Modbus RTU RS485 System integration Functions codes Operating Instructions Technical data Modbus holding registers Appendix Add-on module for use with transmitter types SITRANS F M MAG 6000, SITRANS F M MAG 6000 I and SITRANS F M MASS 6000. 06/2010 A5E00753974-04...
Page 4
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Table of contents Introduction..............................5 Purpose of the Operating Instructions ...................5 Document history ...........................5 Modbus RTU technology .......................6 Further Information ........................7 Safety notes............................... 9 Installation in hazardous area ......................9 Hardware Installation ..........................11 MAG/MASS 6000 IP67 or 19"......................11 MAG 6000 I ..........................12 MASS 6000 Ex d..........................13 Connecting ..............................
Page 6
Table of contents External input ..........................50 Sensor characteristics......................... 51 Product identity ........................... 52 A.10 Service info ..........................52 A.11 Display settings ........................... 53 A.12 Flowmeter status......................... 57 Appendix..............................59 Units ............................59 Units and point positioners......................59 Modbus Coils ..........................64 Error information .........................
See also For more information about SITRANS F C and SITRANS F M transmitters and sensors, please refer to the appropriate Operating Instructions available on the flowdocumentation homepage (http://www.siemens.com/flowdocumentation) or on the SITRANS F literature CD- ROM.
Features The SITRANS F Modbus RTU Communication modules comply with the MODBUS Serial Line Protocol. Among other things this implies a Master-Slave protocol at level 2 of the OSI model. A node (the master) issues explicit commands to one of the slave-nodes and processes responses.
Product information on the Internet The Operating Instructions are available on the CD-ROM shipped with the device, and on the Internet on the Siemens homepage, where further information on the range of SITRANS F flowmeters may also be found: Product information on the internet (http://www.siemens.com/flow)
Page 10
Introduction 1.4 Further Information Modbus RTU RS485 Operating Instructions, 06/2010, A5E00753974-04...
Safety notes CAUTION Correct, reliable operation of the product requires proper transport, storage, positioning and assembly as well as careful operation and maintenance. Only qualified personnel should install or operate this instrument. Note Alterations to the product, including opening or improper repairs of the product, are not permitted.
Page 12
Safety notes 2.1 Installation in hazardous area Modbus RTU RS485 Operating Instructions, 06/2010, A5E00753974-04...
Hardware Installation This chapter describes the HW installation procedure for the add-on module on Siemens Flow Instruments USM-II transmitters. The Module can be installed into SITRANS F C MASS 6000 and SITRANS F M MAG 6000 transmitters. Note Not allowed for use in hazardous areas The Communication module is NOT allowed for use in hazardous areas.
2. Press the add-on module in the direction shown until it stops and is firmly seated in position 3. The installation is completed MAG 6000 I The installation of the add-on module on a SITRANS F M MAG 6000 I is completed as follows: 1. Open the transmitter WARNING...
Installation in hazardous area The communication module is NOT approved for use in hazardous area. The installation of the add-on module on a SITRANS F C MASS 6000 Ex d is completed as follows: 1. Disconnect the equipment from the supply circuits...
Page 16
Hardware Installation 3.3 MASS 6000 Ex d 2. Remove the rear cover by loosening the safety tap allen screw and turn the rear cover counter-clockwise 3. Remove the electronics using the holes provided 4. Remove the flat cable from the plate 5.
Page 17
Hardware Installation 3.3 MASS 6000 Ex d 6. Insert the add-on module as shown. Note The label on the add-on module must face upwards and the connector outwards 7. Press the add-on module into position and connect the flat cable connector. Modbus RTU RS485 Operating Instructions, 06/2010, A5E00753974-04...
Page 18
Hardware Installation 3.3 MASS 6000 Ex d Modbus RTU RS485 Operating Instructions, 06/2010, A5E00753974-04...
Connecting On the electrical termination boards for USM-II transmitters, additional input/output terminals have been reserved for add-on module functions. The numbering range of these terminals is as follows, but how many are actually used depends on the type of add-on module. Additional terminals reserved for add-on modules: ●...
Connecting 4.1 Wiring Wiring Figure 4-1 Modbus USMII connection Table 4- 1 Connection layout Terminal number MODBUS RTU RS485 Data + Data - Shield NOTICE Temination Connecting 91,92 and 93,94 will add termination. This must be carried out if the device is the last on the segment.
System integration This chapter provides information on how to integrate the flowmeter in a Modbus RTU automation and control system. The chapter shows the necessary steps in order to put the system into operation. After finishing the steps, the system is ready to go into normal operation in the Modbus RTU automation control system.
System integration 5.2 Navigating the Modbus display menu Navigating the Modbus display menu 1. Power up the device. If the device has been installed correctly a new menu entry has appeared in the local user interface of the device (between the "Reset mode" and the "Service mode"...
Page 23
System integration 5.2 Navigating the Modbus display menu Table 5- 1 Menu items Item Value Description Device 1-247 Device address [Factory setting: 1] Communication Address Baud rate 1200, 2400, 4800, 9600, 19200, Communication speed 38400, 57600, 76800, 115200 [Factory setting: 19200] Even, 1 stopbit Parity/framing Communication parameters...
Page 24
System integration 5.2 Navigating the Modbus display menu Modbus RTU RS485 Operating Instructions, 06/2010, A5E00753974-04...
Broadcast communication is not secured by the normal check mechanisms and shall be limited to very few uses. A SITRANS F Modbus slave only recognizes (and accepts) few Modbus RTU commands/function codes.
Functions codes 6.2 Read coils Read coils Command messages The read coils functions (01hex x) allow the master to request information from the slave. The command message of a coil read is structured as shown below. Each row in the table compares to a byte in the message –...
Page 27
Functions codes 6.2 Read coils Table 6- 3 Read coil normal response messages Message byte Example Slave address xxhex Function code 01hex Bit count xxhex Coil status byte(s) xxhex xxhex Next coil status byte(s) xxhex xxhex Last coil status byte(s) xxhex xxhex CRC-16...
Functions codes 6.3 Read multiple registers Read multiple registers Command messages The multiple register read functions (03hex) allows the master to request information from the slave. The command message of a multiple register read is structured as shown below. Each row in the table compares to byte in the message – top byte (Slave address) is transmitted first.
Page 29
Functions codes 6.3 Read multiple registers Table 6- 6 Read multiple registers normal response messages Message byte Example Slave address xxhex Function code 03hex Byte count xxhex Starting register Upper xxhex Lower xxhex Next register Upper xxhex Lower xxhex Last register Upper xxhex Lower...
Functions codes 6.4 Write single coil ● Query: 1,3,11,190,0,2,166,11 (Hex 01,03,0B,BE,00,02,A6,0B) ● Response: 1,3,4,189,216,115,34,251,77 (Hex 01,03,04,BD,D8,73,22,FB,4D) ● Sensor temperature = −0.10569 °C Write single coil Command messages The write coil functions (05hex) allow the master to control single bits in the slave. The command message of a coil write is structured as shown below.
Functions codes 6.5 Write multiple registers Table 6- 9 Write coil normal response messages Message byte Example Slave address xxhex Function code 05hex Coil address Upper xxhex Lower xxhex New coil value Upper FFhex or 00hex Lower 00hex CRC-16 Lower xxhex Upper xxhex...
Page 32
Functions codes 6.5 Write multiple registers The initial slave address is 1. Address 0 (broadcast) and other values between 1 and 255 can be used. The function code of this message is 10hex (write multiple registers). The starting register is the first register to be written to. The quantity indicates how many consecutive 16-bit registers are to be written to.
Page 33
Functions codes 6.5 Write multiple registers Message byte Example Starting register Upper xxhex Lower xxhex Quantity Upper xxhex Lower xxhex CRC-16 Lower xxhex Upper xxhex Exception responses The exception response message contains the same slave address as the command message. The function code of the exception message is actually a value of 80 hex plus the original function code of 10 hex.
6.6 Report slave ID command Report slave ID command All SITRANS F slaves will respond to a Report Slave ID command (Command 17) request from the master by giving in formation about device type, vendor, revision level etc. in a...
Run Indicator 0xFF Product Code 25 (0x19) Transmitter Code No 083H0222 Capability bits 0x01, 0xFF, 0x00 Manufacturer name Siemens Product name MASS 6000 Product major rev Product minor rev MODBUS module name MODBUS RTU MODBUS module No 0xFF MODBUS module major rev...
Page 36
Functions codes 6.7 Exception handlng If an exception code 04 is received, further requests have to be done to narrow down the exact problem. If any doubts about the address that failed, "Last Coil/HoldReg ErrorAddr" can be read. This will return the faulty address. MODBUS MODBUS No.
Technical data Table 7- 1 Technical data Device type Slave Baud rates 1200, 2400, 4800, 9600, 19200, 38400, 57800 bits/sec Number of stations Recommended: max. 31 per segment without repeaters Device address range 1-247 Protocol RTU (Other Modbus protocols like ASCII, Plus or TCP/IP are not supported.) RS485, 2 wire Electrical interface...
Modbus holding registers In the following the holding registers for the USM II Modbus RTU module are described. Figure A-1 Modbus Holding Registers Memory Map ● The minimum value of a writable "holding register" value can be read by adding 10000 to the address of the value.
Modbus holding registers A.11 Display settings Table A- 21 Service info, MASS 6000 MODBUS MODBUS No. of bytes Data type Description Read / write register address 4:02701 2700 Double word Operating time (s) 4:02703 2702 Byte array USM II Error pending list See Error information (Page 66) 4:02730 2729...
Page 56
Modbus holding registers A.11 Display settings MODBUS MODBUS No. of bytes Data type Description Read / write register address 4:02903 2902 Byte Display line 2: 0 = Text for line 3 • 1 = Volumeflow • 2 = Volumeflow % •...
Page 57
Modbus holding registers A.11 Display settings Table A- 23 Display settings, MASS 6000 MODBUS MODBUS No. of bytes Data type Description Read / write register address 4:02901 2900 Byte Language: 0 = English • 1 = Deutsch • 2 = Français •...
Appendix Units The following standard SI Units are used in USMII transmitters: SITRANS F M ● Volume flow: m /sec. ● Totalisers: m SITRANS F C ● Mass flow: kg/sec. ● Volume flow: m3/sec. ● Density: kg/m3 ● Temperature: °C ●...
Page 62
Appendix B.2 Units and point positioners Unit Description t / min metric ton per minute lb / min pound per minute mg / min milligram per minute g / min gram per minute 21 ... 31 kg / min kilogram per minute kg/h kilogram per hour ton/h...
Page 63
Appendix B.2 Units and point positioners Unit Description kL / min kiloliter per minute ML/ min megaliter per minute bbl / min barrel per minute / min cubic meter per minute / min cubic feet per minute / min cubic inch per minute USGPM US gallon per minute USMGPM...
Page 64
Appendix B.2 Units and point positioners Unit Description USkGPD kilo US gallon per day UKkGPD kilo imperial gallon per day 64 ... 255 Reserved Table B- 3 Density Units Unit Description kg/m kilogram per cubic meter t / m metric ton per cubic meter lb / m pound per cubic meter mg / m...
Page 65
Appendix B.2 Units and point positioners Table B- 5 Totalizer units for volumeflow Unit Description cubic meter milliliter liter hectoliter kiloliter megaliter USBBL barrels cubic meter cubic feet cubic inch US gallon USMG mega US gallon Imperial gallon UKMG mega Imperial gallon USkG kilo US gallon UKkG...
Appendix B.3 Modbus Coils Modbus Coils In the following the coils for the USM II MODBUS RTU module are described. Figure B-1 Modbus Coils Memory Map Communication settings Table B- 7 Communication settings MODBUS register MODBUS address Data type Description Read/ write 0:00001...
Page 67
Appendix B.3 Modbus Coils Totalizer Table B- 9 Totalizer MODBUS register MODBUS address Data type Description Read/ write 0:00010 Coil Reset totalizer 1: Write: 0 = No effect • 1 = ResetRead: • – always 0 0:00011 Coil Hold totalizer 1: Write: 0 = Run •...
Appendix B.5 Run indicator Error Number A list of all error numbers can be found in the relevant SITRANS F M / SITRANS F C Operating Instructions. No error is represented by 0x7F. • 0: Information Category • 1: Warning •...
Appendix B.6 CRC calculation Only the internally broadcasted flow-value is checked. The expected broadcast-rate is read at power up. If a broadcast is not received after 10 times the expected broadcast rate, the broadcast rate is re-read from the USM (it may have been changed since power up). If the broadcast rate was not changed (and the rate was not zero), the Run Indicator is set OFF.
B.7 Data type mapping Data type mapping Some standard datatypes are defined in the SITRANS F protocol. Most of these datatypes are not present in the MODBUS® RTU protocol as it defines ‘Registers’ and ‘Coils’ for all variables. A register in this context is always 16 bit long. This will prove restrictive for the parameters found in Siemens Flow products and therefore a number of approaches have been adopted to overcome this restriction.
Page 74
Appendix B.8 Float definition Table B- 12 Float definition Value (decimal) IEEE FP B MSB Register N Register N + 1 high high 100.0 42C80000h 55.32 425D47AEh 40000000h 3F800000h -1.0 BF800000h Example Read absolute massflow (4:03001): ● Query: 01,03,0B,B8,00,02,46,0A ● Response: 01,03,04,40,C3,52,93,62,C8 ●...
Glossary Cyclic Redundancy Check. Used for error-checking in MODBUS RTU Modbus master A ModBus device, which is able to access data in one or more connected ModBus slaves. Modbus slave A ModBus device, which is able to respond to requests from a single ModBus master. RS232 Refers t communication standard defined by EIA/TIA-232.(Physical layer) RS485...