IB 6.1.2.8-1B
INSTRUCTIONS FOR MPS-C 2000
ELECTRONIC TRIP CONTROL UNIT
ABB
Courtesy of NationalSwitchgear.com

Advertisement

Table of Contents
loading

Summary of Contents for ABB MPS-C 2000

  • Page 1 IB 6.1.2.8-1B INSTRUCTIONS FOR MPS-C 2000 ELECTRONIC TRIP CONTROL UNIT Courtesy of NationalSwitchgear.com...
  • Page 2: Table Of Contents

    SHORT TIME FUNCTION................. INSTANTANEOUS FUNCTION..............GROUND FUNCTION................CURRENT UNBALANCE................CURRENT SENSOR THRESHOLDS............INFORMATION FUNCTION..............TEST FUNCTIONS.................... VOLTAGE INTERFACE MODULE (VIM)............. SETTINGS....................MPS-C 2000 SETUP INSTRUCTIONS..............GENERAL INSTRUCTIONS..............MENU LAYOUT..................METERING SUBMENU................SETTINGS SUBMENU................CHANGE SETTINGS SUBMENU............. AVAILABLE SETTINGS................PASSWORD PROTECTION..............RECORDS SUBMENU................
  • Page 3: Introduction

    130 KA. The MPS-C 2000 trip control unit measures current to an accuracy of within 1% of the cicuit breaker rating.
  • Page 4: Functions

    1.3 Test Functions The unit can be connected to an external test set to check functions and settings. 1.4 Communication Functions The unit can be connected to switchgear mounted devices which are connected to ABB INCOM Protocol. 2. SETTINGS. 2.1 Range Selection The range selector provides the primary amperage used as the base for the unit.
  • Page 5: Instantaneous Function

    IB 6.1.2.8-1B Page 5 2.3.2 Trip time - Time is defined by the short time overcurrent curves (graph). I²t function is selectable. I²t curves are fixed and do not vary with pickup settings. I²t is operational only from 2X to 4X. Trip times with I²t out are defined as follows: Default is maximum with I²t in.
  • Page 6: Current Unbalance

    IB 6.1.2.8-1B Page 6 2.5.2 Trip time - The time is defined by the overcurrent curves (graph). I²t function is selectable. I²t curves are fixed and do not vary with pickup settings. If the I²t function is out, the trip times are defined as follows: Default is Maximum with I²t in.
  • Page 7: Test Functions

    Page 7 2.8.3 The target resets automatically when the unit is re-energized. Reset occurs in 2 seconds. 2.8.4 The red LED blinks once per second to indicate that the MPS-C 2000 unit is powered up and functioning normally. (self monitor light).
  • Page 8: Mps-C 2000 Setup Instructions

    5.1.1 The front panel keypad consists of four directional arrow keys, a cancel key, an enter key, and an LCD window. 5.1.2 When the MPS-C 2000 unit is connected to a power source, an initial title screen is displayed in the LCD window.
  • Page 9: Menu Layout

    IB 6.1.2.8-1B Page 9 MENU LAYOUT 6.1 The following layout shows the Main Menus and submenus accessed by pressing the “E” key and the up and down arrows. To exit the submenus to return to the Main Menu, the “C” key should be pressed. For layouts of the submenus, refer to sections 6.2 through 6.5.
  • Page 10: Metering Submenu

    IB 6.1.2.8-1B Page 10 6.2 METERING SUBMENU SUBMENU Press "E" ===METER MENU=== ==LOAD VALUES== Load Values Ia: ### Press "C" Ib: ### Ic: ### In: ### Van: ### Vbn: ### Vcn: ### These Vab: ### values will Vbc: ### Scroll up and down not be Vca: ### using arrow keys...
  • Page 11: Settings Submenu

    IB 6.1.2.8-1B Page 11 6.3 SETTINGS SUBMENU SUBMENU Press "E" =SETTINGS MENU= =SHOW SETTINGS= MPS Settings Rating: #### Press "C" LT Pickup: #### LT Delay: #### ST Pickup: #### ST Delay: #### ST Curve: #### INST Pkup: #### GND Pkup: #### Scroll up and down GND Delay: #### using arrow keys...
  • Page 12: Change Settings Submenu

    IB 6.1.2.8-1B Page 12 6.4 CHANGE SETTINGS SUBMENU See instructions below for changing settings sec. 6.4.1 SUBMENU Press "E" Press "E" ==CHANGE MENU== =ENTER PASSWORD= =CHANGE SETTINGS = PRESS "E" TO CHANGE MPS Settings Rating: #### * * * * SETTINGS LT Pickup: #### LT Delay: ####...
  • Page 13: Available Settings

    IB 6.1.2.8-1B Page 13 6.4.2 Available Settings The following is a list of choices for each setting in the CHANGE SETTINGS Submenu: MPS SETTINGS LT PICKUP: 0.5X, 0.6X, 0.7X, 0.8X, 0.9X, 1.0X Sensor rating. LT DELAY: MIN, INT, MAX ST PICKUP: 2X, 3X, 4X, 5X, 6X, 7X, 8X, 9X, 10X, 11X, 12X Sensor rating, and DISABLED. ST DELAY: MIN, INT, MAX ST CURVE: DEF, IIT INST PICKUP: 3X, 4X, 5X, 6X, 7X, 8X, 9X, 10X, 11X, 12X Sensor rating, and DISABLED if INST disable jumper is...
  • Page 14: Records Submenu

    IB 6.1.2.8-1B Page 14 6.5 RECORDS SUBMENU SUBMENU Press "E" =RECORDS MENU= =MPS FLT EVENT= MPS Fault Event Event : ## Press "C" Type: ### Ticks: ### Scroll up and down Ia: ### using arrow keys Ib: ### Ic: ### In: ### Press "Up and Down"...
  • Page 15 IB 6.1.2.8-1B Page 15 Notes: Courtesy of NationalSwitchgear.com...
  • Page 16 IB 6.1.2.8-1B Page 16 Notes: Courtesy of NationalSwitchgear.com...
  • Page 17 IB 6.1.2.8-1B Page 17 Notes: Courtesy of NationalSwitchgear.com...
  • Page 18 IB 6.1.2.8-1B Page 18 ABB Inc. 2300 Mechanicsville Road Florence, SC 29501 Phone: (843) 413-4700 Fax: (843) 413-4850 Courtesy of NationalSwitchgear.com...