Table of contents 5 Table of contents 1 Introduction to the manual Contents of this chapter ................Safety instructions ................. Target audience ..................Terms and abbreviations ................Related documents ................Cabinet-installed multidrive manuals ............Multidrive module manuals ..............2 Hardware description Contents of this chapter ................
Safety instructions for ACS880 liquid-cooled multidrive cabinets and modules (3AXD50000048633 [English]). WARNING! Note that BAMU-12C auxiliary measurement unit is used for measuring main circuit voltage. Main voltage can be present even if auxiliary circuit voltages are switched off.
Target audience This manual is intended for people who install, start-up or operate drives or multidrive modules with BAMU-12C auxiliary measurement unit. The reader is expected to know the fundamentals of electricity, wiring, electrical components and electrical schematic symbols. Terms and abbreviations...
Drive composer start-up and maintenance PC tool user’s manual 3AUA0000094606 Manuals for I/O extension modules, fieldbus adapters, safety options etc. You can find manuals on the Internet. See www.abb.com/drives/documents. For manuals not available in the document library, contact your local ABB representative. ■...
Page 10
Option manuals ACS880-1007LC liquid cooling unit user's manual 3AXD50000129607 ACX-AP-x assistant control panels user’s manual 3AUA0000085685 BAMU-12C auxiliary measurement unit hardware manual 3AXD50000117840 Drive composer start-up and maintenance PC tool user’s manual 3AUA0000094606 Drive application programming (IEC 61131-3) manual 3AUA0000127808...
Hardware description Contents of this chapter The chapter describes the hardware of BAMU-12C auxiliary measurement unit. Hardware description BAMU-12C auxiliary measurement unit is a measurement unit for precise voltage and current measurements. The unit has: • two 3-phase voltage inputs •...
Hardware description 13 Connector Description Voltage measurement connector. For pin descriptions, see section Voltage measurement connections (XU1, XU2) (page 18). Voltage measurement connector. For pin descriptions, see section Voltage measurement connections (XU1, XU2) (page 18). Current measurement connector. For pin descriptions, see section Current measurement connections (XIU, XIV, XIW) (page 19).
Installation 15 Installation Contents of this chapter The chapter instructs in installing BAMU-12C auxiliary measurement unit. Checking the delivery Check that there are no signs of damage. Check that the package contains: • measurement unit • this manual. Placing Install the module inside a cabinet/cubicle in indoor environment. Leave enough space for cabling.
16 Installation WARNING! No condensation is allowed. There are connectors that are connected to drive main circuit potential. Mechanical installation 1. Install a standard 35 × 7.5/15 mm DIN rail to the cabinet into which the unit is to be installed.
Installation 17 Electrical installation ■ Connection diagram Default use of the connectors is shown below. For further details on wiring, see the delivery-specific circuit diagrams. XPOW External power input 24 V DC SHIELD Fiber optic connections Fiber optic connector, transmitter. Connected to the control unit of the drive. Fiber optic connector, receiver.
18 Installation ■ Voltage measurement connections (XU1, XU2) Pin descriptions of connector XU1 are given in the table below. Name Description U-phase 1 Not connected V-phase 1 Not connected W-phase 1 Not connected Neutral 1 Pin descriptions of connector XU2 are given in the table below. Name Description U-phase 2...
DC-50 MBd (50 Mbd/s) ■ Connection to BCU control unit Connect BAMU-12C auxiliary measurement unit to the first unused channel of the BCU control unit with fiber optic cables. For parameter settings, see ACS880 IGBT supply control program firmware manual (3AUA0000131562 [English]).
Distances to other components 690 V AC basic insulation (8 mm [0.31 in]) from control electronics Ambient conditions BAMU-12C auxiliary measurement unit measurement unit complies with RoHS directive (2002/95/EC). Operating temperature without self-heating: 0… +70 °C (32…158 °F) Storage temperature: -40…+85 °C (-40…185 °F)
26 Technical data Related standards • Safety requirements: EN 50178 Electronic equipment for use in power installations • IEC 61800-5-1 Semiconductor power converters for adjustable frequency drive systems • UL 508 C Industrial Control Equipment • EMC emission: EN/IEC 6100-6-4:2007 Emission standard for industrial environments •...
Product and service inquiries Address any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to www.abb.com/searchchannels.