Fiber network module (MM) FN2007: Multi-mode transmission up to 13100 ft Two independent, electrically isolated channels SC connections for fiber optic cable Ground fault detection Trouble signaling via LED and potential-free relay contact Installation in panel Siemens Industry, Inc. A6V10315048_b_en_US Building Technologies Division 01/13/2012...
2. Screw the fiber network module (2) on the three fastening tabs (3) with three fastening screws (1) to the threaded sleeves (4) in the back box. 3. Wire up the fiber network module according to the following pin assignment. Siemens Industry, Inc. A6V10315048_b_en_US Building Technologies Division...
Power B socket, redundant power supply and error contact Fastening tab for enclosure installation Power A socket, power supply and error contact Socket A2/B2, FCnet/C-WEB circuit 2 Socket A1/B1, FCnet/C-WEB circuit 1 Siemens Industry, Inc. A6V10315048_b_en_US Building Technologies Division 01/13/2012...
Fire control panel FN2006/FN2007 Circuit 1 Line 1 Circuit 1 Line 2 X1001 Power A 24 V Power B Periphery board FCI2016 / FCI2017 Wiring of fiber network module, installed in fire control panel Siemens Industry, Inc. A6V10315048_b_en_US Building Technologies Division 01/13/2012...
Page 8
Power B FN2006/FN2007 FN2006/FN2007 Line 2 Line 1 Line 1 Line 2 Power A Power A Power B Power B Wiring example of optical network, class A with four fiber network modules Siemens Industry, Inc. A6V10315048_b_en_US Building Technologies Division 01/13/2012...
Page 9
'Power A', supply input A to fiber network module A1/B1 Electric FCnet/C-WEB connection for circuit '1' A2/B2 Electric FCnet/C-WEB connection for circuit '2' Fiber optic connection (RX), optical receiver Fiber optic connection (TX), optical transmitter Siemens Industry, Inc. A6V10315048_b_en_US Building Technologies Division 01/13/2012...
Page 10
(SAFEDLINK). Ground faults detected at <1 kΩ Total length of electrical FCnet/C-WEB wiring: Max. 3300 ft Each pair individually supervised Siemens Industry, Inc. A6V10315048_b_en_US Building Technologies Division 01/13/2012...
In the event of an error, relay contacts COM and NC are connected. Connector Terminal Plug with housing 1 2 3 4 5 Cover cap (open) C NO NC Terminal Plug without housing 360º shielding Connector power A (B) Siemens Industry, Inc. A6V10315048_b_en_US Building Technologies Division 01/13/2012...
Yellow Creation of ground fault on Flashes Ground fault on A1/B1 mirrored on A2/B2 FCnet/C-WEB circuit '2' LNK2 Green Data transmission for FCnet/C-WEB Flashes Data is being transmitted via A2/B2 circuit '2' Siemens Industry, Inc. A6V10315048_b_en_US Building Technologies Division 01/13/2012...
(corresponds to a minimum fiber length of 13100 ft FCnet/C-WEB Total length of line 3300 ft at 312 kbit/s Impedance 120 Ω Transmission mode Half-duplex Cable type Shielded and unshielded cables Siemens Industry, Inc. A6V10315048_b_en_US Building Technologies Division 01/13/2012...
Operation of this equipment in a residential area is likely to cause interference in which case the user at his own expense will be required to take whatever measures may be required to correct the interference. Siemens Industry, Inc. A6V10315048_b_en_US Building Technologies Division...