CM1N9270en_06
2014-06-11
Desigo™ PX
BACnet router for
• BACnet/IP
• BACnet/LonTalk
• BACnet MS/TP
Routing between BACnet/IP , BACnet/LonTalk (PXG3.L only),
·
and BACnet MS/TP
Supports BACnet/IPv4 and BACnet/IPv6
·
Compliant with ANSI/ASHRAE 135-2012 Annex J
·
Compliant with ISO 16484-5
·
BTL label (BACnet communications passed the BTL test)
·
Support for BBMD (BACnet Broadcast Management Device)
·
Support for Foreign Device
·
Configuration via Xworks Plus or Web browser (via IPv4)
·
Access to network statistics via Web browser
·
Firmware update via Ethernet and USB Device
·
LED indication for Ethernet link and activity
·
LED indication for BACnet/LonTalk and BACnet MS/TP (diagnostics)
·
2-port Ethernet switch for low-cost cabling (10/100 baseT)
·
BACnet MS/TP (RS-485) baud rates: 9600, 19200, 38400, 76800, 115200
·
Plug-in screw terminal blocks for supply, L
·
RJ45 plug for PXM20 (L
·
Operating voltage: AC 24 V or DC 24 V
·
DIN rail mounting
·
BACnet MS/TP Slave Proxy
·
SNMP (v2), MIB-2
·
BACnet NAT
·
ON
W
)
ON
ORKS
9
PXG3.L
PXG3.M
W
, and MS/TP
ORKS
Building Technologies
270

Advertisement

Table of Contents
loading

Summary of Contents for Siemens Desigo PXG3.L

  • Page 1 Desigo™ PX PXG3.L BACnet router for PXG3.M • BACnet/IP • BACnet/LonTalk • BACnet MS/TP Routing between BACnet/IP , BACnet/LonTalk (PXG3.L only), · and BACnet MS/TP Supports BACnet/IPv4 and BACnet/IPv6 · Compliant with ANSI/ASHRAE 135-2012 Annex J · Compliant with ISO 16484-5 ·...
  • Page 2: Router Functions

    BACnet router must be the same in both BACnet networks. The difference of the BACnet network is done by using different BACnet UDP ports. 2 / 10 Siemens PXG3... BACnet router for Ethernet - LONWORKS - MS/TP...
  • Page 3 Service button for identification on network (Ethernet, L ORKS terminal block (PXG3.L only) ORKS MS/TP terminal block Slider for mounting on DIN rail 3 / 10 Siemens PXG3... BACnet router for Ethernet - LONWORKS - MS/TP CM1N9270en_06 Building Technologies 2014-06-11...
  • Page 4: Button Press

    (RUN LED on, SVC LED flashes). The device has now lost any password and other settings. Only the IP network settings remain the same as before. 4 / 10 Siemens PXG3... BACnet router for Ethernet - LONWORKS - MS/TP CM1N9270en_06...
  • Page 5: Installation

    European Directive 2002/96/EC (WEEE) and may not be disposed of as domestic waste. Dispose of the devices via the proper channels. Observe all local and applicable laws. 5 / 10 Siemens PXG3... BACnet router for Ethernet - LONWORKS - MS/TP CM1N9270en_06 Building Technologies...
  • Page 6 2 x 0.6 mm dia. to 1.5 mm Screwdriver Slot screws Screwdriver, size 1 with shaft dia. ≤ 4.5 mm Max. tightening torque 0.6 Nm 6 / 10 Siemens PXG3... BACnet router for Ethernet - LONWORKS - MS/TP CM1N9270en_06 Building Technologies 2014-06-11...
  • Page 7 Color Housing RAL 7035 (light-gray) Dimensions Housing as per DIN 43880, see dimensions Weight Without/with packaging 286 g / 332 g 7 / 10 Siemens PXG3... BACnet router for Ethernet - LONWORKS - MS/TP CM1N9270en_06 Building Technologies 2014-06-11...
  • Page 8 AC24V Line max. 500mA Not connected ORKS Name Description assignment ORKS ORKS MSTP pin assignment Name Description B RS485 – A RS485 Ground RS485 8 / 10 Siemens PXG3... BACnet router for Ethernet - LONWORKS - MS/TP CM1N9270en_06 Building Technologies 2014-06-11...
  • Page 9 Dimensions All dimensions in mm 9 / 10 Siemens PXG3... BACnet router for Ethernet - LONWORKS - MS/TP CM1N9270en_06 Building Technologies 2014-06-11...
  • Page 10 10 / 10 ã 2012 - 2014 Siemens Switzerland Ltd Subject to change Siemens PXG3... BACnet router for Ethernet - LONWORKS - MS/TP CM1N9270en_06 Building Technologies 2014-06-11...

This manual is also suitable for:

Desigo pxg3.mS55842-z105-a100S55842-z106-a101

Table of Contents