In order to keep the manual lean and show you how topics are interrelated, cross-references are used. Field of use The Climatix HMI-TM products can only be used in the field of heating, ventilation, air conditioning and refrigeration. Proper use Prerequisites for flawless and safe operation of the Climatix HMI-TM products are proper transport, installation and commissioning, as well as correct operation.
SCOPE commissioning and service tool Human machine interface Brief introduction The Climatix HMI-TM is designed for display, system configuration, set-up and operation. It is a product of the Climatix range, supporting all Climatix range of controllers. The HMI-TM cannot be used to operate any 3 -party devices.
- Firmware can be updated via controller (SD card support required) Reference documents The following documents contain further information on the products described in this document: Document Document No. Data Sheet “Climatix HMI-TM” CB1N3917en Mounting Instructions “Climatix HMI-TM” CB1M3917en CB1T3917xx CE declaration of conformity 233006-T-0601_EN Environment product declaration (POL871.71)
HMI-TM overview This section introduces the overview of Climatix HMI-TM. Function keys The function keys of HMI-TM are illustrated as follows: Description Key Name Operation Press To increase the input value To enable the acceleration function to increase the value in a large...
For Latin (English) characters, font sizes of 6*12 pixels and 7*14 pixels (width*height) are supported; For Eastern Asian characters such as Chinese, font sizes of 12*12 and 14*14 pixels (width*height) are supported. Here are the examples: Displaying example 9 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building technologies 2BHMI-TM overview 2015-07-02...
Page 10
Regarding how to program a title line, refer to Climatix SCOPE online help. 10 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building Technologies 2BHMI-TM overview 2015-07-02...
Page 11
“►”. The Latin characters and Eastern Asian characters are generated by SCOPE. Font size of characters varies with different versions of SCOPE. 11 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building technologies 2BHMI-TM overview 2015-07-02...
Press and hold key ESC on any page to go to the following page: The HMI settings page supports multi-language. The actual displaying language depends on the certain language selected in the controller. 12 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building Technologies 3BFunctions and operations 2015-07-02...
Page 13
1. Select Backlight color in the HMI setting page. 2. Press key ENTER to highlight Blue. 3. Press key UP to change the color. 13 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building technologies 3BFunctions and operations 2015-07-02...
Page 14
Backlight turn off time for value editing. Brightness The brightness of HMI-TM screen can be configured from 0 to 100. Refer to Backlight turn off time for value editing. 14 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building Technologies 3BFunctions and operations 2015-07-02...
If the version of controller BSP is below 7.32, it will redirect to the home page without downloading the objects. Home page may be different according to the actual application. 15 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building technologies 3BFunctions and operations 2015-07-02...
1. Press and hold key ENTER on any page (except the error report pages) with OEM factory user level to activate the log in/off page as follows: 16 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building Technologies 3BFunctions and operations 2015-07-02...
Page 17
Enter correct 4-digit password and it will go to the target page defined in the HMI template. The corresponding user level will be shown on the upper-right corner. 17 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building technologies 3BFunctions and operations 2015-07-02...
Page 18
Press and hold key ENTER on any page (except the error report pages), and the log in/off page will be displayed: 18 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building Technologies 3BFunctions and operations...
Page 19
To change the password of user level, select Change user password and press key ENTER, and the following page will be displayed: If the entered passwords do not match, the following page will be displayed: Then re-enter the password. 19 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building technologies 3BFunctions and operations 2015-07-02...
The context helper page is fully programmable and should be pre-defined. For instance, the home page can be defined as the context helper of all HMI-TM pages by application engineer. In this case, key INFO serves as homepage. 20 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building Technologies 3BFunctions and operations 2015-07-02...
If “null value supported” is selected during the template creation, a separate scale will appear to the right of the ruler. If the separated scale (null value) is selected, the value will become asterisks. 21 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building technologies 3BFunctions and operations 2015-07-02...
Page 22
Press key ESC to exit and all the modifications will be cancelled. In-place editing: The value can be directly editable on the parameter list page. Press key ESC to one value in one line cancel the value input. 22 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building Technologies 3BFunctions and operations 2015-07-02...
Press key ALARM and the alarm related pages will be displayed by the following order: Alarm list detail → Alarm list → Alarm history → Alarm list/history settings. 23 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building technologies 3BFunctions and operations...
Page 24
To change the sorting methods, select Sort order 1 or Sort order 2 on the Alarm list/-history settings page, and the following page will be displayed: Select one sorting method on this page and press key ENTER to confirm the selection. 24 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building Technologies 3BFunctions and operations 2015-07-02...
Press and hold on the online trend page Press To exit from the online trend page Press To increase the time DOWN Press To decrease the time 25 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building technologies 3BFunctions and operations 2015-07-02...
The function of time scheduler enables to display the schedule in graphics. 1. Define the name for time scheduler (e.g. “Enumeration Scheduler” or “Set point Scheduler”) in SCOPE as follows: 26 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building Technologies 3BFunctions and operations 2015-07-02...
Page 27
To adjust date and time DOWN Press To change the enumeration or set point ENTER Press To confirm the selection INFO Long press (3 sec.) To delete a time scheduler entry 27 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building technologies 3BFunctions and operations 2015-07-02...
Page 28
4. Press key UP/DOWN to adjust the value on the vertical axis. The value is displayed on the top line. Press key ENTER. 5. Repeat step 3 through 4 until all scheduler entries are set. 28 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building Technologies 3BFunctions and operations 2015-07-02...
Page 29
4. Press key UP/DOWN to adjust the value on the vertical axis. The value is displayed on the top line. Press key ENTER. 5. Repeat step 3 through 4 until all scheduler entries are set. 29 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building technologies 3BFunctions and operations 2015-07-02...
Page 30
4. Long press key INFO and hold 3 seconds to delete the scheduler. It is possible to set maximum 6 scheduler entries. Afterwards an error message appears. 30 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building Technologies 3BFunctions and operations 2015-07-02...
To go to the sub page defined on Line 6 Monkey Key Press and hold To go to the defined target page of menu INFO & both keys for 5 mode ALARM seconds 31 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building technologies 3BFunctions and operations 2015-07-02...
Page 32
Lines No. 1, 2 and 3 have the same datapoints (e.g. “999.9°C”). Tick features as above picture (e.g. Right Alignment, Use Engineering Unit). Enumerations datapoint in Iconic mode page template should like: 32 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building Technologies 3BFunctions and operations 2015-07-02...
Page 33
1. Right click the mouse on Language tab of HMI page and select Edit Icons: 2. The dialog box of Select Code will popup. Select a blank icon and click 33 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building technologies 3BFunctions and operations...
Page 34
5. Right click the mouse on Language tab and select Select Icons. 6. The dialog box of Character Map popups. Select All Fonts (Private Characters) from the drop-down list of Font. 34 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building Technologies 3BFunctions and operations 2015-07-02...
2. Connect the HMI-TM to the controller. 3. Press and hold key ESC to enter the following page. 4. Select HMI settings and press key ENTER. Then the following page will be displayed: 35 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building technologies 3BFunctions and operations 2015-07-02...
Page 36
V9.14B0030 is required as a bridge to upgrade to V10.XXB00YY. Follow Firmware update process as above. Do not unplug the cable or power off the controller during the updating process. 36 / 38 Siemens Climatix HMI-TM CB1P3917en02 Building Technologies 3BFunctions and operations 2015-07-02...