Unless otherwise specified, the warranty period for the UpS or UpS part is 36 months from the shipment date (see toshiba international Corporation bill of lading). Unless otherwise specified, the warranty period for a UPS battery is 24 months from the shipment date (see toshiba international Corporation bill of lading).
Page 5
Corporation reserves the right, without prior notice, to update information, make product changes, or discontinue any product or service identified in this publication. toshiba is a registered trademark of the toshiba Corporation. all other product or trade references appearing in this manual are registered trademarks of their respective owners.
Symbols the symbols listed below are used throughout this manual. when symbols are used in this manual they will include important safety information that must be carefully followed. 1600ep Series instruction manual Safety Alert Symbol indicates that a potential personal injury hazard exists.
ATTENTION in capital letters without the safety alert symbol indicates a potentially hazardous situation exists, if not avoided, may result in equipment and property damage. 1600ep Series instruction manual avoided,...
UpS output and the load input. the maximum ambient operating temperature is 104 °F (40 °C). Battery servicing should be performed by qualified Toshiba representative only. Unauthorized personnel should not service batteries. Contact your toshiba authorized service center for battery replacement.
ATTENTION ATTENTION misuse of this equipment may result in human injury and equipment damage. in no event will toshiba Corporation be responsible or liable for either indirect or consequential damage or injury that may result from the use of this equipment.
Application and Use toshiba 1600ep Series of on-line uninterruptible power system (UpS) provides continuous computer- grade AC power in a compact, high performance, and energy efficient unit. The UPS unit assures safe and reliable operation of critical office equipment.
It is illegal to dump lead-acid batteries in landfills or dispose of improperly. please help our earth by contacting the environmental protection agencies in your area, the battery manufacturer, or call toshiba toll-free at (877) 867-8773 for more information about recycling. (see page 47 for location) in the off position.
LED. wait for at least the minimum time indicated on the label and ensure that the CHARGE LED has gone out before opening the door of the UpS once the UpS power has been turned off. Do not attempt to disassemble, modify, or repair the UpS. Call your toshiba sales representative for repair information.
ID plate located on the rear side of the UPS unit, or in the boxes below. Date of last battery charge: 49455 WARNING 1600ep Series instruction manual This unit contains sealed lead acid batteries. Lack of preventative maintenance could result DANGER Battery fuse is always live.
1 – if aC input power is 208 Vac rated, short terminals 11 and 12 with a jumper wire. Do not jumper terminal 13 to 12 or 11. Factory Setting is 208Vac. Use the jumper wire provided by Toshiba. DO NOT add any additional jumpers.
(-3 to -15 V) to high (+3 to +15 V) Closed with normal supply power Common signal return Closed during bypass operation Closed at voltage drop Closed during inverter operation Closed at power failure (FACING CONNECTOR) in the UpS 1600ep Series instruction manual...
POWER FAILURE UPS MODE BACKUP NORMAL NORMAL OS NORMAL OS SHUTDOWN OS SHUTDOWN PROCESS UPS STOP SIGNAL FROM OS CONTINUES OUTPUT UPS OUTPUT VOLTAGE CHECKING TIME TEMPORARILY CUTS OFF THE OUTPUT FOR 10 TO 20 SECONDS 1600ep Series instruction manual...
RemotEye II Network Card the remoteye ii is an optional network card for the toshiba UpS. this card slides into a slot located on the back side (pages 47-48) of the UpS. the card provides a network, or lan-based communication interface for the UpS.
24 hrs. is necessary to obtain proper battery performance level before unit is placed in operation. 1600ep Series instruction manual 3.6 kVa (3.1 kw) (3.1 kw)
Page 24
Standard – hard wire Standard – terminal contacts only Standard (inV, byp, batt, lb, aC, Flt) Standard 6 kVa (5.1 kw) 8 kVa (6.8 kw) 50 hz 32 – 91 °F (0 – 33 °C) 2610 btU/hr 3482 btU/hr 1600ep Series instruction manual...
Page 25
Input/output figures rated for 240 volts. Output ratings given for 0.85PF are only valid when the input voltage is greater than 204 volts; otherwise, ratings given for 0.70pF are applicable. 1600ep Series instruction manual 3.6 kVa (3.1 kw) (3.1 kw) Unit enclosure is made from sheet metal meeting nema1 and Ul type 1 27.5 x 10.0 x 33.0 in.
Page 26
22 kVa (18.7 kw) 18 kVa < 5% 125 a / 277 V 18 kVa 5 min minimum minimum 288 VDC ±3% < .5 Vrms 75.0 a 225 a 1600ep Series instruction manual 22 kVa 5 min 3 min 91.6 a 275 a...
Page 27
204 volts; otherwise, ratings given for 0.70pF are applicable. at 6600 ft (2000 m) above sea level, output capacity should be derated by 3% 1600ep Series instruction manual 14 kVa (11.9 kw) 60 hz (0 – 40 °C) ; 50hz (0 – 33 °C) -20 –...
Page 28
5 x 7.3 x 18.2 in. (127 x 185 x 462 mm) enersys npX-35 51896 18 kVa (15.3 kw) 22 kVa (18.7 kw) 39.1 x 17.5 x 34.8 in. (993 x 444 x 889 mm) 1600ep Series instruction manual...
UpS is now in the bypass mode. to completely stop the UpS, turn the input breaker at the back of the UpS to the OFF position. page 32 and 33) lights green. all leD’s on the front CAUTION CAUTION 1600ep Series instruction manual...
3.6 kVa-rohS 3.6 kVa 6 kVa 8 kVa 10 kVa 14 kVa 18 kVa 22 kVa 1600ep Series instruction manual VOLTAGE CHARGING CURRENT DISCHARGE SHUT-OFF POINT PERIOD 1 PERIOD 2 RATED BATTERY VOLTAGES Vmax...
UPS’s bypass circuit back to the inverter circuit after removing the overload if set to do so (see auto-transfer setting on POWER FLOW IN BYPASS MODE FOR ALL MODELS page 39 and AUTO RETRANSFER on page 35). page 41), then the power 1600ep Series instruction manual...
(see page 25), or the circuit bypass mode (see page 24). The following figure shows the UpS condition after application of the epo switch. POWER FLOW AFTER AN EPO COMMAND FOR ALL MODELS 1600ep Series instruction manual...
Condition UpS in battery backup mode UpS low battery voltage overload Fault Shift key on the front panel (see Select AUDIBLE ALARMS audible pattern 0.5 s 0.5 s 1600ep Series instruction manual page 27).
This information is determined by the UPS operating mode and conditions. these messages are shown in the leD displays and lCD screens on pages 28 through 41. 1600ep Series instruction manual reset Shift...
UpS input aC overvoltage UpS input aC undervoltage (power failure) warning warning normal UpS (inverter) in operation Schedule/timer setting execution notice of reserved operation (5 mins. in advance) no schedule/timer setting 1600ep Series instruction manual page 31). Continue to 33).
UpS operational mode and the current percentage of the maximum UpS capacity being supplied. initially, the UpS is in bypass mode, and the following screen will appear: NOTe: If input voltage is removed while UPS is in the 1600ep Series instruction manual SCREEN ARRANGEMENT GROUPS provides operational status summary...
Page 38
BATTERY TEST BAT VOLTAGE ###% once the battery test has concluded, the lCD will return to display of the current UpS operation mode and percent load. it should appear as follows: UPS OPERATION LOAD ###% 1600ep Series instruction manual...
Start Data, timer Stop Data, weekly Schedule, Special operate, and Special off time screens then special Data Display screens are viewed. these functions can only to be changed via the serial communication interface (see 1600ep Series instruction manual page 32). inpUt Voltage...
YES then the this screen is displayed when scrolling through the Data Setting screens. interVal: 10 Day to Change: SeleCt 1600ep Series instruction manual to Change: SeleCt to Change: SeleCt to Change: SeleCt to Change: SeleCt...
Page 42
YES, the unit will automatically start up in the UpS mode (on line) when input voltage is applied, regardless of what mode it was in when shut down. Default setting is NO. 1600ep Series instruction manual...
Page 43
Set int batt tSt: no to aCCept: Set loops through both possibilities 1600ep Series instruction manual page 33) when the SHIFT/SELECT key is pressed: Shift aUto retran: yeS to Change: SeleCt Select monitor...
Page 44
CanCel. Canceling returns to the Data Settng screens menu. 12/28/2007 (mon) to Change: SeleCt returns to Day and Date Data Setting screen (with new value applied) time 12:13:58 to Change: SeleCt returns to time Data Setting screen (with new value applied) 1600ep Series instruction manual...
Page 45
1 Day to aCCept: Set interVal: 2 Day to aCCept: Set interVal: 99 Day to aCCept: Set loops through 99 possibilities 1600ep Series instruction manual page 33) when the SHIFT/SELECT key is pressed: Shift baUD rate: 1200 to Change:SeleCt monitor Select...
UpS-temp 52°C replaCe bat Soon replaCe battS reQUireS SerViCe pleaSe SerViCe 1600ep Series instruction manual leD message Meaning: the UpS is overloaded (110% or above). Unit will switch to bypass operation or amber shut down if no action is taken.
Flashes Fault 1 hr. from inverter shutdown. try restarting. if condition re-occurs plan for total shutdown and call for service. meaning/action output overvoltage condition output undervoltage condition 1600ep Series instruction manual...
4 min time to Stop 10 SeC Key loCK: en 1600ep Series instruction manual meaning/action Meaning: the UpS has automatically entered the bypass mode because it detected an output current that is larger than the inverter can normally handle.
See audible alarm Functions on page 26 inverter ol: Fault lamp off bypass ol: Fault lamp on Fault relay open; inverter ol: bypass relay closed bypass ol: bypass relay open inverter ol: yes if bypass is oK bypass ol: no 1600ep Series instruction manual...
Page 51
Shutdown – no output after Fault audible alarm Visible alarm relay Contact alarm auto-retransfer 1600ep Series instruction manual DC Circuit overvoltage DC Circuit overcurrent DC-OV Chopper malfunction inverter/chopper fault bypass operation – Chopper and inverter are stopped inverter ol – transfer to bypass yes –...
Preventive Maintenance/Parts Replacement Preventive Maintenance toshiba 1600ep Series of uninterruptible power systems have been designed to provide years of trouble- free operation requiring a minimum of preventive maintenance. the best preventive measure that the UpS user can take is to keep the area around the unit, particularly the air inlet vents, clean and free of moisture and dust accumulations.
Step 3: mount the receptacle panel attach the screws removed from the cover plate through the mounting holes of the receptacle panels and back into the UpS mounting points. mounting Screws Figure 1 1600ep Series instruction manual Figure 2...
UpS position. the UpS leD should be on and the by- pass leD oFF> turn the rUn/Stoop switch to the rUn position on the UpS. the UpS is now operating in the UpS mode. CAUTION 1600ep Series instruction manual...
Page 55
Utility panel and the load panel. the main UpS output is located on the terminal block on the back of the UpS. (tb-4(X1) and tb-7(X3) 240 VaC.) Utility panel 1600ep Series instruction manual maintenanCe bypaSS main...
(88 mm) (88 mm) (88 mm) 14 kVa 18 kVa 22 kVa 8 ea. 8 ea. 8 ea. 1.72 in. 1.72 in. 1.72 in. (43.69 mm) (43.69 mm) (43.69 mm) – – Shipping Weight Pounds Kilograms 1600ep Series instruction manual –...
Page 57
External Layout for 3.6 kVA-RoHS, 3.6 kVA, and 6 kVA units. 1600ep Series instruction manual...
Page 58
External Layout for 8 kVA, 10 kVA, 14 kVA, 18 kVA, and 22 kVA units. Display remote remote panel Contacts Contacts Snmp Snmp port port Cooling Fans terminal block Cover mCCb Front View back View back View 14/18/22 kVa 8/10 kVa 14/18 kVa 10 kVa Side View Flow 1600ep Series instruction manual...
19 mode 22 overload capacity 18 switch 19 capacitors 44 Common-mode noise 5 1600ep Series instruction manual Communication interface 12 Conduit Knock-out, sizes 48 Cooling fan 44 Data See Data Display Screens, Data Setting Screens Data Display Screens 28 29–32...
Page 60
33 monitoring normal input power supply 12 operation modes output disconnect 3 overload Capacity 18 overvoltage DC 43 input 28 output 40 peak output Current 18 power backup 5 See Data Display Screens See modes 1600ep Series instruction manual...
Page 61
20 UpS dimensions 20 wire 11 Specifications 15 Start-Up Screens 29 Starting the UpS 22 1600ep Series instruction manual Status Change indications 41 Stopping the UpS 22 Stop Signal operation 13 Storage 6 temperature 19 synchronization frequency tolerance 41...
Page 64
INDUSTRIAL DIVISION 13131 west little york road, houston, texas 77041 tel (713) 466-0277 Fax. (713) 466-8773 US (800) 231-1412 Canada (800) 872-2192 mexico 01/800/527-1204 www.toshiba.com/ind printed in the U.S.a.