 18°C Piping length : 7 m 9.500 8.500 7.500 6.500 5.500 4.500 Outdoor Temperature (°C) 3.000 2.500 2.000...
Page 48
Heating Characteristics at Different Piping Length Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7 m 10.000 9.500 9.000 8.500 8.000 7.500 Piping Length (m) 2.100 2.000 1.900...
Page 49
Cooling Characteristics at Different Piping Length Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C Piping length : 7 m 7.500 7.000 6.500 6.000 5.500 5.000 Piping Length (m) 2.500 2.400 2.300...
Page 50
19.1.5 WH-ADC0916G9E8 WH-UD12FE8 Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7 m 13.000 12.000 11.000 10.000 9.000...
Page 51
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C Piping length : 7 m 12.500 11.500 10.500 9.500 8.500 7.500 Outdoor Temperature (°C) 5.500 4.500 3.500...
Page 52
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 19°C Indoor water outlet temperature : 14°C Piping length : 7 m 16.000 15.000 14.000 13.000 12.000 11.000 Outdoor Temperature (°C) 5.500 4.500 3.500...
Page 53
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 23°C Indoor water outlet temperature : 18°C Piping length : 7 m 12.000 11.000 10.000 9.000 8.000 7.000 Outdoor Temperature (°C) 5.500 4.500 3.500...
Page 54
Heating Characteristics at Different Piping Length Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7 m 12.500 12.000 11.500 11.000 10.500 10.000 Piping Length (m) 4.000 3.500 3.000...
Page 55
Cooling Characteristics at Different Piping Length Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C Piping length : 7 m 11.000 10.000 9.000 8.000 7.000 6.000 Piping Length (m) 3.800 3.700 3.600...
Page 56
19.1.6 WH-ADC0916G9E8 WH-UD16FE8 Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7 m 17.500 16.000 14.500 13.000 11.500...
Page 57
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C Piping length : 7 m 16.000 14.000 12.000 10.000 8.000 6.000 Outdoor Temperature (°C) 5.500 4.500 3.500...
Page 58
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 19°C Indoor water outlet temperature : 14°C Piping length : 7 m 22.000 20.000 18.000 16.000 14.000 12.000 Outdoor Temperature (°C) 6.500 5.500 4.500...
Page 59
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 23°C Indoor water outlet temperature : 18°C Piping length : 7 m 17.000 15.000 13.000 11.000 9.000 7.000 Outdoor Temperature (°C) 5.500 4.500 3.500...
Page 60
Heating Characteristics at Different Piping Length Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7 m 17.000 16.500 16.000 15.500 15.000 14.500 Piping Length (m) 4.200 4.000 3.800...
Page 61
Cooling Characteristics at Different Piping Length Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C Piping length : 7 m 13.500 12.500 11.500 10.500 9.500 8.500 Piping Length (m) 5.000 4.900 4.800...
Page 62
19.2 Heating Capacity Table 19.2.1 WH-UX09FE8 Water Out (°C) Input Input Input Input Input Input Capacity Capacity Capacity Capacity Capacity Capacity Outdoor Air (°C) Power Power Power Power Power Power 9000 3240 9000 3510 9000 3910 9000 4300 9000 4730 9000 5160 9000...
Page 63
19.2.4 WH-UD09FE8 Water Out (°C) Input Input Input Input Input Input Capacity Capacity Capacity Capacity Capacity Capacity Outdoor Air (°C) Power Power Power Power Power Power 8650 3060 8300 3210 7950 3410 7600 3610 7150 3710 6700 3810 9350 2910 9000 3160 8850...