  • Page 1 SWIFT® INSTALLATION QUICK START GUIDE...
  • Page 2 STOP! Complete a site survey, which includes a Link Test and RF Scan, before continuing. REQUIRED TOOLS AND EQUIPMENT TO CREATE A MESH NETWORK Small Flathead Screwdriver Batteries SWIFT Gateway and Devices SWIFT Detector Bases CR123A 3v All SWIFT devices must be in the factory (Panasonic or Duracell) default state and updated to the current One per each device...
  • Page 3 BEFORE WIRELESS INSTALLATION Install the gateway It is recommended that the gateway be completely installed and wired before making connections to any wireless devices. The gateway is powered by either the Fire Alarm Control Panel’s SLC or by 24V power. Refer to the SWIFT Wireless system manual #LS10036-000FL-E for more information.
  • Page 4 Ensure devices are in the Factory Default state Back With the address code wheels set to 000, insert one battery into the device. The LED on the front will blink red if the device is in the factory default state. If the device is not in the factory default state, follow the directions below.
  • Page 5 PREPARE WIRELESS DEVICES Insert four batteries into the device. Tamper each device by removing the base or faceplate. Twist detectors into their bases. Use a screwdriver to set the Replace faceplates on modules. address on each device. Each device must have a different SLC address.
  • Page 6 ASSIGN A PROFILE Click Start on the home screen Insert the W-USB into your laptop’s to create a mesh network. USB port. Launch SWIFT Tools. Note: W-USB software may need to be updated before use with SWIFT Tools. SWIFT Tools will automatically update the software, if necessary.
  • Page 7 Click Create. Name the profile. In the communicator panel, select the gateway and devices to which the profile will be assigned. When the mesh is fully formed, devices that have the same profile, will be in the same mesh net- Assign a Mesh ID number between 1-255.
  • Page 8 If more devices need Once all desired devices are selected and displayed in the Assign Pro- profiles assignments, file table, click Assign. all devices in the Assign Profile table must be removed first before adding new ones. Click the X to remove devices from the Assign Profile table.
  • Page 9 For security purposes, you will be prompted for a password. If Once all devices are installed, open the profile assignment screen your gateway is unlocked, a Lock Gateway prompt will display. and click Next. This will bring you to the Mesh Formation Screen. Conversely, if your gateway is unlocked, an Unlock Gateway prompt will display.
  • Page 10 Click Start Mesh Formation. Once the mesh has formed, you can either start restructuring the mesh manually or the system will do it automatically. Mesh restructuring can take up to 6 minutes to complete. The mesh network is now forming.
  • Page 11 CONGRATULATIONS! YOU HAVE FORMED A MESH NETWORK!
  • Page 12 For additional support www.firelite.com Customer Service 203-484-7161 Technical Support 800-627-3473 firelite.tech@honeywell.com QFL-61081:B 2/11/2019...