SERVICE MANUAL Outdoor Unit Model No. 1U25YEEFRA WARNING This service information is designed for experienced repair technicians only and is not designed for use by the general publi ● It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product.
Introduction 1.Introduction 1.1 Model name explanation Apply toT1; 220~240V50HZ/1ph DC inverter Heat pump & R32 refrigerant Version number Europe Platform of outdoor units: NEW 0.8P p latform Nominal cooling capacity ( 9000BTU/h ) Type of outdoor unit : U (normal type) The maximum combination number Domestic air conditioner...
Page 4
Intuoduction 1.2 Safety Cautions Be sure to read the following safety cautions before conducting repair work. The caution items are classified into “Warning” and “Caution”. The “Warning” items are especially important since they can lead to death or serious injury if they are not followed closely. The “Caution” items can also lead ●...
Page 5
Intuoduction When disconnecting the suction or discharge pipe of the compressor at the welded section, release the refrigerant gas completely at a well-ventilated place first. If there is a gas remaining inside the compressor , the refrigerant gas or refrigerating machine oil discharges when the pipe is disconnected, and it can cause injury.
Page 6
Intuoduction conduct repair work. Never attempt to modify the equipment. The use of inappropriate parts or tools can cause an electrical shock, excessive heat generation or fire. When relocating the equipment, make sure that the new installation site has sufficient strength to withstand the weight of the equipment.
Page 7
Intuoduction itself is harmless, but it can generate toxic gases when it contacts flames, such as fan and other heaters, stoves and ranges. When replacing the coin battery in the remote controller, be sure to disposed of the old battery to prevent children from swallowing it.
Page 8
Intuoduction Caution Check to see if the parts and wires are mounted and connected properly, and if the connections at the soldered or crimped terminals are secure. Improper installation and connections can cause excessive heat generation, fire or an electrical shock. ●...
Specification 2.Specifications NOMINAL DISTRIBUTION SYSTEM VOLTAGE ● NOMINAL CAPACITY and NOMINAL INPUT n i l Capacity rated Btu/h 8870 9890 ● Power Consumption(Rated) 0.78 6.2/A++ Annual energy consumption ³ 1.2*10 ﹣ ³ TECHNICAL SPECIFICATIONS-UNIT Dimensions H*W*D 700×245×544 ● Packaged H*W*D 845×320×593 Dimensions Weight...
Specification c t i TECHNICAL SPECIFICATIONS-OTHERS Refrigerant type Refrigerant charge 0.55 Refrigerant Maximum allowable distance circuit between indoor an outdoor Maximum allowable level difference ● Refrigerant control CAPILLARY liquid Φ6.35 Piping connections Φ9.52 (external diameter) drain Φ16 ● Heat insulation type Both liquid and Gas pipes ●...
Wiring diagrams 6.Printed Circuit Board Connector Wiring Diagram Connectors PCB (1) (Outdoor Control PCB) CN50 Connector for power N,L, Communicate between indoor and outdoor unit and Ground CN51 Connector for reactor CN52 Connector for the U, V, W wire of the compressor CN21 Connector for fan motor...
Page 14
Wiring diagrams PCB(1) Domestic air conditioner...
Functions and control 7.Outdoor Functions and Control 7.1 Main functions and control specification .1.1 The operation frequency of outdoor unit and its control ● 7.1.1.1 The operation frequency control of compressor The operation frequency scope of compressor: Mode Minimu m operation frequency Maximum operation frequency ●...
Page 17
Functions and control Wh_c<-8 Max_hz2 99 HZ Wh_c<-2 Max_hz3 99 HZ Wh_c<5 Max_hz4 99 HZ Wh_c<10 Max_hz5 80 HZ Wh_c<17 Max_hz6 67 HZ Wh_c<20 Max_hz7 63 HZ Wh_c>=20 Max_hz8 5 52 HZ Remarks: The above are the maximum frequency limitations of the complete appliance which are affected by the environment, and they have nothing to do with the ability of the indoor unit.
Page 18
Functions and control When refrigerating, it is needed to satisfy F-MIN-d(compressor’s Min_hz)< F<F-MAX-d(compressor’s Max_hz) When heating, it is needed to satisfy F-MIN-r (compressor’s Min_hz)< F<F-MAX-r (compressor’s Max_hz) PID control : The innital frequency Sn is determined by Pn . We can calculate Hzoutf according to the value of Kp ,Ki ,Kd, Out_gain,Pn.Then , Fn = Sn + Hzoutf.
Page 19
Functions and control 7.1.4 Four way control For the details of defrosting four-way valve control, see the defrosting process. Four way working in other ways: Under the mode of heating, open the four-way valve, when the compressor is not started or changed to non-heating mode, make sure the compressor is stoped for 2 minutes, and then close the four-way valve.
Page 20
Functions and control state). TC=indoor coil temp. The indoor heat exchanger sensor tests the temperature of the indoor heat exchanger. If the temperature is higher than 63 ℃ , decrease the rotate speed of the compressor and do the high temperature-preventing protection of the indoor heat exchanger;...
Page 21
Functions and control the compressor increases at the prohibited speed. During the starting process of the compressor, if the AC current is greater than 5A, the frequency of the compressor increases at the speed of no faster than 0.1HZ/second. Remarks: when the outdoor temperature is high, there’s compensation for AC current protection. (1) When the outdoor environment temperature is higher than 40℃, AC current protection value decreases by 1A.
Page 32
Service diagnosis 10.3 Error Codes and Description indoor display Code indication Indoor displaying panel code indication Only For 498 and Outdoor Reference fault description 498A display (LED1 flash Page Other display (Red/Green Time times) Run □On★Flash■ Off) Indoor and Communication fault between Page.42 ■...
Page 34
Service diagnosis 10.3.2 EEPROM abnormal Indoor Display E4: Indoor EEPROM error Indoor display F12: Outdoor EEPROM error; Outdoor LED1 flash 1 times Method of The Data detected by the EEPROM are used to determine MCU Malfunction Detection Malfunction When the data of EEPROM is error or the EEPROM is damaged Decision ●...
Page 35
Service diagnosis 10.3.3 Indoor DC fan motor malfunction Indoor Display Method of The rotation speed detected by the Hall IC during fan motor operation is used to determine Malfunction abnormal fan motor operation Detection Malfunction when the d etected rotation feedback signal don’t received in 2 minutes ●...
Page 37
Service diagnosis Check whether Terminal on the outdoor mainboard is well inserted. it is normal Reinsert the terminals Electrify the machine again and turn it on in The motor and the Cool state with the remote controller. outdoor pcb are check whether the motor could run.
Page 40
Service diagnosis 10.3.7 The communication fault between IPM and outdoor PCB Outdoor display: LED1 flash 4 times Method of Communication is detected by checking the IPM module and the outdoor PCB Malfunction Detection Malfunction ■ The outdoor PCB broken leads to communication fault ●...
Page 41
Service diagnosis 10.3.8 Power Supply Over or under voltage fault Outdoor display: LED1 flash 6 times The power supply is over voltage ● Method of An abnormal voltage rise or fall is detected by checking the specified voltage detection circuit. Malfunction Detection Malfunction...
Page 43
Service diagnosis 10.3.10 The communication fault between indoor and outdoor Indoor display outdoor display LED1 flash 15 times Method of Communication is detected by checking the indoor PCB and the outdoor PCB. Malfunction Detection Malfunction ■ The outdoor PCB broken leads to communication fault. Decision ■...
Page 45
Service diagnosis 10.3.11 Loss of synchronism detection Inverter side current detection is abnormal Outdoor Display LED1 flash 18 times ● LED1 flash 19 times Method of The position of the compressor rotor can not detected normally Malfunction Detection Malfunction when the wiring of compressor is wrong or the connection is poor; ●...
Page 61
Remove of front panel Outdoor unit Step Procedure Points 1.Features Loosen the service Be careful not to cover screw and cut your finger by remove the service the fins of the cover. heat exchanger Step Procedure Step Procedure Points Step Procedure Points Points 2.
Page 62
Loosen the screws of the panel. Pull and remove the front panel. Step Procedure Points Remove the fixting screws, then lift the electrical box Domestic air conditioner...
Page 63
Remove side panel Step Procedure Points ■ Loosen the fixting screws and remove the side panel. Remove the casing Step Procedure Points Loosen the fixting screws and remove the side panel. ■ Domestic air conditioner...
Step Procedure Points Loosen the fixting screws remove the fan Domestic air conditioner...
Page 65
Loosen the fixting screws and lift the fan motor. Release stepping motor (2type) Step Procedure Points Remove fixing screws,then lift the fan motor bracket Domestic air conditioner...
Page 66
Cut down and pull out compressor and remove Removal of Heat Exchanger Step Procedure Points Domestic air conditioner...
Page 67
Loosen the marked fixing screws Loosen the fixting hook remove heat exchanger Domestic air conditioner...