Operating Instruction Power Electronic Units (Contrac) OI/PME/LME/EAN823/EBN853/EBN861-EN LME620-AI, PME120-AI (Integrated) EAN823, EBN853, EBN861 (Field-Mounting) To control Contrac actuators in the PME, LME, RHD and RSD Series...
Intended use The power electronic units for type EAI823, EAN823, EBN853 and EBN861 with the interconnection shown in these operating instructions are used to control electrical actuators in the series PME120, LME620, RHD... and RSD..Using these actuators for any other purpose will introduce a risk of personal injury and can also damage or impair the device's operational reliability.
Failure to observe this safety information may result in damage to or destruction of the product and/or other system components. IMPORTANT (NOTICE) This symbol indicates operator tips, particularly useful information, or important information about the product or its further uses. It does not indicate a dangerous or damaging situation. OI/PME/LME/EAN823/EBN853/EBN861-EN...
1.5.2 Name plates for the power electronic unit The name plates for the power electronic unit are located on the lower section (EAN823, EBN853 and EBN861, only) as well as on the cover. Since the modules are stand-alone units, order numbers may vary.
If you intend to store or transport the device for a longer time (> 6 months) we recommend that you wrap it in plastic foil and add desiccant. Protect uncovered metallic surfaces with the appropriate long-term corrosion inhibitor. The permissible long-term storage temperatures must be observed. OI/PME/LME/EAN823/EBN853/EBN861-EN...
When there is a chance that safe operation is no longer possible, put the device out of operation and secure against unintended operation. When mounting the power electronic unit in areas that may be accessed by unauthorized persons, take the required protective measures. OI/PME/LME/EAN823/EBN853/EBN861-EN...
According to EC guidelines for hazardous materials, the owner of hazardous waste is responsible for its disposal or must observe the following regulations for shipping purposes: All devices delivered to ABB Automation Products GmbH must be free from any hazardous materials (acids, alkalis, solvents, etc.).
If it is not possible to dispose of old equipment properly, ABB Service can accept and dispose of returns for a fee. 1.13.2 RoHS Directive 2002/95/EC With the Electrical and Electronic Equipment Act (ElektroG) in Germany, the European Directives 2002/96/EC (WEEE) and 2002/95/EC (RoHS) are translated into national law.
Design and function Modules The power electronic units EAN823, EBN853 and EBN861 consist of 2 housing halves, one holding the connection components and the transformer, the other holding the electronics and the commissioning and service field (ISF) for "local operation" and actuator setup.
Design and function 2.1.2 EAN823, EBN853 Fig. 6 1 Terminal box 4 Holes for cable glands 2 Electronic unit cover 5 Cover for connection space 3 Cover for commissioning and service field (ISF) Fig. 7: Connection area 1 Fuse protection against active feed at...
3 Cover for commissioning and service field (ISF) Fig. 9: Connection area 1 Commissioning and service field (ISF) 5 Motor terminals 2 Hinge screws 6 Fuse for digital outputs DO 1,DO 2, DO 3 3 Cover screws 7 Signal terminals 4 Mains supply terminals OI/PME/LME/EAN823/EBN853/EBN861-EN...
Setpoint function: Linear; setpoint = position value Setpoint input: Digital Function selection: Positioner, parameter: setpoint Positioning loop monitoring: disabled Actual output value: Digital Digital output: DO 1/2 end position signal 0 % / 100 % Operating range: not setup OI/PME/LME/EAN823/EBN853/EBN861-EN...
For information about the installation of actuators with integrated electronic unit refer to the operating instructions for linear or part-turn actuators, see 11.1 “Other applicable documents”. EAN823, EBN853 1. Fasten module on vertical support with screws of property class 8.8 (tensile strength 800...
8.8 (tensile strength 800 N/mm (116032 pounds/square inch), yield strength 640 N/mm (92826 pounds/square inch). 2. Provide adequate room for installation and make sure the actuator is accessible from all sides. 3. The cable glands point down. OI/PME/LME/EAN823/EBN853/EBN861-EN...
(2). 6. Connect the cable as described in Chapter 4.4 “Terminal connection diagrams”. 7. Check the cable connections for firm seating and fasten the cable gland. 8. Close the cover of the connection area or re-connect the connectors. OI/PME/LME/EAN823/EBN853/EBN861-EN...
To prevent interference from electromagnetic fields, the signal and power cables in the connector housing must be routed and connected separately. A metal divider separates the two cable areas inside the universal plug. Fig. 11 1 Power cable 3 Shield 2 Signal cable 4 Separator OI/PME/LME/EAN823/EBN853/EBN861-EN...
Screen at both ends up to the sub distribution board. One-sided screening ext. fuse Bus in Bus out mains in further wiring possible. Contrac actuator connection (plug) Han 24E plug termination endp. 0% endp. 100% 18 19 M00250 Fig. 13 OI/PME/LME/EAN823/EBN853/EBN861-EN...
Electrical connections 4.4.2 EAN823, EBN853, EBN861 4.4.2.1 Analog / digital Important (Notice) The electrical connection is provided by a plug on the actuator and the terminals on the electronic unit. sub distribution board mains Screen connected to both ext. fuse...
To switch the actuator to automatic mode (AUT), the following conditions must be met: • Power must be on for the digital input (DI 1). • AUT is activated via graphic user interface. • MAN is not selected via the commissioning and service field (ISF) (software version 2.00 and higher). OI/PME/LME/EAN823/EBN853/EBN861-EN...
The actuator must be switched to automatic mode (AUT) via digital input DI 1. • AUT is activated via graphic user interface. • MAN is not selected via the commissioning and service field (ISF) (software version 2.00 and higher). Fig. 19: Potential wiring for "Downstream from step controller" operation OI/PME/LME/EAN823/EBN853/EBN861-EN...
Important (Notice) The commissioning and service field is located on the electronic unit. Important (Notice) For information about how to use an engineering or configuration software refer to the additional documentation, see 11.1 “Other applicable documents”. OI/PME/LME/EAN823/EBN853/EBN861-EN...
2 button to end the user interface (software version 2.00 or adjustment process. higher) or error. By simultaneously pressing the 2 button for at least 5 seconds you can switch the actuator to manual mode (MAN). (Software version 2.00 and higher) OI/PME/LME/EAN823/EBN853/EBN861-EN...
Context-sensitive online help can be called at any time via the graphical user interface. Important (Notice) The RS232 communication cable provides a conductive ground connection between the computer and the Contrac electronic unit. If the PC is grounded, a ground loop may form in the system. OI/PME/LME/EAN823/EBN853/EBN861-EN...
Manual (MAN) mode selected via digital input or graphic user interface is indicated by LED 10 lit continuously. In order to switch to automatic (AUT) mode, apply the appropriate digital input signal and / or select AUT mode via the graphic user interface. OI/PME/LME/EAN823/EBN853/EBN861-EN...
In order for the actuator to go into automatic mode after startup, there must be a 24 V DC signal at digital input 1 for actuators with active digital input functions (default setting). If the digital input function is switched off, the actuator will switch to automatic mode immediately on completion of the setup process. OI/PME/LME/EAN823/EBN853/EBN861-EN...
The potential switch connects the reference potential either to the system or the protective ground (see page 28 Fig. 20 item 8). Name: Position A: Position B: Settings: Conventional control via analog setpoint without external electrical isolation: Conventional control via analog setpoint with external electrical isolation: Step controller control: Bus communication: OI/PME/LME/EAN823/EBN853/EBN861-EN...
Electronics Fuse type Dimensions Installation U=115 V U=230 V location EAI823 / External fuse External 16 A; time-lag EAN823 Mains fuse 5 x 20 mm in connection 6.3 A; 3,15 A; time- chamber time-lag Analog setpoint 5 x 20 mm...
Previous error messages are stored in the "Saved Errors" area in the electronic unit. Use the graphic user interface to output the stored errors. Error messages cannot be reset until the cause of the error has been eliminated. OI/PME/LME/EAN823/EBN853/EBN861-EN...
Motor / Gear Monitoring ON Integr. Behavior at critical controller temp. MAN AUT & & & & Actuator Stop Actuator Safety pos. last moves in setpoint desired operating mode Alarm Signal Saved Alarms (Reset Option) General Alarm Display ON OI/PME/LME/EAN823/EBN853/EBN861-EN...
Watchdog monitoring activated Monitoring ON & Error signal Error message via actual value ON & Saved errors (reset option) Analog output 1 to 3.5 mA with "Low alarm" 21.5 to 25 mA with "High alarm" Error display ON OI/PME/LME/EAN823/EBN853/EBN861-EN...
ISF; (if necessary disconnect from valve before) Malfunction when approaching the Actuator in limit range of positioning Drive the actuator back into the end position. sensor. operating range and connect it to the valve. Readjust the actuator for the operating range. OI/PME/LME/EAN823/EBN853/EBN861-EN...
Specifications Specifications Power Electronic Unit EAN823 (Contrac) Ingress protection IP 66 acc. to IEC 60529 / EN 60529 NEMA 4X acc. to CAN/CSA22.2 No. 94 Humidity ≤ 95% annual average; condensation not permitted Ambient temperature -25 … 55 °C (-15 … 130 °F) Transport and storage temperature -25 ...
Default setting: BA 1 (DO 1) ready for operation 0 % BA 2 (DO 2) ready for operation 100 % Individual settings See data sheet 10/68-2.40 or upon request *Full description of communication modules, see parametrization and configuration instructions 45/68-10 OI/PME/LME/EAN823/EBN853/EBN861-EN...
The version of the meter in your possession meets the requirements of the CE mark following European directives: EMC directive 2004/108/EC Low voltage directive 2006/95/EC Important (Notice) All documentation, declarations of conformity, and certificates are available in ABB's download area. www.abb.com/instrumentation OI/PME/LME/EAN823/EBN853/EBN861-EN...
Page 43
Other toxic substances Radioactive Which substances have come into contact with the device? We hereby state that the devices / components shipped have been cleaned and are free from any dangerous or poisonous substances. Town/city, date Signature and company stamp OI/PME/LME/EAN823/EBN853/EBN861-EN...
Safety information for electrical installation ....9 External fuses ............25 Saving your settings..........30 Separating the housing halves ........17 Factory default ............16 Setpoint function: .............16 Failure ..............31 Setup via user interface ...........29 Fuse type ..............33 Signals on the commissioning and service field (ISF) ................31 Fuses ...............25 OI/PME/LME/EAN823/EBN853/EBN861-EN...
Page 45
Typical commissioning with the service field (ISF) ..29 Storage conditions .............8 Storage period ............8 Warranty ..............6 Warranty provisions ...........6 Target groups and qualifications........5 Wire cross-sectional area ........25 Terminal connection diagrams......20, 22 Wire cross-sectional areas ........19 Transport..............8 Change from one to two columns OI/PME/LME/EAN823/EBN853/EBN861-EN...