Four-shelf and zero-shelf bay assembly
Hide thumbs Also See for ONS 15454:

Advertisement

Fuse and Alarm Panel Wiring
Figure 22
The Cisco ONS 15454 bay assemblies use 4-pair, CAT 3-rated, twisted pair wire for FAP wiring. To
achieve all of the alarming capabilities of the FAP the wiring is doubled on the pins of the alarm cards.
Table 1
Log on to http://www.cisco.com/techsupport or call the Cisco Technical Assistance Center (TAC) to
report a service-affecting problem (800 553-2447).
Table 1
Wire Pair
First pair: Loss of power
White/Blue (C)-Blue/White (NO)
Second pair: Loss of power
White/Orange (C)-Orange/White (NO)
Third pair: Fuse
White/Green (C)-Green/White (NC)
Fourth pair: Fuse
White/Brown (C)-Brown/White (NC)
Fifth pair: Fuse
White/Slate (C)-Slate/White (NO)
Sixth pair: Fuse
Red/Blue (C)-Blue/Red (NO)
1. Place a jumper wire from side A1/power, pins 2 and 3 to use the first alarm for a loss of power to the A sides.
2. Place a jumper wire from side B1/power, pins 2 and 3 to use the second alarm for a loss of power to the B sides.
3. Place a jumper wire from side A/fuse, pins 4 and 5 to use the third alarm for a blown fuse condition on the
A sides.
4. Place a jumper wire from side B/fuse, pins 4 and 5 to use the fourth alarm for a blown fuse condition on the
B sides.
Place a jumper wire from side A2/power, pins 5 and 6 to use the fifth alarm for a loss of power to the A2 sides.
5.
Place a jumper wire from side B2/power, pins 5 and 6 to use the sixth alarm for a loss of power to the B2 sides.
6.
Unpacking and Installing the Cisco ONS 15454 Four-Shelf and Zero-Shelf Bay Assembly
24
FAP and power
lists the FAP wiring for each wire pair and
FAP Power Alarm Wiring
6
Figure 23
FAP Termination
Side: A1
1
Pin column: Power
Pins: 2 and 3
Side: B1
2
Pin column: Power
Pins: 2 and 3
Side: A
3
Pin column: Fuse
Pins: 4 and 5
Side: B
4
Pin column: Fuse
Pins: 4 and 5
Side: A2
5
Pin column: Power
Pins: 5 and 6
Side: B2
Pin column: Power
Pins: 5 and 6
illustrates the FAP wiring.
Environmental Termination
First environmental
termination at the bottom of
the 15454 shelf
Second environmental
termination at the bottom of
the 15454 shelf
Third environmental
termination at the bottom of
the 15454 shelf
Fourth environmental
termination at the bottom of
the 15454 shelf
Fifth environmental
termination at the bottom of
the 15454 shelf
Sixth environmental
termination at the bottom of
the 15454 shelf
78-13271-05