Print Log; Print Disablements - Honeywell NOTIFIER ID61 Operating Manual

Table of Contents

Advertisement

ID61/62 Series Panel - Operating Manual

4.14.1 Print Log

[U0 PRINT]
1
[U0 PRINT LOG]
Enter date range (dd/mm/yy)
- - / - - / - - to - - / - - / - -
5
Printing Event Log

4.14.2 Print Disablements

1
[U0 PRINT]
[U0 PRINT DISABLEMENTS]
5
This option prints events from the log. Proceed as follows:
1 At the Print menu, press '
to select the Log option.
1 : Log
2 : Disablements
3 : On-Demand
2 Use the numeric keypad to select the type of events
to be printed (e.g. 'All' prints all logged events, 'Fire'
prints logged fire events and so on).
1 : All
2 : Fire
4 : Pre-Alarm
5 : Test
3 Either press '
' to print all instances of the selected
5
event type, or use the numeric keypad followed by
'
' to enter a range of dates within which the event
5
type is to be printed must have occurred. The date must
be entered in the correct format (see Section 4.10.2).
4 Event data of the selected type within the selected
range is then sent to the printer.
Note: If the paper runs our while printing is in progress,
abort the current print session before changing the
paper roll and then re-select the print option.
This option prints current disablements (for previous,
logged disablements use the Log option described
above). Proceed as follows:
1 At the Print menu, press '
to select the Disablements option.
1 : Log
2 : Disablements
3 : On-Demand
2 Use the numeric keypad to select the type of
disablements to be printed.
2 : Zone
3 : Outputs
3 There are no further selections. Disablement data of
the selected type is then sent to the printer.
45
' on the numeric keypad
1
4 : Maintenance
3 : Fault
6 : Disablement
: All <:Cancel
<: Stop
' on the numeric keypad
2
4 : Maintenance
1 : Device
997-458-000-8, Issue 8