UPS5000-H-(400 kVA-800 kVA) User Manual (100 kVA Power Modules) Issue Date 2021-08-03 HUAWEI TECHNOLOGIES CO., LTD.
Page 2
Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
The "NOTICE", "CAUTION", "WARNING", and "DANGER" statements in this document do not cover all the safety instructions. They are only supplements to the safety instructions. Huawei will not be liable for any consequence caused by the violation of general safety requirements or design, production, and usage safety standards.
Do not power on the equipment before it is installed or confirmed by professionals. 1.2 Personnel Requirements ● Personnel who plan to install or maintain Huawei equipment must receive thorough training, understand all necessary safety precautions, and be able to correctly perform all operations. ●...
Page 21
NO TICE To ensure battery safety and battery management accuracy, use batteries provided by Huawei. Huawei is not responsible for any battery faults caused by batteries not provided by Huawei. Battery Installation Before installing batteries, observe the following safety precautions: ●...
2 Product Overview Product Overview 2.1 Positioning The UPS5000-H is a high-end modular UPS launched by Huawei. It adopts online double conversion and modular redundancy design for components. Based on the digital signal processing (DSP) technology, the UPS5000-H features high efficiency and power density.
The impact of environment on the UPS reliability is reduced. 2.3 Application Scenarios The UPS5000-H is suitable for power systems in various indoor scenarios, including large-sized data centers or communications centers, equipment rooms of large-sized enterprises, equipment rooms of financial systems, industrial automated equipment, and scheduling centers.
Page 54
View or obtain UPS running information during inspection. NOTE Only Huawei service engineers or authorized service engineers are allowed to use the WiFi module. To ensure security, remove the WiFi module immediately after use. ● Insert a USB flash drive to import and export configuration files, export run logs, and upgrade software.
The ECM extended subrack, surge protection box subrack, intelligent detection card, and top outlet kit do not support onsite installation. If you require the optional components, inform Huawei when you purchase the UPS so that Huawei can install them before delivery. 5.2 Dry Contact Extended Card...
Page 92
6 Installation Installation on Channel Steel NO TICE ● Huawei does not provide channel steel or expansion bolts used for securing channel steel. It is recommended that the customer purchase at least 50 mm wide channel steel. ● Ensure that the surface of channel steel is level.
Page 100
6 Installation Installation on Channel Steel NO TICE ● Huawei does not provide channel steel or expansion bolts used for securing channel steel. It is recommended that the customer purchase at least 50 mm wide channel steel. ● Ensure that the surface of channel steel is level.
Page 109
6 Installation Installation on Channel Steel NO TICE ● Huawei does not provide channel steel or expansion bolts used for securing channel steel. It is recommended that the customer purchase at least 50 mm wide channel steel. ● Ensure that the surface of channel steel is level.
Page 115
----End Installation on Channel Steel NO TICE ● Huawei does not provide channel steel or expansion bolts used for securing channel steel. It is recommended that the customer purchase at least 50 mm wide channel steel. ● Ensure that the surface of channel steel is level.
Page 119
----End Installation on Channel Steel NO TICE ● Huawei does not provide channel steel or expansion bolts used for securing channel steel. It is recommended that the customer purchase at least 50 mm wide channel steel. ● Ensure that the surface of channel steel is level.
Page 128
6 Installation Installation on Channel Steel NO TICE ● Huawei does not provide channel steel or expansion bolts used for securing channel steel. It is recommended that the customer purchase at least 50 mm wide channel steel. ● Ensure that the surface of channel steel is level.
Page 138
----End Installation on Channel Steel NO TICE ● Huawei does not provide channel steel or expansion bolts used for securing channel steel. It is recommended that the customer purchase at least 50 mm wide channel steel. ● Ensure that the surface of channel steel is level.
Page 144
----End Installation on Channel Steel NO TICE ● Huawei does not provide channel steel or expansion bolts used for securing channel steel. It is recommended that the customer purchase at least 50 mm wide channel steel. ● Ensure that the surface of channel steel is level.
6.10 Connecting a Remote EPO Switch NO TICE ● Huawei does not provide the EPO switch or cable. Prepare them by yourself. The recommended cable size is 0.3 mm ● Equip the EPO switch with a protective cover to prevent misoperations, and protect the cable with a protective tube.
Before power-on, ensure that all the UPS switches and upstream switches are OFF. Procedure Step 1 Turn on the upstream bypass and mains input switches. After the UPS is powered on, initialization begins. The MDU displays the Huawei logo and an initialization progress bar. ----End Issue 03 (2021-08-03)
Service Expert app. Skip this step if the UPS is not powered on for the first time. ● The Service Expert app can be downloaded from HUAWEI AppGallery and can only run on Android. 7.1.2.1 Obtaining Startup Password Procedure Step 1 Download and install the Service Expert app.
1 Hz or is steady on, press and hold down the BATT START button on the UPS bypass control module for more than 2 seconds. The system automatically enters the battery cold start state. The MDU displays the Huawei logo and an initialization progress bar.
Page 185
If the input power is normal, the rectifier starts automatically. The MDU starts and displays the Huawei logo and a progress bar. Wait until the MDU starts properly. NO TE If the input SPD circuit breaker is not switched on, the system can start properly, but an Input surge arrester alarm will be reported.
Customers are not allowed to maintain components behind protective covers that can be removed only using tools. If the components are to be maintained, contact Huawei technical support. ● Only maintenance engineers can maintain power modules and bypass modules.