Infra-red flicker detector

Advertisement

Possible faults
1. LED's light up during the pre-purge phase (control
box switches to lockout):
a) Sensitivity set too high
b) Stray light
c) Ignition spark visible to detector (directly or reflection).
Correct by preventing direct sight of ignition spark.
d) Interference from ignition cable (lay cables some
distance apart, or possibly screen the detector).
2. No indication from LED's after establishment of flame:
a) Incorrect or faulty wiring
b) Sensitivity set too low
c) Detector positioned wrongly (receives no light)
d) Detector or viewing window dirty
e) Defective detector
f)
IRD flange M93 defective (cracks or other mechanical
defects)
g) wrong IRD flange, special magnetic IRD flange M93
is needed.
CONNECTION OF IRD 1020.1 TO SATRONIC BURNER CONTROL BOXES
IRD
1020.1
IRD
1020.1
IRD
1020.1
SENSITIVITY –CHARACTERISTIC OF IRD 1020.1 (BLUE, WHITE)
IRD-Type
Sensitivity
blue
standard
white
increased
blue
black
brown
blue
black
brown
blue
black
brown
Characteristic
For Gas- or dual fuel burner
Immune to Ignition spark detection
For Gas- or dual fuel burner for difficult to detect flame
Immune to Ignition spark detection
3
IRD 1020.1 TERMINALS
1
brown
Control box type
TFI 812
Terminal no.
8
Terminal no.
1
Terminal no.
9
Control box type
MMI
Terminal no.
8
Terminal no.
2
Terminal no.
9
Control box type TMG 740
Terminal no.
8
Terminal no.
1
Terminal no.
20
2
black
blue
DKG 97.
DMG 97.
DLG 97.
8
8
1
2
9
9
SGU 930(i)
N
15
1