hit counter script

Siemens SIMATIC NET RUGGEDCOM M2200 Installation Manual page 44

Rugged ethernet switches
Hide thumbs Also See for SIMATIC NET RUGGEDCOM M2200:
Table of Contents

Advertisement

IEC 61000-4-17
IEC 61000-4-18
IEC 61000-4-29
a
Siemens-specified severity levels
EMC Immunity Type Tests per IEEE 1613
Note
The RUGGEDCOM M2200 meets Class 2 requirements for an all-fiber configuration
and Class 1 requirements for copper ports. Class 1 allows for temporary communica-
tion loss, while Class 2 requires error-free and interrupted communications.
Radiated RFI
Fast Transient
Oscillatory
RUGGEDCOM M2200
Installation Manual, 03/2020, C79000-G8976-1044-16
Test
Ripple on DC
Power Supply
Damped Os-
cillatory Wave
Voltage Dips
and Interrupts
IEC 60255-5
Dielectric Strength
HV Impulse
Description
ESD
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Signal Ports
DC Power Ports
AC Power Ports
6.2 EMC and Environmental Type Tests
Description
DC Power Ports
Slow Damped
DC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Test Levels
Severity Levels
10%
2.5 kV Common
Mode on Pow-
er and Signal
1.0 kV Differential
Mode on Power
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
2 kV (Fail-Safe
Relay Output)
2 kV
2 kV
5 kV (Fail-Safe
Relay Output)
5 kV
Test Levels
±2 kV
±4 kV
±8 kV
±4 kV
±8 kV
±15 kV
35 V/m
4 kV @ 2.5 kHz
4 kV
4 kV
4 kV
2.5 kV Common Mode @ 1 MHz
2.5 kV Common
1 kV differential mode @ 1 MHz
2.5 kV Common
1 kV differential mode @ 1 MHz
Certification
3
3
 
 
 
 
 
 
 
35

Advertisement